EL296V
Elite · two-stage · variable-speed · 96%
Lennox EL296V two-stage 96% Elite with a variable-speed blower and a 7-segment SureLight IFC (ignition control 107045-XX / 103130-XX — same E2xx family as EL297DFV / EL296UHV field boards). Codes are E plus three digits. Two pressure switches, two hoses. Confirm any odd extra code on THAT door card — revisions shuffle a few numbers in the E292/E310 neighborhood.
Not ML196 flash (1–9 LED). Not SLP99V (iComfort-native modulating — E105 is first-class there). Not EL296E (constant-torque cousin — same gas/PS/limit E2xx, no serial-blower E201 as the motor story). Not SL280 / EL280 (80% metal vent).
AFUE
96% two-stage condensing
Blower
Variable-speed ECM (serial, not a tap motor)
IFC
SureLight 7-seg E-prefix · 107045-XX / 103130-XX family
Draft
Two pressure switches · two hoses · never teed
Sister SKU
EL296UHV upflow · EL296DFV downflow
Tstat
Usually 24V W1/W2. iComfort RS bus is optional, not required.
This board
SureLight 7-seg IFC (E2xx)
- Idle is a decimal blink at 1 Hz (0.5 s on / 0.5 s off). That is not a fault.
- Faults are E plus three digits. Write the full number. E225 ≠ E223 ≠ E229.
- Pushbutton menu: E = recall last 10 (c twice to clear). F = flame µA. P = program unit size (VS only).
- This chart is the 107045-XX / 103130-XX SureLight family used on EL296V. Confirm any odd extra code on THAT door card before you order a part.
- E105-style RS-bus codes appear only if iComfort is wired. Many EL296V jobs are 24V.
Hold the IFC button to a solid E. Last 10 codes, most recent first. Select c and press again while c flashes to erase. Exit at the triple-bar. 7-seg also repeats the active fault.
Universal swap
Current Elite SureLight 107045 / 103130 is not on the ICM2813 list. ICM2813 / 21D83M-843 are the older 10M93 / 12L69 generation.
Silk: 107045 · 103130 · 10M9301 · 12L6901 · 56L8401
White-Rodgers
- 21D83M-843
Same older SureLight / 50A62 / 50A66 family. Confirm the WR sheet names that exact number.
ICM
- ICM2813
Only if the silk is 10M9301 / 12L6901 / 56L8401 / 69M08 / 83M00 — not 107045-XX.
Honeywell
—- ICM2813 ordered because the door says SureLight — 107045 is a different generation.
- ICM289 BCC boards. iComfort SLP99V card. EL296E motor in this VS cabinet.
- 50A55-843.
After you pull the dead card
- 1Read the ignition-control number. 107045-XX / 103130-XX → OEM Elite SureLight. 10M93 / 12L69 → ICM2813.
Field wiring
Written landings for Lennox EL296V. Not a factory schematic.
SLP99V / SL297NV / EL296V communicating. iComfort S30/S40 on I+ and I−. Many EL296V jobs are still 24V — use that landing if RS wires are empty.
Written circuit description only — FieldBench does not redraw maker schematics. Example: R to W closes on a heat call; verify 24V at W1 before you change the IFC.
Open manufacturer PDFHeat sequence
- 1Power. L1 / N → IFC120V
- 2Call. Data pair or 24V W → IFCBus or 24V
- 3Draft. IFC → inducer → proveTwo-stage PS or a pressure band
- 4Ignite. IFC → HSI → valve120V igniter
- 5Blow. IFC → serial ECMNo tap, no cap
This indoor
Elite VS. iComfort I+/I− or 24V W1/W2. E105 = data on a 24V job.
iComfort communicating
S30/S40 and a communicating outdoor, or communicating indoor-only.
iComfort S30 / S40
R, C, I+, I−.
- R24V hot24V
- CCommon24V
- I+DataData
- I−DataData
iComfort IFC
E105 on a 24V-only job means data wires landed on RS terminals. Pull them.
- I+DataData
- I−DataData
- R24V24V
- CCommon24V
- W124V heat if used24V
Landing
- DataStat I+/I−IFC I+/I−outdoor
iComfort data
- 24VR and C at the stat
~24 VAC
EL296V as 24V
No iComfort outdoor. Conventional W1/W2/Y. Leave I+ / I− empty.
Two-stage 24V stat
Normal W1/W2/Y/G. RS / I+ unused.
- RHot24V
- CCommon24V
- W1Low fire24V
- W2High fire24V
- YCool24V
- GFan24V
Landing
- 24VStat W1/W2IFC W1/W2
Two-stage heat
- 24VStat YIFC Youtdoor Y
Cool
IFC harness — communicating two-stage
Call arrives on the data pair (or 24V W). Gas train is still inducer / prove / igniter / valve.
Transformer + fuse
24V still exists for accessories and for a 24V outdoor. Data pair is not the transformer.
- L1 / N120VLine
- R / C24V strip24V
- FUSEOn the IFC24V
24V safety chain
Limit / rollout / door still open the heat path. Codes are on THIS IFC language.
- DOORInterlock24V
- LIMITMain limit24V
- ROLLOUTManual reset24V
Two-speed inducer + dual PS
Low vs high prove. Do not tee the hoses. Do not apply this to a modulating cousin.
- IND LO/HITwo-speed inducerLine
- LPSLow prove24V
- HPSHigh prove24V
HSI + two-stage valve
Two solenoids or a two-stage valve. Staging is the bus or W1/W2, not a tap.
- HSI120V igniterLine
- MV / HV24V low / high solenoids24V
- FLAMEµA DC24V
Serial variable-speed ECM
IFC talks to the motor on the serial harness. No F-taps. No dual run cap on this blower.
- SERIALIFC-to-motor harness. Unplugged motor = CFM / comm fault, not a tap problem24V
- CFMSet in the IFC menu / model plug / CoolCloud — not a dip switch on most of these24V
Landing
- LineCallIFCinducerprove
Low then high
- LineIFCHSIvalve
120V igniter, 24V or serial valve
- 24VFlame rodIFC
µA DC
- DataIFCserial blower
No F-taps. No PSC cap.
Prove it
- If the stat is S30, I+/I− must be landed and the furnace must be on the equipment list.
- E105 with a 24V stat = data wires on the RS terminals.
Do not
- Do not land Y on I+.
- ML196 / EL196E / EL296E are 24V unless the silk actually has iComfort.
I+ / I− are the published iComfort terminals.
Sequence
- 1
W1
Low inducer → low PS must close. Failure here is E223 / E227 / later E229.
- 2
Trial
HSI (E207 / E290 if the circuit is open) → low-fire valve (E204–E206) → flame (E240 / E270 if no µA).
- 3
W2 / high
High inducer → high PS. E225 if high-fire prove fails. E229 = IFC abandoned low-fire prove and lit on high.
- 4
Limits
E250 = limit string open. Open >3 min or recycle-on-limit becomes E274. E252 = discharge air too high.
- 5
Blower
VS motor talks serial to the IFC. After a board or motor swap, P-menu unit size must match or you get E201 / E202 / E203.
Faults on this IFC
Step 1, then 2, then 3. Expected reading and the fail branch sit under each check.
idle
Decimal blink
Idle / heartbeat. Decimal blinks 1 Hz. Not a fault.
1 Confirm this is not a fault
On the Lennox EL296V this readout (idle) is run status, not a lockout. Write what the display actually shows and whether W/Y/G is present at the IFC.
Expect: Idle / Ht / CF / stage+CFM words change when you apply and remove the call.
If fail: If the word never changes on a real call, the call is not reaching this IFC.
