Models
Goodmanfurnace

GRVS80-U

Ultra-low NOx · single-stage · 80% · SCAQMD / SJV

Goodman California ultra-low NOx 80% (GRVS80-U and cousins). Premix / metal-fiber burner, not the 40 ng/J Low-NOx wrinkle-bend used on GR9S80. Draft and limit language can look like GMS80 — the burner and gas train do not. Confirm the -U plate and the ULN conversion kit before you treat it as a standard 80%.

Not GR9S80 / GMS80 standard Low-NOx. Not GRVS96-U / CDVS96-U (96% ULN). Not a 50A55 drop-in just because it is 80%.

NOx

SCAQMD / SJV ultra-low NOx — not 40 ng/J Low NOx

AFUE

80% · Category I metal vent

Burner

Premix / metal-fiber ULN. Different orifices, different LP path.

This board

Single-stage LED IFC (80%)

  • Same 1–9 meanings as GMSS96. Physics do not match.
  • 3-flash = metal-vent draft, not a drowned 96% collector.
  • 6-flash rollout is still a hazard. 4-flash is still the dirty A-coil on top of an 80%.

Flashes until power is pulled. Write the count first.

Universal swap

No universal

Ultra-low NOx premix. No published universal. Not a 50A55 80% drop-in.

Silk: GRVS80-U

White-Rodgers

ICM

Honeywell

  • 50A55-843 ‘because 80%’. GR9S80 standard Low-NOx board.

After you pull the dead card

  1. 1OEM ULN IFC. Do not convert the premix burner.

Field wiring

Written landings for Goodman GRVS80-U. Not a factory schematic.

Furnace · single-stage 24V
R / C / W / Y / GGas furnace

Conventional single-stage furnace IFC. One W. Cool Y passes through to the outdoor. No ComfortBridge, no ABCD, no W2.

Written circuit description only — FieldBench does not redraw maker schematics. Example: R to W closes on a heat call; verify 24V at W1 before you change the IFC.

Open manufacturer PDF

Heat sequence

  1. 1Power. L1 / N → IFC → transformer → R120V in, 24V out
  2. 2Call. Stat W → IFC W~24 VAC
  3. 3Draft. IFC → inducer → PS close120V motor, 24V prove
  4. 4Ignite. IFC → HSI120 VAC
  5. 5Gas. IFC → valve~24 VAC
  6. 6Flame. Rod → IFCµA DC
  7. 7Blow. IFC → heat speedAfter flame prove

This indoor

ULN 80% 9-speed. Still 24V W/Y. Not ComfortBridge.

24V single-stage heat

Door card is one-stage. Twin terminal empty unless the job is actually twinned.

Wall thermostat

Single-stage heat/cool. W2 from a leftover two-stage stat does nothing useful.

  • R24V hot from the IFC24V
  • CCommon24V
  • WHeat24V
  • YCool — also starts the outdoor24V
  • GFan24V

Furnace IFC

Transformer lives here. Y out to the outdoor contactor. TWIN empty on a standalone.

  • RHot to the stat24V
  • CCommon — must reach the outdoor24V
  • WHeat call24V
  • YCool in / cool out24V
  • GBlower24V
  • TWINEmpty unless twinned24V

Landing

  • 24VIFC Rstat R

    ~24 VAC hot

  • 24VIFC Cstat Coutdoor C

    Common

  • 24VStat WIFC W

    Heat. Stays in this cabinet.

  • 24VStat YIFC Youtdoor Y

    Cool / contactor

  • 24VStat GIFC G

    Fan. Does not go outdoors.

IFC harness — single-stage heat

After W arrives. This is the gas train, not the thermostat strip.

Transformer + fuse

120V primary. 24V secondary. Dark stat = fuse / door / transformer first.

  • L1 / N120V to the IFCLine
  • XFMR24V to R24V
  • FUSEOn the IFC24V

24V safety chain

Door, limit, rollout in series. Open anywhere kills heat.

  • DOORInterlock24V
  • LIMITMain limit — rise / no airflow24V
  • ROLLOUTManual reset. Do not jumper and leave24V

Inducer + one pressure switch

W → inducer 120V → PS closes → IFC continues. One hose, one switch.

  • IND120V from the IFC to the inducerLine
  • PS24V prove back to the IFC24V
  • HOSESingle hose. Do not add a second because two-stage boards have two.24V

HSI + single valve

Igniter is 120V from the IFC. Valve is 24V. Flame rod is µA DC back to the IFC.

  • HSI120V hot-surface igniter — not 24VLine
  • VALVE24V to the single solenoid24V
  • FLAMEµA DC on the rod. Not a 24V circuit24V

9-speed tap ECM

F01–F09 on the harness. Heat tap and cool tap are separate. Not a 14-pin serial motor and not a run cap.

  • F01–F09Speed taps on the IFC / harness24V
  • HEATDefault often F02 — F01 is an E3 generator on many 9-speed doors24V
  • COOL / Y / GCool tap. Wrong tap freezes the coil and looks like LPS outdoors.24V

Landing

  • LineL1IFCinducer

    120 VAC after W

  • 24VIFCPSIFC

    ~24 VAC prove. Open PS = no ignition.

