Lennox
6 flash
LockoutPS lockout
Hardened 3-flash / 2-flash. Retries used up on draft.
Walk 6 flash in Diagnose
3 plates — walk the one on the cabinet
First check
1 Prove inducer and the live code
Do not pull power — that clears the Lennox ML180 active code. Write 6 flash. Is the inducer spinning on this call? Silent inducer is not a pressure switch. Fix chimney / inducer / common vent, then reset.
Expect: 120 VAC at the inducer on a heat call. Wheel turning.
If fail: 120 VAC missing → IFC / door switch / incoming power. Voltage + dead motor → inducer.
If pass: Inducer running + this code → trap, hose, switch, vent (step 2).
The rest of the walkthrough is Diagnose.
On the plates
- Fix the 3-flash physics (trap/PVC) before you reset.
- Fix chimney / inducer / common vent, then reset.
Plates that use 6 flash
Same number, other makers
6 flash on Lennox is not the same code on these plates.