If pass: The board is alive. Diagnose the comfort complaint, not this code.
2 Prove the call at the board
Measure R to W / Y / G at the Lennox EL296V IFC, not at the thermostat. Communicating plates need the data pair and a live indoor address — 24 V on W is not the test.
Expect: If you expected a code, press E for recall — idle only means nothing is active right now.
If fail: Fix the stat, harness, or data pair before you change parts.
3 Watch one full sequence
Leave power on. Watch SureLight 7-seg IFC (E2xx) through one cycle and write the first real fault that replaces this status word.
Expect: W1: Low inducer → low PS must close. Failure here is E223 / E227 / later E229.
E
Error recall
Menu: last 10 stored codes.
1 Confirm this is not a fault
On the Lennox EL296V this readout (E) is run status, not a lockout. Write what the display actually shows and whether W/Y/G is present at the IFC.
Expect: Idle / Ht / CF / stage+CFM words change when you apply and remove the call.
If fail: If the word never changes on a real call, the call is not reaching this IFC.
If pass: The board is alive. Diagnose the comfort complaint, not this code.
2 Prove the call at the board
Measure R to W / Y / G at the Lennox EL296V IFC, not at the thermostat. Communicating plates need the data pair and a live indoor address — 24 V on W is not the test.
Expect: Write them in order before you clear.
If fail: Fix the stat, harness, or data pair before you change parts.
3 Watch one full sequence
Leave power on. Watch SureLight 7-seg IFC (E2xx) through one cycle and write the first real fault that replaces this status word.
Expect: W1: Low inducer → low PS must close. Failure here is E223 / E227 / later E229.
F
Flame signal
Menu: live flame current in µA on the 7-seg.
1 Measure µA while it is running
Do not clean first and guess. Series-µA the rod on Lennox EL296V during a call. Falling µA is oxide, ground, or a dying flame. A hard drop is often the pressure switch or limit opening, not the rod. Use this on an E240 / E270 call instead of guessing the rod.
Expect: Flame (F menu): µA per EL296 card. Rising while running.
2 Rod, ground, then gas
Clean the rod with a non-scratch pad — not sandpaper. Chassis ground to burner box and IFC (painted screw and missing star washer are classic). Then manifold on the stage that is dropping and confirm LP conversion leftovers. Exits on power reset, hold-to-bars, or 10 minutes.
Expect: Manifold on the rating plate. Solid burner-box ground.
3 Prove it is not a switch opening
Watch the live Lennox EL296V display when flame drops. A PS or limit code that appears at the drop means the rod was a victim. Inducer, hose, vent wind, or a limit on a wrong heat tap.
Expect: µA stable and the live code stays a flame code — then rod/valve/IFC. Otherwise chase the new code.
P
Program unit size
VS only. Stores cabinet / motor capacity in non-volatile memory.
1 Read the plug / card on THIS cabinet
On Lennox EL296V the model plug or shared-data card must match this cabinet size. A 100 kBtu plug in an 80 cabinet overfires and limits. A leftover memory card after a control swap throws d0/d4-class codes. Required after IFC or blower swap. Wrong or blank size → E202 / E203.
Expect: Plug / card part matches the rating plate and the replacement control bulletin.
2 Reseat, then confirm the menu
Kill power, reseat, restore power. On communicating plates open the setup and confirm unit size / motor HP. Follow the P-menu character for THIS EL296V cabinet, then hold to accept.
Expect: IFC recognizes the plug. No size-mismatch code.
3 Do not run it mismatched
A wrong plug is not a ‘temporary’ fix. It will throw limit, ignition, or blower-band codes that look like bad parts. Fit the correct plug, then re-run the original complaint.
Expect: One clean sequence on the correct identity.
E105
RS BUS communication
No other devices on the RS bus, or the bus is too noisy to talk.
1 Data pair, not 24 V
On Lennox EL296V indoor/outdoor comm is a data pair (AB, S1/S2, U, ComfortBridge, ComfortLink — whatever THIS plate uses). It is not a 24 V Y. Check polarity, continuity, and that nobody landed it on R/C. Only if iComfort is actually wired — i+/i− polarity, one communicating control, indoor/outdoor on the bus.
Expect: Pair continuous, not shorted to chassis, polarity per the diagram.
2 Power both ends, then the outdoor status
Indoor transformer and outdoor control both alive. Read the outdoor LED / 7-seg. Water in the outdoor control is the usual dead-end after a storm. Many EL296V jobs are 24V. E105 on a 24V-only install means data wires landed on the RS terminals. Pull them.
Expect: Both controls powered. Outdoor showing a comm or address state, not a blank board.
3 Address / bias, then the control
Communicating plates need a matching indoor address and sometimes a terminating bias. Swap is last: known-good pair + power both ends + correct address.
Expect: Indoor sees the outdoor. No comm code after a power cycle.
E111
Low line voltage
Line voltage below nameplate. Control waits; resumes ~5 s after voltage recovers.
1 Measure at the IFC under load
On Lennox EL296V line-voltage codes are incoming power. Measure L1/L2 (or L1/N) at the board while it is trying to run, not just at the disconnect. L1 to N at the IFC, not just the disconnect. Brownout, loose lug, undersized circuit.
Expect: Voltage in the rating-plate window under load.
2 Drop, breaker, and the whip
Large drop from the disconnect to the IFC is a loose lug or damaged whip. Breaker that will not hold under inducer/blower start is the circuit, not the board. Some older EL296UHE cards print E110 as low line and E111 as polarity reversed — confirm THAT door card.
Expect: Minimal drop. Tight lugs. Correct breaker size.
3 Transformer 24 V last
If line is good and 24 V is low, load the transformer (stat + valve + accessories). A collapsing 24 V looks like a comm or fuse call.
Expect: 24 V holds under load. Line stays in window.
E112
Ground not detected
IFC does not see earth ground. Unit shuts down.
1 Hot and neutral at the IFC, not the disconnect
On Lennox EL296V polarity/ground is measured at the board. A correctly landed disconnect with a swapped whip at the IFC still throws this. Green to cabinet and IFC. Painted screw / missing star washer.
Expect: L1 hot, N neutral, ~120 VAC L1 to N, ~0 VAC N to ground.
2 Burner-box and IFC ground
Green ground to cabinet and IFC. Painted screw and missing star washer fail the ground check and kill flame sense. Resumes ~5 s after a real ground is provided.
Expect: Near-zero ohms burner box to IFC ground screw.
3 Then flame and HSI
Polarity/ground faults take out HSI and flame sense together. After the wiring is right, run one heat cycle and confirm µA and igniter glow before you change those parts.
Expect: Code cleared. One clean light. µA in range.
E113
High line voltage
Line voltage above nameplate.
1 Measure at the IFC under load
On Lennox EL296V line-voltage codes are incoming power. Measure L1/L2 (or L1/N) at the board while it is trying to run, not just at the disconnect. Measure at the IFC. Boost transformer, generator, or utility high.
Expect: Voltage in the rating-plate window under load.
2 Drop, breaker, and the whip
Large drop from the disconnect to the IFC is a loose lug or damaged whip. Breaker that will not hold under inducer/blower start is the circuit, not the board. Resumes ~5 s after voltage is in range.
Expect: Minimal drop. Tight lugs. Correct breaker size.
3 Transformer 24 V last
If line is good and 24 V is low, load the transformer (stat + valve + accessories). A collapsing 24 V looks like a comm or fuse call.
Expect: 24 V holds under load. Line stays in window.
E114
Line frequency out of range
No clean 60 Hz. OEM: no 60 Hertz power.
