EL196E
Elite · single-stage · 96% · CT
Lennox Elite single-stage 96% CT (EL196E; EL195E is a related Elite 95/96 single-stage). SureLight 7-seg on many SKUs. One PS. Not EL296E (two-stage) and not ML196 (Merit flash).
Not EL296E / EL296V two-stage. Not ML196 Merit flash. Not EL195NE ULN.
AFUE
Up to 96% single-stage condensing
Staging
One fire rate · one PS
This board
SureLight 7-seg IFC (E2xx, CT motor)
- Same E-prefix as EL296V for gas, PS, HSI, flame, and limits.
- Idle decimal blink, E recall, F flame µA still apply. P-menu unit size is a VS story — this cabinet uses taps.
- E201 serial-blower comm is not the primary motor fault on a stock EL296E. If you see it, someone put a VS motor in this cabinet.
- Confirm any odd extra code on THAT door card.
Same E-menu as EL296V: last 10, c twice to clear.
Universal swap
Current Elite SureLight 107045 is not ICM2813. Older 10M93 / 12L69 only.
Silk: 107045 · 10M9301 · 12L6901
White-Rodgers
- 21D83M-843
Same older SureLight family when the WR sheet names that number.
ICM
- ICM2813
10M9301 / 12L6901 / 56L8401 only — not 107045.
Honeywell
—- ICM2813 ordered because the door says SureLight.
- 50A55-843.
After you pull the dead card
- 1Read the ignition-control number. 107045 → OEM. 10M93 → ICM2813.
Field wiring
Written landings for Lennox EL196E. Not a factory schematic.
Conventional single-stage furnace IFC. One W. Cool Y passes through to the outdoor. No ComfortBridge, no ABCD, no W2.
Written circuit description only — FieldBench does not redraw maker schematics. Example: R to W closes on a heat call; verify 24V at W1 before you change the IFC.
Open manufacturer PDFHeat sequence
- 1Power. L1 / N → IFC → transformer → R120V in, 24V out
- 2Call. Stat W → IFC W~24 VAC
- 3Draft. IFC → inducer → PS close120V motor, 24V prove
- 4Ignite. IFC → HSI120 VAC
- 5Gas. IFC → valve~24 VAC
- 6Flame. Rod → IFCµA DC
- 7Blow. IFC → heat speedAfter flame prove
This indoor
Elite single-stage 96% CT. Not EL296V I+.
24V single-stage heat
Door card is one-stage. Twin terminal empty unless the job is actually twinned.
Wall thermostat
Single-stage heat/cool. W2 from a leftover two-stage stat does nothing useful.
- R24V hot from the IFC24V
- CCommon24V
- WHeat24V
- YCool — also starts the outdoor24V
- GFan24V
Furnace IFC
Transformer lives here. Y out to the outdoor contactor. TWIN empty on a standalone.
- RHot to the stat24V
- CCommon — must reach the outdoor24V
- WHeat call24V
- YCool in / cool out24V
- GBlower24V
- TWINEmpty unless twinned24V
Landing
- 24VIFC Rstat R
~24 VAC hot
- 24VIFC Cstat Coutdoor C
Common
- 24VStat WIFC W
Heat. Stays in this cabinet.
- 24VStat YIFC Youtdoor Y
Cool / contactor
- 24VStat GIFC G
Fan. Does not go outdoors.
IFC harness — single-stage heat
After W arrives. This is the gas train, not the thermostat strip.
Transformer + fuse
120V primary. 24V secondary. Dark stat = fuse / door / transformer first.
- L1 / N120V to the IFCLine
- XFMR24V to R24V
- FUSEOn the IFC24V
24V safety chain
Door, limit, rollout in series. Open anywhere kills heat.
- DOORInterlock24V
- LIMITMain limit — rise / no airflow24V
- ROLLOUTManual reset. Do not jumper and leave24V
Inducer + one pressure switch
W → inducer 120V → PS closes → IFC continues. One hose, one switch.
- IND120V from the IFC to the inducerLine
- PS24V prove back to the IFC24V
- HOSESingle hose. Do not add a second because two-stage boards have two.24V
HSI + single valve
Igniter is 120V from the IFC. Valve is 24V. Flame rod is µA DC back to the IFC.
