Heat fail
LockoutReliatel heat fail
Heat section did not prove.
Walk Heat fail in Diagnose
2 plates — walk the one on the cabinet
First check
1 Write the live code and watch one cycle
On Trane YHC read Reliatel — Precedent YHC before you pull power. Write Heat fail exactly. Watch one full sequence and note which step dies. Ignition module path. Reliatel reports the fail — the IGC/IGN still has the LED.
Expect: Call: Occupied / G starts the indoor fan. Y1 is cool. W is gas heat. They are different boards in the same box.
The rest of the walkthrough is Diagnose.
On the plates
- W at Reliatel, then the ignition module in the heat section.
- Inducer, PS, HSI, valve, flame — same physics as any packaged IGC, Reliatel just reports ‘heat fail.’
- Do not replace RTRM because a rollout is open.
- Ignition module path. Reliatel reports the fail — the IGC/IGN still has the LED.