1 Measure at the IFC under load
On Lennox EL296V line-voltage codes are incoming power. Measure L1/L2 (or L1/N) at the board while it is trying to run, not just at the disconnect. Generator / inverter / poorly conditioned backup power is the usual.
Expect: Voltage in the rating-plate window under load.
2 Drop, breaker, and the whip
Large drop from the disconnect to the IFC is a loose lug or damaged whip. Breaker that will not hold under inducer/blower start is the circuit, not the board. Utility frequency events are rare — confirm you are not on a job-site gen set.
Expect: Minimal drop. Tight lugs. Correct breaker size.
3 Transformer 24 V last
If line is good and 24 V is low, load the transformer (stat + valve + accessories). A collapsing 24 V looks like a comm or fuse call.
Expect: 24 V holds under load. Line stays in window.
E115
Low 24V
Secondary below ~18–30 V class. Control restarts if voltage recovers.
1 Measure at the IFC under load
On Lennox EL296V line-voltage codes are incoming power. Measure L1/L2 (or L1/N) at the board while it is trying to run, not just at the disconnect. 24 VAC at the IFC under load. Extra accessories robbing the transformer.
Expect: Voltage in the rating-plate window under load.
2 Drop, breaker, and the whip
Large drop from the disconnect to the IFC is a loose lug or damaged whip. Breaker that will not hold under inducer/blower start is the circuit, not the board. Door-switch / shorted valve / undersized VA. Fix the load before you upsize the transformer.
Expect: Minimal drop. Tight lugs. Correct breaker size.
3 Transformer 24 V last
If line is good and 24 V is low, load the transformer (stat + valve + accessories). A collapsing 24 V looks like a comm or fuse call.
Expect: 24 V holds under load. Line stays in window.
E117
Poor ground
Ground is present but dirty. Warning only — clears ~30 s after it recovers.
1 Hot and neutral at the IFC, not the disconnect
On Lennox EL296V polarity/ground is measured at the board. A correctly landed disconnect with a swapped whip at the IFC still throws this. Same ground path as E112, just not open. Flame µA and HSI both suffer.
Expect: L1 hot, N neutral, ~120 VAC L1 to N, ~0 VAC N to ground.
2 Burner-box and IFC ground
Green ground to cabinet and IFC. Painted screw and missing star washer fail the ground check and kill flame sense. Do not ignore a repeating E117 on an E240 / E270 call.
Expect: Near-zero ohms burner box to IFC ground screw.
3 Then flame and HSI
Polarity/ground faults take out HSI and flame sense together. After the wiring is right, run one heat cycle and confirm µA and igniter glow before you change those parts.
Expect: Code cleared. One clean light. µA in range.
E201
Indoor blower communication failure
IFC lost serial talk with the VS indoor blower (including a motor that never powered up).
1 Reseat the serial plug
On Lennox EL296V this is a communicating / serial ECM, not a tap motor. Kill power, reseat the 14-pin (or OEM serial plug) at the motor and at the IFC. Pins straight, no corrosion. Motor harness seated at IFC and module. 120/240 at the motor, not just the IFC.
Expect: Plug fully seated both ends. Correct motor for this cabinet.
2 Power and the data pair at the motor
Line voltage at the motor, then the serial/data pair continuity. A half-seated plug or a pinched harness throws comm on a good motor. After a board or motor swap this is usually P-menu / wrong motor — see E202 / E203.
Expect: Line voltage present. Data pair not shorted to chassis.
3 Motor vs IFC serial driver
Known-good motor still throws this code = Lennox EL296V IFC serial driver. Known-good IFC still throws it = motor module. Do not put a PSC or 9-speed tap motor on a serial IFC.
Expect: One clean CFM request after a known-good pair.
E202
Indoor blower HP / unit capacity mismatch
Programmed unit size does not match the motor horsepower the IFC sees.
1 Read the plug / card on THIS cabinet
On Lennox EL296V the model plug or shared-data card must match this cabinet size. A 100 kBtu plug in an 80 cabinet overfires and limits. A leftover memory card after a control swap throws d0/d4-class codes. P menu: pick the character for THIS cabinet, hold to store, let the IFC reset.
Expect: Plug / card part matches the rating plate and the replacement control bulletin.
2 Reseat, then confirm the menu
Kill power, reseat, restore power. On communicating plates open the setup and confirm unit size / motor HP. An EL296E constant-torque motor in this VS cabinet will throw E202 / E310. Use the VS motor.
Expect: IFC recognizes the plug. No size-mismatch code.
3 Do not run it mismatched
A wrong plug is not a ‘temporary’ fix. It will throw limit, ignition, or blower-band codes that look like bad parts. Fit the correct plug, then re-run the original complaint.
Expect: One clean sequence on the correct identity.
E203
Appliance capacity not programmed
Unit size code is blank or invalid after a new IFC.
1 Read the plug / card on THIS cabinet
On Lennox EL296V the model plug or shared-data card must match this cabinet size. A 100 kBtu plug in an 80 cabinet overfires and limits. A leftover memory card after a control swap throws d0/d4-class codes. This is a P-menu job, not a bad motor. Program size, then retest.
Expect: Plug / card part matches the rating plate and the replacement control bulletin.
2 Reseat, then confirm the menu
Kill power, reseat, restore power. On communicating plates open the setup and confirm unit size / motor HP. Remove the stat from the bus if iComfort is fighting the program cycle.
Expect: IFC recognizes the plug. No size-mismatch code.
3 Do not run it mismatched
A wrong plug is not a ‘temporary’ fix. It will throw limit, ignition, or blower-band codes that look like bad parts. Fit the correct plug, then re-run the original complaint.
Expect: One clean sequence on the correct identity.
E204
Gas valve mis-wired
Valve harness does not match what the IFC commanded.
1 Coil ohms and 24 VAC during trial only
On Lennox EL296V measure each solenoid. 24 VAC should appear only during trial / the commanded stage. Stage 1 / stage 2 leads on the correct valve terminals. Pinched or swapped harness.
Expect: Coil ohms per the valve sticker. 24 VAC only when the IFC commands that stage.
2 Do not energize a leaking valve
If the unexpected-flame code is also in history, shut the cock and replace the valve. Applying 24 V as a ‘test’ and walking away is a gas leak. Clears when the wiring is repaired — do not replace the IFC first.
Expect: No flame with the cock shut and solenoids de-energized.
3 IFC relay vs the valve
Voltage at the harness and a dead coil = valve. No voltage during a known trial = IFC relay or a lockout that never opened the valve (look at the live code).
Expect: Known trial + 24 VAC + good coil = flame. Otherwise IFC.
E205
Gas valve control relay shorted
IFC thinks its valve relay contacts are shorted.
1 Coil ohms and 24 VAC during trial only
On Lennox EL296V measure each solenoid. 24 VAC should appear only during trial / the commanded stage. Unplug the valve. If E205 stays, the IFC relay is the fault.
Expect: Coil ohms per the valve sticker. 24 VAC only when the IFC commands that stage.
2 Do not energize a leaking valve
If the unexpected-flame code is also in history, shut the cock and replace the valve. Applying 24 V as a ‘test’ and walking away is a gas leak. If it clears, ohm the valve coil and harness for a short to chassis.
Expect: No flame with the cock shut and solenoids de-energized.
3 IFC relay vs the valve
Voltage at the harness and a dead coil = valve. No voltage during a known trial = IFC relay or a lockout that never opened the valve (look at the live code).
Expect: Known trial + 24 VAC + good coil = flame. Otherwise IFC.
E206
Second-stage gas valve relay failure
High-fire solenoid will not drive. OEM: furnace runs first stage only for the rest of the call.
