AM9S96
Single-stage · multi-speed · 96% AFUE
Single-stage 96% with one pressure switch and a flash-code or simple 7-seg IFC. Use the 1–9 flash chart. Do not apply AR9T96 E8/E9 high-fire codes — there is no high-fire switch. Do not apply AR9S96 0140F20003-B E0–E7 (that is the current 9-speed 7-seg single). Do not apply AMVC96 / ARVT96 ComfortBridge E/b/d codes.
Not AR9T96 (two-stage, dual PS, 7-seg E1–E9). Not AR9S96 (current single-stage 9-speed, 0140F20003-B, E0–E7 — not this flash card). Not ARVT96 / AMVC96 (communicating VS). GMSS96 is the Goodman-badge single-stage chart — same flash family, different listing.
Input / AFUE
Up to 96% · 40–120 kBtu family · single-stage heat
Staging
Single-stage gas valve · single-speed inducer · one pressure switch
Blower
Multi-speed ECM or PSC depending on exact SKU
Heat exch.
Stainless tubular primary + stainless secondary
Ignition
120 VAC silicon nitride HSI
Vent
PVC 2-pipe or 1-pipe
Tstat
Conventional 24V · W Y G R C
Sister SKU
AMH96 · Goodman GM9S96 same flash family · GMSS96 lives on the Goodman chart
This board
Single-stage IFC · red LED flash or basic 7-seg
- Count flashes between the long pause. Rapid flash is polarity, not ‘code 10’.
- LED off = no 120/24. LED steady on (some revs) = idle with 24 V present.
- One pressure switch only. 2-flash closed-with-inducer-off, 3-flash open-with-inducer-on.
- Do not read this as an AR9T96 E-code card or an AMVC96 triple-7-seg menu.
Last fault often repeats until power is cycled. Write it first.
Universal swap
Older Amana single-stage. If the silk is PCBBF110/112/123 or B18099-26, ICM2811 is the carton.
Silk: PCBBF110 · PCBBF112 · PCBBF123 · B18099-26 · 0130F00005 · B18099-13
White-Rodgers
- 50M56U-843
If the dead board is already a 50A55/50A65/50M56 single-stage HSI, the WR/ICM2812 kit is the universal path.
ICM
Honeywell
- S9200U1000
Resideo S9200U1000 lists Goodman/Amana B18099-06/08/10/13 and 102077-xx. Not PCBBF110/123 and not a 9-speed tap.
- AR9S96 0140F20003-B thinking — that is a 9-speed E0–E7 card, not this LED flash plate.
- ComfortBridge boards.
After you pull the dead card
- 1Kill power. Photograph the silk-screen part number on the dead board before you pull it.
- 2Match staging (1 vs 2 vs modulating), igniter (carbide / nitride / spark), and motor (PSC / ECMx / 9-speed tap / serial VS).
- 3Set heat-off delay and any 80+/90+ jumper to the door card. Prove one full try and flame µA before you leave.
Field wiring
Written landings for Amana AM9S96. Not a factory schematic.
Conventional single-stage furnace IFC. One W. Cool Y passes through to the outdoor. No ComfortBridge, no ABCD, no W2.
Written circuit description only — FieldBench does not redraw maker schematics. Example: R to W closes on a heat call; verify 24V at W1 before you change the IFC.
Open manufacturer PDFHeat sequence
- 1Power. L1 / N → IFC → transformer → R120V in, 24V out
- 2Call. Stat W → IFC W~24 VAC
- 3Draft. IFC → inducer → PS close120V motor, 24V prove
- 4Ignite. IFC → HSI120 VAC
- 5Gas. IFC → valve~24 VAC
- 6Flame. Rod → IFCµA DC
- 7Blow. IFC → heat speedAfter flame prove
This indoor
Older flash 96%. LED 1–9. Still one W.
24V single-stage heat
Door card is one-stage. Twin terminal empty unless the job is actually twinned.
Wall thermostat
Single-stage heat/cool. W2 from a leftover two-stage stat does nothing useful.
- R24V hot from the IFC24V
- CCommon24V
- WHeat24V
- YCool — also starts the outdoor24V
- GFan24V
Furnace IFC
Transformer lives here. Y out to the outdoor contactor. TWIN empty on a standalone.
- RHot to the stat24V
- CCommon — must reach the outdoor24V
- WHeat call24V
- YCool in / cool out24V
- GBlower24V
- TWINEmpty unless twinned24V
Landing
- 24VIFC Rstat R
~24 VAC hot
- 24VIFC Cstat Coutdoor C
Common
- 24VStat WIFC W
Heat. Stays in this cabinet.
