York
6-flash
LockoutIGC 6-flash — example
Example on many CES rooftop IGCs: ignition lockout after retries. Confirm THIS sticker.
Walk 6-flash in Diagnose
Sign in for the next measurement
First check
1 Watch one full try — do not reset
Write the York ZF code. Watch inducer, HSI glow, valve click, flame, µA. The step that dies is the repair. Resetting only burns another try into a harder lockout. Watch one try: inducer → PS → glow → valve → flame. The dead step is the repair.
Expect: Call → Fan → Econo → Cool → Heat
The rest of the walkthrough is Diagnose.
On the plates
- Watch one try: inducer → PS → glow → valve → flame. The dead step is the repair.
- HSI ohms, 24 VAC at the valve during trial, inlet gas on the roof.
Plates that use 6-flash
Same number, other makers
6-flash on York is not the same code on these plates.