CO2 ERR
ProtectCO2 SENS ERR (JADE LCD example)
JADE LCD: CO2 / SENS ERR. DCV sensor failed or the 0–10 V input is floating. Damper holds open; compressor never runs.
Walk CO2 ERR in Diagnose
Sign in for the next measurement
First check
1 Damper position vs command
On Goodman GPG16 look at the economizer before the compressor. Commanded open? Blade actually open? Linkage off the shaft is a rooftop weekly. Read CO2 in an empty space. 400–800 ppm typical empty retail. 2000 ppm empty is a failed sensor.
Expect: Blade matches the module command. Stuck open = overventilation. Stuck closed = no free cooling.
The rest of the walkthrough is Diagnose.
On the plates
- Read CO2 in an empty space. 400–800 ppm typical empty retail. 2000 ppm empty is a failed sensor.
- 0–10 V at the DCV input vs the sensor. If DCV is unused, set the input OFF on JADE.