Lennox
E274
LockoutSoft lockout — last recycle limit open or limit >3 min
Hardened E250.
Walk E274 in Diagnose
4 plates — walk the one on the cabinet
First check
1 Airflow before you touch the limit
On Lennox EL195NE a limit is airflow or overfire until proven otherwise. Do not replace the limit first. Filter, blower wheel, A-coil, and the heat-speed setting for THIS motor (tap, model plug, or communicating CFM — not a sister SKU chart). Hardened E250. VS CFM, media cabinet, rise.
Expect: Rise in the rating-plate window. Static vs this cabinet’s blower chart.
The rest of the walkthrough is Diagnose.
On the plates
- Hardened E250. VS CFM, media cabinet, rise.
- If a rollout is open in that string, stop and inspect the exchanger before you up the CFM.
- Heat tap, static, rollout string.