- 24VStat YIFC Youtdoor Y
Cool / contactor
- 24VStat GIFC G
Fan. Does not go outdoors.
IFC harness — single-stage heat
After W arrives. This is the gas train, not the thermostat strip.
Transformer + fuse
120V primary. 24V secondary. Dark stat = fuse / door / transformer first.
- L1 / N120V to the IFCLine
- XFMR24V to R24V
- FUSEOn the IFC24V
24V safety chain
Door, limit, rollout in series. Open anywhere kills heat.
- DOORInterlock24V
- LIMITMain limit — rise / no airflow24V
- ROLLOUTManual reset. Do not jumper and leave24V
Inducer + one pressure switch
W → inducer 120V → PS closes → IFC continues. One hose, one switch.
- IND120V from the IFC to the inducerLine
- PS24V prove back to the IFC24V
- HOSESingle hose. Do not add a second because two-stage boards have two.24V
HSI + single valve
Igniter is 120V from the IFC. Valve is 24V. Flame rod is µA DC back to the IFC.
- HSI120V hot-surface igniter — not 24VLine
- VALVE24V to the single solenoid24V
- FLAMEµA DC on the rod. Not a 24V circuit24V
PSC blower + run cap
Heat / cool / park taps on the motor. The cap is on this blower — not the outdoor dual can.
- HEATHeat speed tap24V
- COOLCool speed tap24V
- PARKUnused leads parked24V
- CAPRun capacitor on the blowerCap
Landing
- LineL1IFCinducer
120 VAC after W
- 24VIFCPSIFC
~24 VAC prove. Open PS = no ignition.
- LineIFCHSI
120 VAC during trial
- 24VIFCgas valve
~24 VAC after flame prove starts
- 24VFlame rodIFC
µA DC. Not 24V.
- LineIFCblower
120V tap + cap
Prove it
- 24 VAC from R to C at the IFC. Fuse / transformer first if the stat is dark.
- W at the IFC under a heat call. Then inducer / igniter / valve per THIS door card.
Do not
- Do not land a ComfortBridge 1/2 or Infinity ABCD pair on this IFC.
- Do not hunt W2 / E8 / high-fire on a one-stage door.
- TWIN must be empty on a standalone.
9-speed tap, PSC, and CT motors share this thermostat landing. The motor is on the IFC harness diagram.
Sequence
- 1
W
Inducer on → single PS closes → HSI → valve → flame → blower delay.
- 2
Prove
One NO pressure switch. Already closed with inducer off → 2-flash. Never closes → 3-flash.
- 3
No W2 path
There is no high-fire prove. A ‘W2’ wire is unused or tied for an AC stage, not furnace high fire.
Faults on this IFC
Step 1, then 2, then 3. Expected reading and the fail branch sit under each check.
1 flash
Retry lockout
Ignition retries exceeded.
1 Watch one full try — do not reset
Write the Amana AM9S96 code. Watch inducer, HSI glow, valve click, flame, µA. The step that dies is the repair. Resetting only burns another try into a harder lockout. Watch one full try: inducer, HSI glow, valve click, flame.
Expect: W → Prove → No W2 path
2 Gas and the valve
Cock open, inlet pressure, then manifold on the stage that is failing vs the rating plate. 24 VAC at the valve during trial? Coil ohms? A valve that never opens looks like a ‘bad igniter’ if you did not watch the sequence. Gas cock, manifold vs plate, orifice.
Expect: Manifold: Single-stage plate value only — no low/high pair.
3 Flame prove, then the lockout timer
Glow + valve + no prove → rod, ground, or IFC sense. Prove then drop → µA / PS / limit. Soft lockouts on this family often auto-reset on a long clock — do not sit on resets. Rod µA and chassis ground.
Expect: Flame rod: µA per this door card. Rising while running is the goal.
2 flash
PS closed, inducer off
Single switch welded or IFC input shorted.
1 Unplug the switch with the inducer off
On Amana AM9S96 this code is the switch made when the inducer is not running. Unplug that switch only. Unplug the only PS. Code change = switch or water in the hose.
Expect: Code changes when the harness is open.
If fail: Wrong switch, or the IFC input is shorted.
If pass: Switch/hose path. Go to step 2.
2 Water in the hose vs a welded switch
Blow the hose. Water holding residual draft is more common than a welded switch. Confirm the hose is not teed and not routed uphill. Ohm the switch with the hose off. Hose routed downhill? Residual draft fakes closed.
Expect: Hose empty. Switch opens with no draft.