- HSI120V hot-surface igniter — not 24VLine
- VALVE24V to the single solenoid24V
- FLAMEµA DC on the rod. Not a 24V circuit24V
Constant-torque ECM
Tap / profile motor. Not serial VS. Not a PSC cap.
- TAPSHeat / cool / adjust profiles on the IFC24V
- COMMONMotor common back to the IFC24V
Landing
- LineL1IFCinducer
120 VAC after W
- 24VIFCPSIFC
~24 VAC prove. Open PS = no ignition.
- LineIFCHSI
120 VAC during trial
- 24VIFCgas valve
~24 VAC after flame prove starts
- 24VFlame rodIFC
µA DC. Not 24V.
- LineIFCblower
IFC heat speed / tap
Prove it
- 24 VAC from R to C at the IFC. Fuse / transformer first if the stat is dark.
- W at the IFC under a heat call. Then inducer / igniter / valve per THIS door card.
Do not
- Do not land a ComfortBridge 1/2 or Infinity ABCD pair on this IFC.
- Do not hunt W2 / E8 / high-fire on a one-stage door.
- TWIN must be empty on a standalone.
9-speed tap, PSC, and CT motors share this thermostat landing. The motor is on the IFC harness diagram.
Sequence
- 1
W1 / W2
Same two-stage 96% physics as EL296V: low inducer → low PS → HSI → valve → flame → high inducer → high PS.
- 2
Blower
Heat/cool taps or profiles, not a serial CFM request. Wrong heat tap is the E250 generator.
Faults on this IFC
Step 1, then 2, then 3. Expected reading and the fail branch sit under each check.
E207
HSI sensed open
Hot-surface ignitor circuit measures open.
1 Ohms at the igniter, then at the IFC
On Lennox EL196E measure cold ohms at the igniter plug, then at the IFC connector. An open at the plug is the element or local harness. Open only at the IFC is the harness rub-through on the collector. Cold ohms, then 120 VAC during trial. Same ignitor family as EL296V.
Expect: Nitride cold ohms per THIS door sticker — do not use an 80% Norton chart.
2 120 VAC during warm-up
Call for heat and measure 120 VAC at the igniter during the warm-up window. 0 V + good ohms = IFC igniter relay. Voltage + no glow = cracked nitride.
Expect: 120 VAC only during warm-up. Visible glow before the valve opens.
3 Do not keep cycling a cracked element
A cracked nitride can ohm ‘good’ cold and open hot. If ohms and voltage are good and there is no glow, replace the igniter. Confirm polarity/ground (this plate’s polarity code) before you condemn a new igniter.
Expect: One clean light after a known-good igniter and a proven ground.
E223
Low PS failed OPEN
Low-fire pressure path did not make.
1 Prove inducer and the live code
Do not pull power — that clears the Lennox EL196E active code. Write E223. Is the inducer spinning on this call? Silent inducer is not a pressure switch. Trap, PVC, low hose, inducer port (same known EL296 clog).
Expect: 120 VAC at the inducer on a heat call. Wheel turning.
If fail: 120 VAC missing → IFC / door switch / incoming power. Voltage + dead motor → inducer.
If pass: Inducer running + this code → trap, hose, switch, vent (step 2).
2 Trap, collector, and the hose
A drowned 96% trap will not make collector pressure. Pull the trap, flush it, confirm the collector box and inducer outlet are not full. Hose cracked, off the port, or full of water fakes an open switch. Two hoses, never teed.
Expect: Trap flowing, hose dry and downhill, ports not swapped on a two-switch board.
3 Switch ohms, then vent load
Ohm the pressure switch: NO, must close when that inducer speed is making the collector setpoint. If the switch is good, walk the PVC — bird screen, ice, long 2" run, wind, shared chase.
Expect: LPS / HPS: Two NO switches, two hoses, never teed.
If fail: Replace the open switch only after the vent and trap are proven.
If pass: Switch closes on draft and the code stays → IFC input.
E224
Low PS failed CLOSED
Low switch made with inducer off.
1 Unplug the switch with the inducer off
On Lennox EL196E this code is the switch made when the inducer is not running. Unplug that switch only. Unplug it. Water in the hose or a welded disc.
Expect: Code changes when the harness is open.
If fail: Wrong switch, or the IFC input is shorted.