1 Let it cool, then read the drive LED
On Lennox EL296V overcurrent / overheat is often a dirty coil, a failed OD fan, or a locked compressor — not a dead inverter. Clear airflow, confirm the OD fan, and read the drive LED before you order a control. W2 present? 24 VAC at stage-2 coil on a high call.
Expect: OD fan running. Coil clean. Drive LED decoded from THIS outdoor’s card.
2 Voltage and compressor windings
Incoming voltage in range (this plate’s line-voltage code). Compressor windings even, no ground. A shorted compressor will kill a new drive. If wiring is good and it never stages, replace the IFC — it is already heating on low.
Expect: Balanced windings. No winding to ground. Line voltage stable under load.
3 Charge and the drive last
A starved or flooded compressor will overcurrent. Confirm SH/SC and charge weight. Only then condemn the inverter.
Expect: Charge on the nameplate. Drive code gone after a cool-down and a clean coil.
E207
HSI sensed open
Hot-surface ignitor circuit measures open.
1 Ohms at the igniter, then at the IFC
On Lennox EL296V measure cold ohms at the igniter plug, then at the IFC connector. An open at the plug is the element or local harness. Open only at the IFC is the harness rub-through on the collector. Cold ohms at the ignitor, then at the IFC. Replace if open or out of the IOM range.
Expect: HSI: Cold ohms in the IOM range. 120 VAC during trial.
2 120 VAC during warm-up
Call for heat and measure 120 VAC at the igniter during the warm-up window. 0 V + good ohms = IFC igniter relay. Voltage + no glow = cracked nitride. Harness rub-through on the collector is common on these cabinets.
Expect: 120 VAC only during warm-up. Visible glow before the valve opens.
3 Do not keep cycling a cracked element
A cracked nitride can ohm ‘good’ cold and open hot. If ohms and voltage are good and there is no glow, replace the igniter. Confirm polarity/ground (this plate’s polarity code) before you condemn a new igniter.
Expect: One clean light after a known-good igniter and a proven ground.
E223
Low PS failed OPEN
Low-fire pressure switch did not close on the heat call.
1 Prove inducer and the live code
Do not pull power — that clears the Lennox EL296V active code. Write E223. Is the inducer spinning on this call? Silent inducer is not a pressure switch. Inducer actually on low? Low-fire hose only, 96% trap, PVC intake/exhaust.
Expect: Inducer port: Open to the collector, not packed with oxide. Two hoses, never teed.
If fail: 120 VAC missing → IFC / door switch / incoming power. Voltage + dead motor → inducer.
If pass: Inducer running + this code → trap, hose, switch, vent (step 2).
2 Trap, collector, and the hose
A drowned 96% trap will not make collector pressure. Pull the trap, flush it, confirm the collector box and inducer outlet are not full. Hose cracked, off the port, or full of water fakes an open switch. Clean the inducer pressure port — known EL296. Dust packs the port and throws the whole PS family.
Expect: Trap flowing, hose dry and downhill, ports not swapped on a two-switch board.
3 Switch ohms, then vent load
Ohm the pressure switch: NO, must close when that inducer speed is making the collector setpoint. If the switch is good, walk the PVC — bird screen, ice, long 2" run, wind, shared chase.
Expect: Switch closes on known draft. Vent unrestricted.
If fail: Replace the open switch only after the vent and trap are proven.
If pass: Switch closes on draft and the code stays → IFC input.
E224
Low PS failed CLOSED
Low-fire switch is made when it should be open.
1 Unplug the switch with the inducer off
On Lennox EL296V this code is the switch made when the inducer is not running. Unplug that switch only. Unplug the low switch. Water in the hose or a welded switch.
Expect: Code changes when the harness is open.
If fail: Wrong switch, or the IFC input is shorted.
If pass: Switch/hose path. Go to step 2.
2 Water in the hose vs a welded switch
Blow the hose. Water holding residual draft is more common than a welded switch. Confirm the hose is not teed and not routed uphill. Ohm the switch with the hose off. Inducer still coasting / hose holding residual draft.
Expect: Hose empty. Switch opens with no draft.
3 IFC input last
If the switch ohms open, the hose is dry, and the code does not change with the harness off, the Lennox EL296V IFC input is shorted. Do not keep swapping switches.
Expect: Known-good open switch + open harness = code gone. If not, IFC.
E225
High PS failed OPEN
IFC commanded high; high-fire switch did not close.
1 Prove the high-fire call
Write the live Lennox EL296V code before you pull power. Confirm this IFC is actually commanded to high — W2 at the board, or the staging timer has expired. Does the inducer actually go high?
Expect: R to W2 ~24 VAC (conventional) or a high-stage request on a communicating stat.
If fail: No high request → thermostat / staging / menu. Not a high-fire pressure switch.
If pass: Go to step 2. Do not jump the high-fire switch to ‘see if it runs.’
2 Prove the inducer actually went high
Listen and amp the inducer on low vs high. No speed-up → IFC high output or inducer winding. Speed-up and this code still live → high-fire PS path (hose, switch, vent). High-fire hose not teed to the low switch. Vent capacity on 110/135 kBtu cabinets.
Expect: Inducer port: Open to the collector, not packed with oxide. Two hoses, never teed.
If fail: Measure 120 VAC on the high-speed inducer lead during the high call. 0 V = IFC. Voltage + dead motor = inducer.
3 Isolate the HIGH hose and switch
High-fire hose on the high tap only — a tee with the low switch is the common first-install miss on this dual-switch plate. Blow the hose, confirm it is dry and downhill to the collector. Ohm the high-fire switch: it is NO and must close only on high draft.
Expect: NO switch. Opens with hose off. Closes on high collector draft.
If fail: Welded open, cracked hose, or water in the line. Replace the failed part — do not leave a jumper.
If pass: Switch and hose good → step 4 (vent / condensate / IFC).
4 Vent, condensate, and the IFC input
High fire needs more draft than a low-fire code ever saw. Check PVC size on this cabinet, shared chase, wind, ice, bird screen, and condensate backing into the collector only on high. If the switch closes on known draft and the code stays, the Lennox EL296V IFC input is the last call.
Expect: Clear vent, dry collector, known-good switch, then IFC.
E226
High PS failed CLOSED
High-fire switch is made when it should be open.
1 Prove the switch is made with inducer not on high
On Lennox EL296V this code means the high-fire switch is closed when it should be open. Do not treat it as the low-fire stuck-closed code. Write the live display, then unplug the high-fire switch only.
Expect: Code should change when the high-fire harness is open.
If fail: IFC input shorted or you unplugged the wrong switch.
2 Hose water and a welded switch
Water in the high-fire hose holds residual draft and fakes a closed switch. Route downhill to the collector. Ohm the switch with the hose off — a welded high-fire switch stays closed. Unplug the high switch only. Water or a welded disc. W2 shorted so the IFC thinks it should already be in high.
Expect: Hose dry. Switch opens with no draft.
3 Confirm the IFC is not commanding high
W2 shorted to W1, a communicating stat stuck on high, or an IFC that never drops inducer speed will keep this code alive. Measure W2 at the board and watch inducer speed after you open the high-fire harness.
Expect: Inducer on low (or off) with W2 open. High-fire switch ohms open.
E227
Low PS opened during trial or run
Low switch had closed, then opened mid-trial or in run.
1 Prove inducer and the live code
Do not pull power — that clears the Lennox EL296V active code. Write E227. Is the inducer spinning on this call? Silent inducer is not a pressure switch. Wind, ice, trap siphon, inducer dropping out after light-off.
Expect: Inducer port: Open to the collector, not packed with oxide. Two hoses, never teed.
