Goodman
3 flash
LockoutPS open
Metal-vent draft not proven.
Walk 3 flash in Diagnose
5 plates — walk the one on the cabinet
First check
1 Prove inducer and the live code
Do not pull power — that clears the Goodman GMS80 active code. Write 3 flash. Is the inducer spinning on this call? Silent inducer is not a pressure switch. Cap, liner, common-vent tables, inducer wheel.
Expect: 120 VAC at the inducer on a heat call. Wheel turning.
If fail: 120 VAC missing → IFC / door switch / incoming power. Voltage + dead motor → inducer.
If pass: Inducer running + this code → trap, hose, switch, vent (step 2).
The rest of the walkthrough is Diagnose.
On the plates
- Trap and collector first — these 96%s drown overnight.
- Inducer 120 VAC and spinning. Hose on the only collector tap.
- PVC intake/exhaust, bird screen, ice, wind.
- Trap and collector first. 92% still makes condensate.
- Inducer 120 VAC, hose on the only tap, PVC termination.
- Cap, liner, common-vent tables, inducer wheel.
- PS hose on the inducer housing — flue condensate on a long metal run, not a 96% collector.
- Do not cut a PVC trap that does not exist.
Plates that use 3 flash
Same number, other makers
3 flash on Goodman is not the same code on these plates.