Trane
Fan fail
LockoutReliatel fan fail
Indoor fan did not prove.
Walk Fan fail in Diagnose
2 plates — walk the one on the cabinet
First check
1 Write the live code and watch one cycle
On Trane YHC read Reliatel — Precedent YHC before you pull power. Write Fan fail exactly. Watch one full sequence and note which step dies. YHC often has a different motor/VFD than YSC. Use this blower table.
Expect: Call: Occupied / G starts the indoor fan. Y1 is cool. W is gas heat. They are different boards in the same box.
The rest of the walkthrough is Diagnose.
On the plates
- Belt, ECM, or the proving pressure switch / current sensor.
- VFD limp mode can drop static below the prove setpoint. That is not a bad RTRM.
- YHC often has a different motor/VFD than YSC. Use this blower table.