If fail: 120 VAC missing → IFC / door switch / incoming power. Voltage + dead motor → inducer.
If pass: Inducer running + this code → trap, hose, switch, vent (step 2).
2 Trap, collector, and the hose
A drowned 96% trap will not make collector pressure. Pull the trap, flush it, confirm the collector box and inducer outlet are not full. Hose cracked, off the port, or full of water fakes an open switch. Same port-clean as E223 — a half-clogged port will make then drop.
Expect: Trap flowing, hose dry and downhill, ports not swapped on a two-switch board.
3 Switch ohms, then vent load
Ohm the pressure switch: NO, must close when that inducer speed is making the collector setpoint. If the switch is good, walk the PVC — bird screen, ice, long 2" run, wind, shared chase.
Expect: Switch closes on known draft. Vent unrestricted.
If fail: Replace the open switch only after the vent and trap are proven.
If pass: Switch closes on draft and the code stays → IFC input.
E228
Combustion air inducer calibration failure
IFC could not finish pressure-switch calibration.
1 Is the wheel free?
Spin the Lennox EL296V blower by hand. Ice, debris, or a seized bearing is not a control problem. Confirm the motor type on this plate — serial ECM, 9-speed tap, or X-13 — before you grab a capacitor. Vent and both hoses seated. Inducer must be able to sweep both switches.
Expect: Wheel free. Correct motor family for this IFC.
2 Command vs rotation
Call for G or heat and confirm the IFC is actually requesting CFM (taps, serial, or communicating). Amp the motor. Locked rotor + a good command = motor. No command = IFC / harness / shared data. Fix E223/E225 physics first — calibration will not pass on a clogged port.
Expect: Command present. Motor amps in range, not locked.
3 Static and the wrong motor
High static will trip current/limit codes and look like a dead motor. Measure TES vs this cabinet. Wrong horsepower or a leftover memory card after a control swap is the other half of this call.
Expect: Static on the blower chart. Matching motor / shared-data card.
E229
Ignition on high fire
Low-fire switch did not close in time, so the IFC ran the inducer high and lit on high. OEM: no action needed as a separate repair.
1 Prove inducer and the live code
Do not pull power — that clears the Lennox EL296V active code. Write E229. Is the inducer spinning on this call? Silent inducer is not a pressure switch. This is a low-fire draft problem wearing a high-fire costume. Fix E223 / E227 physics. Do not start on the high-fire manifold screw.
Expect: Inducer port: Open to the collector, not packed with oxide. Two hoses, never teed.
If fail: 120 VAC missing → IFC / door switch / incoming power. Voltage + dead motor → inducer.
If pass: Inducer running + this code → trap, hose, switch, vent (step 2).
2 Trap, collector, and the hose
A drowned 96% trap will not make collector pressure. Pull the trap, flush it, confirm the collector box and inducer outlet are not full. Hose cracked, off the port, or full of water fakes an open switch. Also fires on high for ~60 s if continuous fan was already on (heat-exchanger warmup) — that one is information only.
Expect: Trap flowing, hose dry and downhill, ports not swapped on a two-switch board.
3 Switch ohms, then vent load
Ohm the pressure switch: NO, must close when that inducer speed is making the collector setpoint. If the switch is good, walk the PVC — bird screen, ice, long 2" run, wind, shared chase.
Expect: Switch closes on known draft. Vent unrestricted.
If fail: Replace the open switch only after the vent and trap are proven.
If pass: Switch closes on draft and the code stays → IFC input.
E240
Low flame current — run mode
Flame is present but µA is below the run threshold.
1 Measure µA while it is running
Do not clean first and guess. Series-µA the rod on Lennox EL296V during a call. Falling µA is oxide, ground, or a dying flame. A hard drop is often the pressure switch or limit opening, not the rod. F menu for live µA. Clean the rod — not sandpaper. Neutral-to-ground and E117.
Expect: Flame (F menu): µA per EL296 card. Rising while running.
2 Rod, ground, then gas
Clean the rod with a non-scratch pad — not sandpaper. Chassis ground to burner box and IFC (painted screw and missing star washer are classic). Then manifold on the stage that is dropping and confirm LP conversion leftovers. Clears at the end of the heat call. Repeating E240 becomes E270 / E273.
Expect: Manifold on the rating plate. Solid burner-box ground.
3 Prove it is not a switch opening
Watch the live Lennox EL296V display when flame drops. A PS or limit code that appears at the drop means the rod was a victim. Inducer, hose, vent wind, or a limit on a wrong heat tap.
Expect: µA stable and the live code stays a flame code — then rod/valve/IFC. Otherwise chase the new code.
E241
Flame sensed out of sequence — flame still present
Rod sees flame with the valve de-energized. Flame is still there.
1 Shut the gas cock first
On Lennox EL296V the rod sees flame with the valve de-energized. Shut the cock. If flame stays, the valve is leaking — replace it. Do not jump or energize it as a test. Shut the gas cock. Leaking valve — replace, do not jump.
Expect: Flame dies when the cock is shut.
If fail: Leaking valve. Replace. Do not leave the unit.
2 Rod and IFC flame circuit
If flame dies with the cock shut, the rod is shorted to ground or the IFC flame circuit is lying. Unplug the rod, inspect ceramic, and check the harness for a rub-through on the collector. If flame dies when you shut the cock, the IFC flame circuit / rod short is next.
Expect: Rod isolated from ground. IFC does not report flame with the rod unplugged.
3 Confirm valve solenoids are actually off
Measure 24 VAC at both solenoids after the call drops. A welded IFC relay or a shorted W will keep a solenoid wet and look like ‘unexpected flame.’ Replace the IFC only after the valve and rod are proven.
Expect: 0 VAC at both solenoids after the call. No flame.
E250
Limit switch circuit open
Primary / rollout / secondary string is open. If it stays open >3 min the IFC goes to a 1-hour soft lockout (E274).
1 Treat this as flame outside the exchanger
Do not reset the Lennox EL296V rollout and walk away. Write the code, kill the call, and look for flame at the burners, crossover, and vestibule before you do anything else.
Expect: No flame outside the exchanger. Burners seated. Crossover lit.
If pass: Still inspect secondary / flue / condensate before you reset.
2 Secondary, condensate, and flue
Blocked secondary, drowned collector, or a plugged flue pushes flame out the front. Pull the inducer/collector look, confirm the trap is flowing, and check PVC/vent. VS heat CFM vs the EL296 chart — not a 9-speed tap. Filter, coil, media cabinet. Walk the rollout string if E270 / E274 also store. Manual-reset rollout is a hazard until the cause is gone.
Expect: Dry collector, open flue, trap clear.
3 Reset only after the cause is fixed
Manual-reset rollout. Recurring rollout on Lennox EL296V is a CO / fire call — cracked primary, misaligned burners, or a failed secondary. Confirm CO in the space before you leave.
Expect: One clean cycle after the cause is fixed. No second reset as a repair.
E252
Discharge air too high
Leaving-air temperature above the gas-heat limit (DAT sensor).
1 Airflow before you touch the limit
On Lennox EL296V a limit is airflow or overfire until proven otherwise. Do not replace the limit first. Filter, blower wheel, A-coil, and the heat-speed setting for THIS motor (tap, model plug, or communicating CFM — not a sister SKU chart). Rise vs plate. Heat CFM in the IFC, not a guess.
Expect: Rise in the rating-plate window. Static vs this cabinet’s blower chart.
2 Measure static and temperature rise
Total external static vs the Lennox EL296V blower chart for this cabinet size. Supply minus return rise after 8–10 minutes. A new 5" media cabinet or closed supplies will trip this all winter. Input rate / manifold. Sensor itself only after airflow and fire are right.