If pass: Switch/hose path. Go to step 2.
2 Water in the hose vs a welded switch
Blow the hose. Water holding residual draft is more common than a welded switch. Confirm the hose is not teed and not routed uphill. Ohm the switch with the hose off.
Expect: Hose empty. Switch opens with no draft.
3 IFC input last
If the switch ohms open, the hose is dry, and the code does not change with the harness off, the Lennox EL196E IFC input is shorted. Do not keep swapping switches.
Expect: Known-good open switch + open harness = code gone. If not, IFC.
E225
High PS failed OPEN
High-fire prove failed.
1 Prove the high-fire call
Write the live Lennox EL196E code before you pull power. Confirm this IFC is actually commanded to high — W2 at the board, or the staging timer has expired. Inducer actually high? High hose on the high tap only.
Expect: R to W2 ~24 VAC (conventional) or a high-stage request on a communicating stat.
If fail: No high request → thermostat / staging / menu. Not a high-fire pressure switch.
If pass: Go to step 2. Do not jump the high-fire switch to ‘see if it runs.’
2 Prove the inducer actually went high
Listen and amp the inducer on low vs high. No speed-up → IFC high output or inducer winding. Speed-up and this code still live → high-fire PS path (hose, switch, vent).
Expect: LPS / HPS: Two NO switches, two hoses, never teed.
If fail: Measure 120 VAC on the high-speed inducer lead during the high call. 0 V = IFC. Voltage + dead motor = inducer.
3 Isolate the HIGH hose and switch
High-fire hose on the high tap only — a tee with the low switch is the common first-install miss on this dual-switch plate. Blow the hose, confirm it is dry and downhill to the collector. Ohm the high-fire switch: it is NO and must close only on high draft.
Expect: LPS / HPS: Two NO switches, two hoses, never teed.
If fail: Welded open, cracked hose, or water in the line. Replace the failed part — do not leave a jumper.
If pass: Switch and hose good → step 4 (vent / condensate / IFC).
4 Vent, condensate, and the IFC input
High fire needs more draft than a low-fire code ever saw. Check PVC size on this cabinet, shared chase, wind, ice, bird screen, and condensate backing into the collector only on high. If the switch closes on known draft and the code stays, the Lennox EL196E IFC input is the last call.
Expect: Clear vent, dry collector, known-good switch, then IFC.
E226
High PS failed CLOSED
High switch made when it should be open.
1 Prove the switch is made with inducer not on high
On Lennox EL196E this code means the high-fire switch is closed when it should be open. Do not treat it as the low-fire stuck-closed code. Write the live display, then unplug the high-fire switch only.
Expect: Code should change when the high-fire harness is open.
If fail: IFC input shorted or you unplugged the wrong switch.
2 Hose water and a welded switch
Water in the high-fire hose holds residual draft and fakes a closed switch. Route downhill to the collector. Ohm the switch with the hose off — a welded high-fire switch stays closed. Unplug the high switch. Residual draft or welded disc.
Expect: Hose dry. Switch opens with no draft.
3 Confirm the IFC is not commanding high
W2 shorted to W1, a communicating stat stuck on high, or an IFC that never drops inducer speed will keep this code alive. Measure W2 at the board and watch inducer speed after you open the high-fire harness.
Expect: Inducer on low (or off) with W2 open. High-fire switch ohms open.
E227
Low PS opened during trial or run
Made, then dropped mid-cycle.
1 Prove inducer and the live code
Do not pull power — that clears the Lennox EL196E active code. Write E227. Is the inducer spinning on this call? Silent inducer is not a pressure switch. Wind, ice, trap siphon, half-clogged inducer port.
Expect: 120 VAC at the inducer on a heat call. Wheel turning.
If fail: 120 VAC missing → IFC / door switch / incoming power. Voltage + dead motor → inducer.
If pass: Inducer running + this code → trap, hose, switch, vent (step 2).
2 Trap, collector, and the hose
A drowned 96% trap will not make collector pressure. Pull the trap, flush it, confirm the collector box and inducer outlet are not full. Hose cracked, off the port, or full of water fakes an open switch.
Expect: Trap flowing, hose dry and downhill, ports not swapped on a two-switch board.