  • LineIFCHSI

    120 VAC during trial

  • 24VIFCgas valve

    ~24 VAC after flame prove starts

  • 24VFlame rodIFC

    µA DC. Not 24V.

  • LineIFCblower

    IFC heat speed / tap

Prove it

  • 24 VAC from R to C at the IFC. Fuse / transformer first if the stat is dark.
  • W at the IFC under a heat call. Then inducer / igniter / valve per THIS door card.

Do not

  • Do not land a ComfortBridge 1/2 or Infinity ABCD pair on this IFC.
  • Do not hunt W2 / E8 / high-fire on a one-stage door.
  • TWIN must be empty on a standalone.

9-speed tap, PSC, and CT motors share this thermostat landing. The motor is on the IFC harness diagram.

Sequence

  1. 1

    W

    Inducer → metal-vent PS → HSI → valve → flame → blower. Chimney and common vent matter.

Faults on this IFC

Step 1, then 2, then 3. Expected reading and the fail branch sit under each check.

3 flash

PS open

lockout

Metal-vent draft not proven.

  1. 1 Prove inducer and the live code

    Do not pull power — that clears the Goodman GRVS80-U active code. Write 3 flash. Is the inducer spinning on this call? Silent inducer is not a pressure switch. Cap, liner, common-vent tables, inducer wheel.

    Expect: 120 VAC at the inducer on a heat call. Wheel turning.

    If fail: 120 VAC missing → IFC / door switch / incoming power. Voltage + dead motor → inducer.

    If pass: Inducer running + this code → trap, hose, switch, vent (step 2).

  2. 2 Trap, collector, and the hose

    A drowned 96% trap will not make collector pressure. Pull the trap, flush it, confirm the collector box and inducer outlet are not full. Hose cracked, off the port, or full of water fakes an open switch. PS hose on the inducer housing — flue condensate on a long metal run, not a 96% collector.

    Expect: Trap flowing, hose dry and downhill, ports not swapped on a two-switch board.

  3. 3 Switch ohms, then vent load

    Ohm the pressure switch: NO, must close when that inducer speed is making the collector setpoint. If the switch is good, walk the PVC — bird screen, ice, long 2" run, wind, shared chase. Do not cut a PVC trap that does not exist.

    Expect: Switch closes on known draft. Vent unrestricted.

    If fail: Replace the open switch only after the vent and trap are proven.

    If pass: Switch closes on draft and the code stays → IFC input.

4 flash

Limit

warn

Airflow. 80% coils still dirty.

  1. 1 Airflow before you touch the limit

    On Goodman GRVS80-U a limit is airflow or overfire until proven otherwise. Do not replace the limit first. Filter, blower wheel, A-coil, and the heat-speed setting for THIS motor (tap, model plug, or communicating CFM — not a sister SKU chart). Filter, heat tap, A-coil on top.

    Expect: Rise in the rating-plate window. Static vs this cabinet’s blower chart.

  2. 2 Measure static and temperature rise

    Total external static vs the Goodman GRVS80-U blower chart for this cabinet size. Supply minus return rise after 8–10 minutes. A new 5" media cabinet or closed supplies will trip this all winter.

    Expect: Rise typically 35–65 °F — rating plate wins.

    If fail: Fix the restriction or the heat-speed setting. The limit is doing its job.

    If pass: Airflow in range → step 3 (overfire / limit itself).

  3. 3 Overfire, then the limit circuit

    Clock the meter / manifold on the stage that is tripping vs the rating plate. Then ohm the limit after it cools — a limit that never recloses is failed. Rollout in the same circuit is a different call (see rollout on this door card).

    Expect: Manifold on plate. Limit closed when cool.

6 flash

Rollout

hazard

Flame containment.

  1. 1 Treat this as flame outside the exchanger

    Do not reset the Goodman GRVS80-U rollout and walk away. Write the code, kill the call, and look for flame at the burners, crossover, and vestibule before you do anything else.

    Expect: No flame outside the exchanger. Burners seated. Crossover lit.

    If pass: Still inspect secondary / flue / condensate before you reset.

  2. 2 Secondary, condensate, and flue

    Blocked secondary, drowned collector, or a plugged flue pushes flame out the front. Pull the inducer/collector look, confirm the trap is flowing, and check PVC/vent. Exchanger, burners, flue. Reset only after cause.

    Expect: Dry collector, open flue, trap clear.

  3. 3 Reset only after the cause is fixed

    Manual-reset rollout. Recurring rollout on Goodman GRVS80-U is a CO / fire call — cracked primary, misaligned burners, or a failed secondary. Confirm CO in the space before you leave.

    Expect: One clean cycle after the cause is fixed. No second reset as a repair.

7 / 8 flash

Flame / igniter

warn

Rod or HSI.

  1. 1 Ohms at the igniter, then at the IFC

    On Goodman GRVS80-U measure cold ohms at the igniter plug, then at the IFC connector. An open at the plug is the element or local harness. Open only at the IFC is the harness rub-through on the collector. µA, nitride or Norton per this cabinet, gas.