Expect: Rise typically 35–65 °F — rating plate wins.
If fail: Fix the restriction or the heat-speed setting. The limit is doing its job.
If pass: Airflow in range → step 3 (overfire / limit itself).
3 Overfire, then the limit circuit
Clock the meter / manifold on the stage that is tripping vs the rating plate. Then ohm the limit after it cools — a limit that never recloses is failed. Rollout in the same circuit is a different call (see rollout on this door card).
Expect: Manifold on plate. Limit closed when cool.
E270
Soft lockout — max retries, no flame current
Tried to light, never saw flame current. Soft lockout. Clears on a successful heat call.
1 Measure µA while it is running
Do not clean first and guess. Series-µA the rod on Lennox EL296V during a call. Falling µA is oxide, ground, or a dying flame. A hard drop is often the pressure switch or limit opening, not the rod. Watch a try: inducer, HSI glow, valve click, flame, then F-menu µA. Which step dies?
Expect: Flame (F menu): µA per EL296 card. Rising while running.
2 Rod, ground, then gas
Clean the rod with a non-scratch pad — not sandpaper. Chassis ground to burner box and IFC (painted screw and missing star washer are classic). Then manifold on the stage that is dropping and confirm LP conversion leftovers. This is ignition, not rollout. The older field rumor that E270 ‘is rollout’ is wrong on this SureLight family — rollout lives in the E250 / E274 string.
Expect: Manifold on the rating plate. Solid burner-box ground.
3 Prove it is not a switch opening
Watch the live Lennox EL296V display when flame drops. A PS or limit code that appears at the drop means the rod was a victim. Inducer, hose, vent wind, or a limit on a wrong heat tap.
Expect: µA stable and the live code stays a flame code — then rod/valve/IFC. Otherwise chase the new code.
E271
Soft lockout — last retry failed because PS opened
Retries used up; the last try died when a pressure switch opened.
1 Prove inducer and the live code
Do not pull power — that clears the Lennox EL296V active code. Write E271. Is the inducer spinning on this call? Silent inducer is not a pressure switch. Treat as a hardened E223 / E227. Port, trap, PVC, inducer.
Expect: Inducer port: Open to the collector, not packed with oxide. Two hoses, never teed.
If fail: 120 VAC missing → IFC / door switch / incoming power. Voltage + dead motor → inducer.
If pass: Inducer running + this code → trap, hose, switch, vent (step 2).
2 Trap, collector, and the hose
A drowned 96% trap will not make collector pressure. Pull the trap, flush it, confirm the collector box and inducer outlet are not full. Hose cracked, off the port, or full of water fakes an open switch. Do not replace the ignitor because the stack says 270-family.
Expect: Trap flowing, hose dry and downhill, ports not swapped on a two-switch board.
3 Switch ohms, then vent load
Ohm the pressure switch: NO, must close when that inducer speed is making the collector setpoint. If the switch is good, walk the PVC — bird screen, ice, long 2" run, wind, shared chase.
Expect: Switch closes on known draft. Vent unrestricted.
If fail: Replace the open switch only after the vent and trap are proven.
If pass: Switch closes on draft and the code stays → IFC input.
E272
Soft lockout — last recycle PS opened
Recycles used up; last recycle failed because a pressure switch opened.
1 Prove inducer and the live code
Do not pull power — that clears the Lennox EL296V active code. Write E272. Is the inducer spinning on this call? Silent inducer is not a pressure switch. It ran, then draft dropped. Wind, ice, trap siphon, inducer after light-off.
Expect: Inducer port: Open to the collector, not packed with oxide. Two hoses, never teed.
If fail: 120 VAC missing → IFC / door switch / incoming power. Voltage + dead motor → inducer.
If pass: Inducer running + this code → trap, hose, switch, vent (step 2).
2 Trap, collector, and the hose
A drowned 96% trap will not make collector pressure. Pull the trap, flush it, confirm the collector box and inducer outlet are not full. Hose cracked, off the port, or full of water fakes an open switch. Same two-hose / port-clean as the E223 cluster.
Expect: Trap flowing, hose dry and downhill, ports not swapped on a two-switch board.
3 Switch ohms, then vent load
Ohm the pressure switch: NO, must close when that inducer speed is making the collector setpoint. If the switch is good, walk the PVC — bird screen, ice, long 2" run, wind, shared chase.
Expect: Switch closes on known draft. Vent unrestricted.
If fail: Replace the open switch only after the vent and trap are proven.
If pass: Switch closes on draft and the code stays → IFC input.
E273
Soft lockout — last recycle flame failure
Recycles used up; last recycle lost flame signal.
1 Measure µA while it is running
Do not clean first and guess. Series-µA the rod on Lennox EL296V during a call. Falling µA is oxide, ground, or a dying flame. A hard drop is often the pressure switch or limit opening, not the rod. F-menu µA, rod, ground, manifold after blower-on. Flame that dies when the wheel starts is often draft or a weak rod.
Expect: Flame (F menu): µA per EL296 card. Rising while running.
2 Rod, ground, then gas
Clean the rod with a non-scratch pad — not sandpaper. Chassis ground to burner box and IFC (painted screw and missing star washer are classic). Then manifold on the stage that is dropping and confirm LP conversion leftovers. Pairs with E240.
Expect: Manifold on the rating plate. Solid burner-box ground.
3 Prove it is not a switch opening
Watch the live Lennox EL296V display when flame drops. A PS or limit code that appears at the drop means the rod was a victim. Inducer, hose, vent wind, or a limit on a wrong heat tap.
Expect: µA stable and the live code stays a flame code — then rod/valve/IFC. Otherwise chase the new code.
E274
Soft lockout — last recycle limit open or limit >3 min
Recycles used up because the limit string opened, or a limit stayed open longer than 3 minutes.
1 Airflow before you touch the limit
On Lennox EL296V a limit is airflow or overfire until proven otherwise. Do not replace the limit first. Filter, blower wheel, A-coil, and the heat-speed setting for THIS motor (tap, model plug, or communicating CFM — not a sister SKU chart). Hardened E250. VS CFM, media cabinet, rise.
Expect: Rise in the rating-plate window. Static vs this cabinet’s blower chart.
2 Measure static and temperature rise
Total external static vs the Lennox EL296V blower chart for this cabinet size. Supply minus return rise after 8–10 minutes. A new 5" media cabinet or closed supplies will trip this all winter. If a rollout is open in that string, stop and inspect the exchanger before you up the CFM.
Expect: Rise typically 35–65 °F — rating plate wins.
If fail: Fix the restriction or the heat-speed setting. The limit is doing its job.
If pass: Airflow in range → step 3 (overfire / limit itself).
3 Overfire, then the limit circuit
Clock the meter / manifold on the stage that is tripping vs the rating plate. Then ohm the limit after it cools — a limit that never recloses is failed. Rollout in the same circuit is a different call (see rollout on this door card).
Expect: Manifold on plate. Limit closed when cool.
E275
Flame out of sequence lockout
Soft lockout after out-of-sequence flame. Same hazard family as E241.
1 Shut the gas cock first
On Lennox EL296V the rod sees flame with the valve de-energized. Shut the cock. If flame stays, the valve is leaking — replace it. Do not jump or energize it as a test. Shut the cock. Valve leak or IFC flame circuit.
Expect: Flame dies when the cock is shut.
If fail: Leaking valve. Replace. Do not leave the unit.
2 Rod and IFC flame circuit
If flame dies with the cock shut, the rod is shorted to ground or the IFC flame circuit is lying. Unplug the rod, inspect ceramic, and check the harness for a rub-through on the collector. 1-hour-class lockout. Do not keep resetting.