3 IFC input last
If the switch ohms open, the hose is dry, and the code does not change with the harness off, the Amana AM9S96 IFC input is shorted. Do not keep swapping switches. IFC input shorted — only after the switch ohms open.
Expect: Known-good open switch + open harness = code gone. If not, IFC.
3 flash
PS open, inducer on
Draft / trap / hose / inducer.
1 Prove inducer and the live code
Do not pull power — that clears the Amana AM9S96 active code. Write 3 flash. Is the inducer spinning on this call? Silent inducer is not a pressure switch. Trap, collector, and vent first — these 96%s drown a collector overnight.
Expect: 120 VAC at the inducer on a heat call. Wheel turning.
If fail: 120 VAC missing → IFC / door switch / incoming power. Voltage + dead motor → inducer.
If pass: Inducer running + this code → trap, hose, switch, vent (step 2).
2 Trap, collector, and the hose
A drowned 96% trap will not make collector pressure. Pull the trap, flush it, confirm the collector box and inducer outlet are not full. Hose cracked, off the port, or full of water fakes an open switch. Inducer 120 VAC and spinning.
Expect: Trap flowing, hose dry and downhill, ports not swapped on a two-switch board.
3 Switch ohms, then vent load
Ohm the pressure switch: NO, must close when that inducer speed is making the collector setpoint. If the switch is good, walk the PVC — bird screen, ice, long 2" run, wind, shared chase. Hose dry and on the only collector tap.
Expect: Pressure switch: One NO switch. Closed only after inducer is up.
If fail: Replace the open switch only after the vent and trap are proven.
If pass: Switch closes on draft and the code stays → IFC input.
4 flash
Open limit
Airflow or overfire.
1 Airflow before you touch the limit
On Amana AM9S96 a limit is airflow or overfire until proven otherwise. Do not replace the limit first. Filter, blower wheel, A-coil, and the heat-speed setting for THIS motor (tap, model plug, or communicating CFM — not a sister SKU chart). Filter, coil, return, heat-speed tap. A 96% coil on a low heat tap will limit.
Expect: Heat tap / rise: Match the installer’s tap to the rise range on the rating plate (typically 35–65°F).
2 Measure static and temperature rise
Total external static vs the Amana AM9S96 blower chart for this cabinet size. Supply minus return rise after 8–10 minutes. A new 5" media cabinet or closed supplies will trip this all winter. Rise vs rating plate.
Expect: Heat tap / rise: Match the installer’s tap to the rise range on the rating plate (typically 35–65°F).
If fail: Fix the restriction or the heat-speed setting. The limit is doing its job.
If pass: Airflow in range → step 3 (overfire / limit itself).
3 Overfire, then the limit circuit
Clock the meter / manifold on the stage that is tripping vs the rating plate. Then ohm the limit after it cools — a limit that never recloses is failed. Rollout in the same circuit is a different call (see rollout on this door card). Clock the meter — overfire trips limits with a clean filter.
Expect: Manifold: Single-stage plate value only — no low/high pair.
5 flash
Flame with valve off
Leaking valve or false flame sense.
1 Shut the gas cock first
On Amana AM9S96 the rod sees flame with the valve de-energized. Shut the cock. If flame stays, the valve is leaking — replace it. Do not jump or energize it as a test. Shut the gas cock. If flame stays, leaking valve — replace, do not jump.
Expect: Flame dies when the cock is shut.
If fail: Leaking valve. Replace. Do not leave the unit.
2 Rod and IFC flame circuit
If flame dies with the cock shut, the rod is shorted to ground or the IFC flame circuit is lying. Unplug the rod, inspect ceramic, and check the harness for a rub-through on the collector. Rod shorted to ground or IFC flame circuit.
Expect: Rod isolated from ground. IFC does not report flame with the rod unplugged.
3 Confirm valve solenoids are actually off
Measure 24 VAC at both solenoids after the call drops. A welded IFC relay or a shorted W will keep a solenoid wet and look like ‘unexpected flame.’ Replace the IFC only after the valve and rod are proven.
Expect: 0 VAC at both solenoids after the call. No flame.
6 flash
Rollout open
Flame containment.
1 Treat this as flame outside the exchanger
Do not reset the Amana AM9S96 rollout and walk away. Write the code, kill the call, and look for flame at the burners, crossover, and vestibule before you do anything else.
Expect: No flame outside the exchanger. Burners seated. Crossover lit.
If pass: Still inspect secondary / flue / condensate before you reset.
