Trane codes

Trane

CO2 ERR

Protect

CO2 SENS ERR (JADE LCD example)

JADE LCD: CO2 / SENS ERR. DCV sensor failed or the 0–10 V input is floating. Damper holds open; compressor never runs.

Walk CO2 ERR in Diagnose

2 plates — walk the one on the cabinet

First check

1 Damper position vs command

On Trane YHC look at the economizer before the compressor. Commanded open? Blade actually open? Linkage off the shaft is a rooftop weekly. Read CO2 in an empty space. 400–800 ppm typical empty retail. 2000 ppm empty is a failed sensor.

Expect: Blade matches the module command. Stuck open = overventilation. Stuck closed = no free cooling.

The rest of the walkthrough is Diagnose.

On the plates

  • Read CO2 in an empty space. 400–800 ppm typical empty retail. 2000 ppm empty is a failed sensor.
  • 0–10 V at the DCV input vs the sensor. If DCV is unused, set the input OFF on JADE.

Plates that use CO2 ERR

Same number, other makers

CO2 ERR on Trane is not the same code on these plates.