Expect: Rod isolated from ground. IFC does not report flame with the rod unplugged.
3 Confirm valve solenoids are actually off
Measure 24 VAC at both solenoids after the call drops. A welded IFC relay or a shorted W will keep a solenoid wet and look like ‘unexpected flame.’ Replace the IFC only after the valve and rod are proven.
Expect: 0 VAC at both solenoids after the call. No flame.
E290
Ignitor circuit fault
Failed ignitor or triggering circuitry. 1-hour soft lockout until flame proves stable.
1 Ohms at the igniter, then at the IFC
On Lennox EL296V measure cold ohms at the igniter plug, then at the IFC connector. An open at the plug is the element or local harness. Open only at the IFC is the harness rub-through on the collector. Ohms the HSI. Open / out of IOM range = replace the ignitor.
Expect: HSI: Cold ohms in the IOM range. 120 VAC during trial.
2 120 VAC during warm-up
Call for heat and measure 120 VAC at the igniter during the warm-up window. 0 V + good ohms = IFC igniter relay. Voltage + no glow = cracked nitride. Good ohms + no 120 VAC during trial = IFC / harness.
Expect: 120 VAC only during warm-up. Visible glow before the valve opens.
3 Do not keep cycling a cracked element
A cracked nitride can ohm ‘good’ cold and open hot. If ohms and voltage are good and there is no glow, replace the igniter. Confirm polarity/ground (this plate’s polarity code) before you condemn a new igniter.
Expect: One clean light after a known-good igniter and a proven ground.
E292
Heat airflow restricted below minimum
VS heat CFM is below the minimum the IFC will allow for this firing rate.
1 Is the wheel free?
Spin the Lennox EL296V blower by hand. Ice, debris, or a seized bearing is not a control problem. Confirm the motor type on this plate — serial ECM, 9-speed tap, or X-13 — before you grab a capacitor. Filter, coil, wheel, return. Media cabinets on Elite jobs are the usual.
Expect: Wheel free. Correct motor family for this IFC.
2 Command vs rotation
Call for G or heat and confirm the IFC is actually requesting CFM (taps, serial, or communicating). Amp the motor. Locked rotor + a good command = motor. No command = IFC / harness / shared data. Some communicating SureLight cards print a different sentence next to E292 — confirm THAT door card before you condemn a motor.
Expect: Command present. Motor amps in range, not locked.
3 Static and the wrong motor
High static will trip current/limit codes and look like a dead motor. Measure TES vs this cabinet. Wrong horsepower or a leftover memory card after a control swap is the other half of this call.
Expect: Static on the blower chart. Matching motor / shared-data card.
E310
Blower unable to start
Indoor blower did not start — seized bearings / obstructed wheel class.
1 Is the wheel free?
Spin the Lennox EL296V blower by hand. Ice, debris, or a seized bearing is not a control problem. Confirm the motor type on this plate — serial ECM, 9-speed tap, or X-13 — before you grab a capacitor. Spin the wheel. Ice, debris, rusted module, unplugged harness.
Expect: Wheel free. Correct motor family for this IFC.
2 Command vs rotation
Call for G or heat and confirm the IFC is actually requesting CFM (taps, serial, or communicating). Amp the motor. Locked rotor + a good command = motor. No command = IFC / harness / shared data. Door-card note: a few revisions park a DAT-sensor sentence on E310. If the card says sensor, treat it as a sensor. If it says wheel/bearings, treat it as a motor.
Expect: Command present. Motor amps in range, not locked.
3 Static and the wrong motor
High static will trip current/limit codes and look like a dead motor. Measure TES vs this cabinet. Wrong horsepower or a leftover memory card after a control swap is the other half of this call.
Expect: Static on the blower chart. Matching motor / shared-data card.
E311
Blower temperature too high
Blower / module overtemp. IFC sheds or parks heat.
1 Airflow before you touch the limit
On Lennox EL296V a limit is airflow or overfire until proven otherwise. Do not replace the limit first. Filter, blower wheel, A-coil, and the heat-speed setting for THIS motor (tap, model plug, or communicating CFM — not a sister SKU chart). Static, wheel rub, module fins packed with dust.
Expect: Rise in the rating-plate window. Static vs this cabinet’s blower chart.
2 Measure static and temperature rise
Total external static vs the Lennox EL296V blower chart for this cabinet size. Supply minus return rise after 8–10 minutes. A new 5" media cabinet or closed supplies will trip this all winter. After a motor swap, confirm you did not put an EL296E CT motor in this VS plug.
Expect: Rise typically 35–65 °F — rating plate wins.
If fail: Fix the restriction or the heat-speed setting. The limit is doing its job.
If pass: Airflow in range → step 3 (overfire / limit itself).
3 Overfire, then the limit circuit
Clock the meter / manifold on the stage that is tripping vs the rating plate. Then ohm the limit after it cools — a limit that never recloses is failed. Rollout in the same circuit is a different call (see rollout on this door card).
Expect: Manifold on plate. Limit closed when cool.
E312
Restricted airflow — cooling / CF
Cooling or continuous-fan CFM is below the setting. Cutback / high-static warning.
1 Airflow before you touch the limit
On Lennox EL296V a limit is airflow or overfire until proven otherwise. Do not replace the limit first. Filter, blower wheel, A-coil, and the heat-speed setting for THIS motor (tap, model plug, or communicating CFM — not a sister SKU chart). Filter and duct. VS motor is already in torque limit (roughly 0–0.8 in. w.c. class).
Expect: Rise in the rating-plate window. Static vs this cabinet’s blower chart.
2 Measure static and temperature rise
Total external static vs the Lennox EL296V blower chart for this cabinet size. Supply minus return rise after 8–10 minutes. A new 5" media cabinet or closed supplies will trip this all winter. Not a heat-call code. Do not chase E312 with a pressure switch.
Expect: Rise typically 35–65 °F — rating plate wins.
If fail: Fix the restriction or the heat-speed setting. The limit is doing its job.
If pass: Airflow in range → step 3 (overfire / limit itself).
3 Overfire, then the limit circuit
Clock the meter / manifold on the stage that is tripping vs the rating plate. Then ohm the limit after it cools — a limit that never recloses is failed. Rollout in the same circuit is a different call (see rollout on this door card).
Expect: Manifold on plate. Limit closed when cool.
Workflows
E229 / E223 / E225 / E227 cluster
The EL296 that will not stay on low, lights hard, or never proves draft.
1 Prove the call and the live code
Photograph the 7-seg and pull E-recall. Order matters: 223 then 229 means low prove failed and the IFC escalated to high-fire light-off.
Expect: Write whatever SureLight 7-seg IFC (E2xx) is showing. Hold the IFC button to a solid E. Last 10 codes, most recent first. Select c and press again while c flashes to erase. Exit at the triple-bar. 7-seg also repeats the active fault.
If fail: No call at the IFC → stat / harness. Do not change gas parts.
2 Isolate the first failed step in the sequence
Clean the inducer pressure port. EL296s clog this port with oxide/dust and throw the whole PS family. Known fix before you replace a switch.
Expect: Trial: HSI (E207 / E290 if the circuit is open) → low-fire valve (E204–E206) → flame (E240 / E270 if no µA).
3 Confirm with a number, then the next part
Two hoses, two switches. A tee is a miswire. Low hose on the low tap only. Trap and PVC next. Then ohms each switch with the matching inducer speed. E228 (calibration) will not pass until the port and hoses are right.