2 Secondary, condensate, and flue
Blocked secondary, drowned collector, or a plugged flue pushes flame out the front. Pull the inducer/collector look, confirm the trap is flowing, and check PVC/vent. Exchanger, burners, flue. Blocked secondary / condensate.
Expect: Dry collector, open flue, trap clear.
3 Reset only after the cause is fixed
Manual-reset rollout. Recurring rollout on Amana AM9S96 is a CO / fire call — cracked primary, misaligned burners, or a failed secondary. Confirm CO in the space before you leave. Reset only after the cause is fixed. Recurring rollout is a CO / fire call.
Expect: One clean cycle after the cause is fixed. No second reset as a repair.
7 flash
Low flame
Weak µA.
1 Measure µA while it is running
Do not clean first and guess. Series-µA the rod on Amana AM9S96 during a call. Falling µA is oxide, ground, or a dying flame. A hard drop is often the pressure switch or limit opening, not the rod. Clean rod with a non-scratch pad — not sandpaper.
Expect: Flame rod: µA per this door card. Rising while running is the goal.
2 Rod, ground, then gas
Clean the rod with a non-scratch pad — not sandpaper. Chassis ground to burner box and IFC (painted screw and missing star washer are classic). Then manifold on the stage that is dropping and confirm LP conversion leftovers. Chassis ground to burner box and IFC.
Expect: Manifold: Single-stage plate value only — no low/high pair.
3 Prove it is not a switch opening
Watch the live Amana AM9S96 display when flame drops. A PS or limit code that appears at the drop means the rod was a victim. Inducer, hose, vent wind, or a limit on a wrong heat tap. Manifold / orifice / LP conversion.
Expect: µA stable and the live code stays a flame code — then rod/valve/IFC. Otherwise chase the new code.
8 flash
Igniter fault
Open / cracked HSI.
1 Ohms at the igniter, then at the IFC
On Amana AM9S96 measure cold ohms at the igniter plug, then at the IFC connector. An open at the plug is the element or local harness. Open only at the IFC is the harness rub-through on the collector. Ohms at the igniter plug, then at the IFC.
Expect: HSI: Nitride, 120 VAC during warm-up. Cold ohms per sticker.
2 120 VAC during warm-up
Call for heat and measure 120 VAC at the igniter during the warm-up window. 0 V + good ohms = IFC igniter relay. Voltage + no glow = cracked nitride. 120 VAC during trial.
Expect: 120 VAC only during warm-up. Visible glow before the valve opens.
3 Do not keep cycling a cracked element
A cracked nitride can ohm ‘good’ cold and open hot. If ohms and voltage are good and there is no glow, replace the igniter. Confirm polarity/ground (this plate’s polarity code) before you condemn a new igniter. Cracked nitride element.
Expect: One clean light after a known-good igniter and a proven ground.
9 flash
Polarity / ground
L1/N or chassis ground.
1 Hot and neutral at the IFC, not the disconnect
On Amana AM9S96 polarity/ground is measured at the board. A correctly landed disconnect with a swapped whip at the IFC still throws this. Hot and neutral at the IFC, not just the disconnect.
Expect: L1 hot, N neutral, ~120 VAC L1 to N, ~0 VAC N to ground.
2 Burner-box and IFC ground
Green ground to cabinet and IFC. Painted screw and missing star washer fail the ground check and kill flame sense. Burner-box ground screw.
Expect: Near-zero ohms burner box to IFC ground screw.
3 Then flame and HSI
Polarity/ground faults take out HSI and flame sense together. After the wiring is right, run one heat cycle and confirm µA and igniter glow before you change those parts. Rapid flash on some revs is the same polarity complaint, not a high count.
Expect: Code cleared. One clean light. µA in range.
Workflows
No heat (single-stage 96%)
AM9S96 / AMH96 / GM9S96. Tstat calling W, indoor cold.
1 Prove the call and the live code
Count flashes. Do not use an AR9T96 E-code card or an AMVC96 ComfortBridge menu.
Expect: Write whatever Single-stage IFC · red LED flash or basic 7-seg is showing. Last fault often repeats until power is cycled. Write it first.
If fail: No call at the IFC → stat / harness. Do not change gas parts.
2 Isolate the first failed step in the sequence
Door switch in? 120 VAC at L1, 24 VAC across the fuse.
Expect: Prove: One NO pressure switch. Already closed with inducer off → 2-flash. Never closes → 3-flash.
3 Confirm with a number, then the next part
W present at the IFC (not just at the stat). R to W ~24 VAC. 3-flash: trap and vent first — these 96%s drown a collector overnight. 2-flash with inducer off: unplug the only PS. Code change = switch/hose.