    Expect: Nitride cold ohms per THIS door sticker — do not use an 80% Norton chart.

  2. 2 120 VAC during warm-up

    Call for heat and measure 120 VAC at the igniter during the warm-up window. 0 V + good ohms = IFC igniter relay. Voltage + no glow = cracked nitride.

    Expect: 120 VAC only during warm-up. Visible glow before the valve opens.

  3. 3 Do not keep cycling a cracked element

    A cracked nitride can ohm ‘good’ cold and open hot. If ohms and voltage are good and there is no glow, replace the igniter. Confirm polarity/ground (this plate’s polarity code) before you condemn a new igniter.

    Expect: One clean light after a known-good igniter and a proven ground.

Workflows

No heat on GRVS80-U

SCAQMD / SJV job, 80% Goodman.

  1. 1 Prove the call and the live code

    Confirm the -U / ULN plate. A standard GR9S80 LP kit is the wrong carton.

    Expect: Write whatever Single-stage LED IFC (80%) is showing. Flashes until power is pulled. Write the count first.

    If fail: No call at the IFC → stat / harness. Do not change gas parts.

  2. 2 Isolate the first failed step in the sequence

    Premix burner: look at the ULN gas train and the burner face, not a wrinkle-bend crossover.

    Expect: The first dead output or open prove.

  3. 3 Confirm with a number, then the next part

    Draft is still metal-vent. 3-flash / PS open is chimney / inducer, not a trap. Do not drill or ‘open up’ a ULN burner to make it light. That voids the listing.

    Expect: Vent: Cat I. Spillage is a fail.

    If fail: Stay on this plate. The out-of-range reading is the part.

    If pass: Reading in range → the next step in this workflow is the repair.

Test points

Vent

Cat I. Spillage is a fail.

Gotchas

  • 40 ng/J Low-NOx (most GR9 / GM plates) is not SCAQMD ultra-low NOx. Wrong kit, wrong orifices, failed inspection.
  • CDVS96-U is the 96% ULN cousin — collector and trap exist there.

Related plates

Install this plate

Install Goodman GRVS80-U as Ultra-low NOx · single-stage · 80% · SCAQMD / SJV.

Ultra-low NOx · single-stage · 80% · SCAQMD / SJV

This plate — not the sister SKU

  • Not GR9S80 / GMS80 standard Low-NOx. Not GRVS96-U / CDVS96-U (96% ULN). Not a 50A55 drop-in just because it is 80%.
  • 40 ng/J Low-NOx (most GR9 / GM plates) is not SCAQMD ultra-low NOx. Wrong kit, wrong orifices, failed inspection.
  • CDVS96-U is the 96% ULN cousin — collector and trap exist there.

IFC on this door

  • Same 1–9 meanings as GMSS96. Physics do not match.
  • 3-flash = metal-vent draft, not a drowned 96% collector.
  • 6-flash rollout is still a hazard. 4-flash is still the dirty A-coil on top of an 80%.

Hardware

  • NOx: SCAQMD / SJV ultra-low NOx — not 40 ng/J Low NOx
  • AFUE: 80% · Category I metal vent
  • Burner: Premix / metal-fiber ULN. Different orifices, different LP path.

First fire

  1. 1Confirm the -U / ULN plate. A standard GR9S80 LP kit is the wrong carton.
  2. 2Premix burner: look at the ULN gas train and the burner face, not a wrinkle-bend crossover.
  3. 3Draft is still metal-vent. 3-flash / PS open is chimney / inducer, not a trap.
  4. 4Do not drill or ‘open up’ a ULN burner to make it light. That voids the listing.

Do not on Goodman GRVS80-U

  • Not GR9S80 / GMS80 standard Low-NOx. Not GRVS96-U / CDVS96-U (96% ULN). Not a 50A55 drop-in just because it is 80%.
  • 40 ng/J Low-NOx (most GR9 / GM plates) is not SCAQMD ultra-low NOx. Wrong kit, wrong orifices, failed inspection.
  • CDVS96-U is the 96% ULN cousin — collector and trap exist there.

Maker literature

FieldBench does not host manufacturer files. Each link opens the maker’s own literature page in a new tab.

  • Goodman literature libraryLiterature searchSearch the exact plate (GR9T960804CN, GR9S960603BN). Full I/O PDFs are often dealer-gated.Open manufacturer PDF
  • Goodman literature libraryLiterature searchSearch Goodman GRVS80-U on the maker’s literature page.Open manufacturer PDF

Warranty and bulletins

Affected models, serial range, symptom, remedy, date. Maker files open on the manufacturer site.

All bulletins
  • PWCFURNUQNTE

    warranty sheet

    Goodman gas furnace limited warranty — unit-replacement certificate

    Registered furnace — parts / heat exchanger / unit replacement terms · Limited warranty certificate

  • Dealer portals

    dealer

    Where remaining service letters live

    Current-year service letters not on a public literature page · Maker dealer portal