Expect: E-code: Three digits. E229 ≠ E225. Confirm odd extras on the door card. · Inducer port: Open to the collector, not packed with oxide. Two hoses, never teed.
If fail: Stay on this plate. The out-of-range reading is the part.
If pass: Reading in range → the next step in this workflow is the repair.
E250 trips after 10 minutes
Heat works, then drops. Limit string.
1 Prove the call and the live code
VS heat CFM vs the EL296 chart — not a 9-speed tap and not a PSC blower.
Expect: Write whatever SureLight 7-seg IFC (E2xx) is showing. Hold the IFC button to a solid E. Last 10 codes, most recent first. Select c and press again while c flashes to erase. Exit at the triple-bar. 7-seg also repeats the active fault.
If fail: No call at the IFC → stat / harness. Do not change gas parts.
2 Isolate the first failed step in the sequence
Coil and filter. Elite jobs often got a thick media cabinet that starves heat CFM.
Expect: Trial: HSI (E207 / E290 if the circuit is open) → low-fire valve (E204–E206) → flame (E240 / E270 if no µA).
3 Confirm with a number, then the next part
If E270 / E274 also store, walk the rollout string before you up the CFM and leave. Manual-reset rollout is not ‘just a limit.’ E252 stored with E250 = leaving air too hot. Rise and input, then the DAT sensor.
Expect: E-code: Three digits. E229 ≠ E225. Confirm odd extras on the door card. · Inducer port: Open to the collector, not packed with oxide. Two hoses, never teed.
If fail: Stay on this plate. The out-of-range reading is the part.
If pass: Reading in range → the next step in this workflow is the repair.
E270 / E240 ignition
No heat, retries, or weak flame after it lights.
1 Prove the call and the live code
Watch one full try. Write whether the inducer proved, whether the HSI glowed, whether the valve clicked, whether you saw flame.
Expect: Write whatever SureLight 7-seg IFC (E2xx) is showing. Hold the IFC button to a solid E. Last 10 codes, most recent first. Select c and press again while c flashes to erase. Exit at the triple-bar. 7-seg also repeats the active fault.
If fail: No call at the IFC → stat / harness. Do not change gas parts.
2 Isolate the first failed step in the sequence
F menu for rod µA. E240 in run that stacks into E270 / E273 is a rod / ground / manifold problem, not a new IFC.
Expect: Trial: HSI (E207 / E290 if the circuit is open) → low-fire valve (E204–E206) → flame (E240 / E270 if no µA).
3 Confirm with a number, then the next part
HSI ohms (E207 / E290). Open or out of IOM range = ignitor, not the board. E271 / E272 in the same stack means draft died — go back to the E223 cluster. Do not replace the ignitor for a pressure-switch lockout.
Expect: E-code: Three digits. E229 ≠ E225. Confirm odd extras on the door card. · Inducer port: Open to the collector, not packed with oxide. Two hoses, never teed.
If fail: Stay on this plate. The out-of-range reading is the part.
If pass: Reading in range → the next step in this workflow is the repair.
E201 / E202 / E203 after a board or motor swap
New IFC or new blower, no heat, serial-blower codes.
1 Prove the call and the live code
This motor is variable-speed serial, not an EL296E tap motor. The wrong motor in this cabinet throws E202 / E310.
Expect: Write whatever SureLight 7-seg IFC (E2xx) is showing. Hold the IFC button to a solid E. Last 10 codes, most recent first. Select c and press again while c flashes to erase. Exit at the triple-bar. 7-seg also repeats the active fault.
If fail: No call at the IFC → stat / harness. Do not change gas parts.
2 Isolate the first failed step in the sequence
P menu: program the unit size character for THIS cabinet. Hold to store. Let the IFC reset.
Expect: Trial: HSI (E207 / E290 if the circuit is open) → low-fire valve (E204–E206) → flame (E240 / E270 if no µA).
3 Confirm with a number, then the next part
E203 = size never programmed. E202 = size does not match the motor HP the IFC sees. E201 = it cannot even talk to the motor. Harness, motor line voltage, then motor. Do not shotgun the IFC until P is set.
Expect: E-code: Three digits. E229 ≠ E225. Confirm odd extras on the door card. · Inducer port: Open to the collector, not packed with oxide. Two hoses, never teed.
If fail: Stay on this plate. The out-of-range reading is the part.
If pass: Reading in range → the next step in this workflow is the repair.
Test points
E-code
Three digits. E229 ≠ E225. Confirm odd extras on the door card.
Inducer port
Open to the collector, not packed with oxide. Two hoses, never teed.
Flame (F menu)
µA per EL296 card. Rising while running.
HSI
Cold ohms in the IOM range. 120 VAC during trial.
P menu
Unit size stored for this VS cabinet after any IFC or motor swap.
Gotchas
- ML196 looks similar in the basement and uses 1–9 flashes. Pulling an EL296 E250 card onto an ML is how techs replace the wrong part.
- EL296E is the constant-torque Elite — E2xx gas/PS/limit still apply, motor setup does not. A VS motor in an E cabinet (or a CT motor in this V cabinet) is an E202 / E310 call.
- SLP99V is a different communicating IFC. E105 is native there, optional here.
- E270 on this family is max retries / no flame current — not ‘rollout.’ Rollout is the E250 / E274 string.
- E229 is OEM information: no separate high-fire repair. Fix low-fire draft.
- Door-card drift: some 107045 cousins print E110 for low line or swap the E292 / E310 sentence. Believe the card on that unit.
Related plates
- lennox-el296eConstant-torque Elite cousin. Same E2xx gas/PS/limit. Airflow is tap/profile — no serial-blower E201 as the primary motor story.
- lennox-ml196Merit 96% flash (1–9). Same PVC physics, completely different display. Do not use E223 language on an ML LED.
- lennox-slp99vSignature modulating iComfort. E105 is native. Capacity is a percent, not W1/W2.
- lennox-sl280Elite 80% two-stage, metal vent. A 7-seg E223 there is chimney/inducer, not a 96% trap.
Install this plate
Install EL296V as Elite two-stage 96% VS. SureLight 7-seg E2xx. 24V W1/W2; iComfort is optional.
Cat IV PVC · two-stage · VS serial ECM · SureLight E2xx · 24V primary
IFC & vent
- E223 is the 96% draft / pressure path — trap, collector, PVC. Same number on SL280 is a chimney. Do not mix.
- VS serial blower. P-menu / CFM on this IFC, not Merit flash 1–9.
- iComfort stat is optional on EL296. The furnace runs on 24V W1/W2 without it.
First fire
- 1W1 then W2. Watch E2xx live. Prime the trap before you change an inducer.
- 2Set heat CFM in the VS menu for this cabinet (EL296UHV size on the plate).
Do not on Lennox EL296V
- Do not apply ML196 1–9 flash language.
- Do not treat E105 / iComfort pairing as mandatory the way SLP99 does.
Maker literature
FieldBench does not host manufacturer files. Each link opens the maker’s own literature page in a new tab.
- EL296UHE unit information (1246k)ServiceLennox unit information for the EL296UHE family — components, placement, start-up. Full I/O is on LennoxPros.Open manufacturer PDF
- Lennox residential furnacesLiterature searchEL296V / ML196E / SLP99V / SL280V listing. Wiring and I/O: LennoxPros.Open manufacturer PDF
Warranty and bulletins
Affected models, serial range, symptom, remedy, date. Maker files open on the manufacturer site.
Residential limited warranty
warranty sheetLennox furnace warranty
Registered EL / ML / SL / SLP furnace warranty · Dealer claims portal
Dealer portals
dealerWhere remaining service letters live
Current-year service letters not on a public literature page · Maker dealer portal