Amana
3 flash
LockoutPS open, inducer on
Draft / trap / hose / inducer.
Walk 3 flash in Diagnose
Sign in for the next measurement
First check
1 Prove inducer and the live code
Do not pull power — that clears the Amana AM9S96 active code. Write 3 flash. Is the inducer spinning on this call? Silent inducer is not a pressure switch. Trap, collector, and vent first — these 96%s drown a collector overnight.
Expect: 120 VAC at the inducer on a heat call. Wheel turning.
If fail: 120 VAC missing → IFC / door switch / incoming power. Voltage + dead motor → inducer.
If pass: Inducer running + this code → trap, hose, switch, vent (step 2).
The rest of the walkthrough is Diagnose.
On the plates
- Trap, collector, and vent first — these 96%s drown a collector overnight.
- Inducer 120 VAC and spinning.
- Hose dry and on the only collector tap.
- If the PS closes and the IFC still 3-flashes, the IFC input is the fault.
Plates that use 3 flash
Same number, other makers
3 flash on Amana is not the same code on these plates.