Expect: Pressure switch: One NO switch. Closed only after inducer is up. · Manifold: Single-stage plate value only — no low/high pair.
If fail: Stay on this plate. The out-of-range reading is the part.
If pass: Reading in range → the next step in this workflow is the repair.
4-flash limit trips
Blower on, burners drop, 4-flash.
1 Prove the call and the live code
Heat-speed tap first. A 96% coil on top of a furnace left on a low heat tap will limit all winter.
Expect: Write whatever Single-stage IFC · red LED flash or basic 7-seg is showing. Last fault often repeats until power is cycled. Write it first.
If fail: No call at the IFC → stat / harness. Do not change gas parts.
2 Isolate the first failed step in the sequence
Filter, wheel, coil, return size. A new media cabinet the installer added is the usual callback.
Expect: Prove: One NO pressure switch. Already closed with inducer off → 2-flash. Never closes → 3-flash.
3 Confirm with a number, then the next part
Rise vs plate. Clock the meter if rise is high with a clean filter. Secondary / condensate — a drowned coil raises head in the exchanger and trips limit.
Expect: Pressure switch: One NO switch. Closed only after inducer is up. · Manifold: Single-stage plate value only — no low/high pair.
If fail: Stay on this plate. The out-of-range reading is the part.
If pass: Reading in range → the next step in this workflow is the repair.
Test points
Pressure switch
One NO switch. Closed only after inducer is up.
Manifold
Single-stage plate value only — no low/high pair.
Flame rod
µA per this door card. Rising while running is the goal.
HSI
Nitride, 120 VAC during warm-up. Cold ohms per sticker.
Heat tap / rise
Match the installer’s tap to the rise range on the rating plate (typically 35–65°F).
Gotchas
- GMSS96 is the Goodman-badge listing of this flash family — use the Goodman GMSS96 chart, not this alias.
- A leftover W2 from a previous two-stage furnace does nothing useful here and confuses the next tech.
- Do not install a second pressure switch ‘because two-stage boards have two.’
- AR9T96 E8/E9 and AMVC96 b/d codes do not apply. One switch, flash count, conventional 24V.
Related plates
- amana-ar9s96Current single-stage 9-speed 96% — 7-seg E0–E7 on 0140F20003-B, not this LED 1–9 flash card.
- amana-ar9t96Two-stage 9-speed cousin — dual PS, 7-seg E1/E2 vs E8/E9. Do not use that chart on this single-stage flash IFC.
- amana-amvc96ComfortBridge communicating VS cousin. Triple 7-seg, serial ECM, memory card. Not this board.
Install this plate
Install AM9S96 as a single-stage 96% with one pressure switch and a flash IFC.
Cat IV PVC · single-stage valve · one PS · multi-speed ECM or PSC · 24V W Y G R C
Vent & prove
- One inducer speed, one pressure switch, one hose. There is no high-fire tap to land.
- PVC 2-pipe or 1-pipe. Prime the trap. 3-flash (or the door-card equivalent) is collector / PVC / inducer — not a chimney.
Blower & stat
- Heat and cool taps (or ECM profiles), not a 9-speed AR9T96 card and not ComfortBridge serial.
- Single W from a conventional stat. A leftover W2 wire does nothing useful and can backfeed — cap it.
First fire
- 1W call: inducer, PS close, HSI, valve, flame, heat-speed blower.
- 2Set rise from the AM9S96 / GM9S96 tap chart for this cabinet.
- 3Confirm the door card is the LED flash chart, not a 7-seg E-code sticker from a sister SKU.
Do not on Amana AM9S96
- Do not use the AR9T96 E1/E2 vs E8/E9 chart. One switch.
- Do not install a ComfortBridge outdoor on a data pair this board does not have.
Maker literature
FieldBench does not host manufacturer files. Each link opens the maker’s own literature page in a new tab.
- AM9S96 product pageProduct pageSingle-stage 96% flash / multi-speed.Open manufacturer PDF
- AM9S96 specification sheetSpec sheetSearch this plate in the Goodman literature library.Open manufacturer PDF
- Amana literature libraryLiterature searchGas furnace / air-handler PDFs. Match the plate, not just the Amana badge.Open manufacturer PDF
Warranty and bulletins
Affected models, serial range, symptom, remedy, date. Maker files open on the manufacturer site.
Standard limited warranty
warranty sheetAmana furnace heat-exchanger / unit-replacement terms
Registered residential furnace warranty terms · Limited warranty certificate
Dealer portals
dealerWhere remaining service letters live
Current-year service letters not on a public literature page · Maker dealer portal