3 Switch ohms, then vent load
Ohm the pressure switch: NO, must close when that inducer speed is making the collector setpoint. If the switch is good, walk the PVC — bird screen, ice, long 2" run, wind, shared chase.
Expect: LPS / HPS: Two NO switches, two hoses, never teed.
If fail: Replace the open switch only after the vent and trap are proven.
If pass: Switch closes on draft and the code stays → IFC input.
E228
Inducer calibration failure
Could not finish PS calibration.
1 Is the wheel free?
Spin the Lennox EL196E blower by hand. Ice, debris, or a seized bearing is not a control problem. Confirm the motor type on this plate — serial ECM, 9-speed tap, or X-13 — before you grab a capacitor. Fix the port and hoses first. Calibration will not pass on a clogged collector.
Expect: Wheel free. Correct motor family for this IFC.
2 Command vs rotation
Call for G or heat and confirm the IFC is actually requesting CFM (taps, serial, or communicating). Amp the motor. Locked rotor + a good command = motor. No command = IFC / harness / shared data.
Expect: Heat tap: Rise in the plate range. Wrong tap = E250.
3 Static and the wrong motor
High static will trip current/limit codes and look like a dead motor. Measure TES vs this cabinet. Wrong horsepower or a leftover memory card after a control swap is the other half of this call.
Expect: Static on the blower chart. Matching motor / shared-data card.
E229
Ignition on high fire
Low PS did not close; IFC lit on high. OEM: not a separate high-fire repair.
1 Prove the high-fire call
Write the live Lennox EL196E code before you pull power. Confirm this IFC is actually commanded to high — W2 at the board, or the staging timer has expired. Fix E223 physics. Do not start on the high-fire manifold screw.
Expect: R to W2 ~24 VAC (conventional) or a high-stage request on a communicating stat.
If fail: No high request → thermostat / staging / menu. Not a high-fire pressure switch.
If pass: Go to step 2. Do not jump the high-fire switch to ‘see if it runs.’
2 Prove the inducer actually went high
Listen and amp the inducer on low vs high. No speed-up → IFC high output or inducer winding. Speed-up and this code still live → high-fire PS path (hose, switch, vent).
Expect: LPS / HPS: Two NO switches, two hoses, never teed.
If fail: Measure 120 VAC on the high-speed inducer lead during the high call. 0 V = IFC. Voltage + dead motor = inducer.
3 Isolate the HIGH hose and switch
High-fire hose on the high tap only — a tee with the low switch is the common first-install miss on this dual-switch plate. Blow the hose, confirm it is dry and downhill to the collector. Ohm the high-fire switch: it is NO and must close only on high draft.
Expect: LPS / HPS: Two NO switches, two hoses, never teed.
If fail: Welded open, cracked hose, or water in the line. Replace the failed part — do not leave a jumper.
If pass: Switch and hose good → step 4 (vent / condensate / IFC).
4 Vent, condensate, and the IFC input
High fire needs more draft than a low-fire code ever saw. Check PVC size on this cabinet, shared chase, wind, ice, bird screen, and condensate backing into the collector only on high. If the switch closes on known draft and the code stays, the Lennox EL196E IFC input is the last call.
Expect: Clear vent, dry collector, known-good switch, then IFC.
E240
Low flame current — run mode
Weak µA while running.
1 Measure µA while it is running
Do not clean first and guess. Series-µA the rod on Lennox EL196E during a call. Falling µA is oxide, ground, or a dying flame. A hard drop is often the pressure switch or limit opening, not the rod. F menu, rod, ground. Repeating E240 becomes E270 / E273.
Expect: Typically ≥ 1.0 µA DC on this family — confirm the door card. Rising while running.
2 Rod, ground, then gas
Clean the rod with a non-scratch pad — not sandpaper. Chassis ground to burner box and IFC (painted screw and missing star washer are classic). Then manifold on the stage that is dropping and confirm LP conversion leftovers.
Expect: Manifold on the rating plate. Solid burner-box ground.
3 Prove it is not a switch opening
Watch the live Lennox EL196E display when flame drops. A PS or limit code that appears at the drop means the rod was a victim. Inducer, hose, vent wind, or a limit on a wrong heat tap.
Expect: µA stable and the live code stays a flame code — then rod/valve/IFC. Otherwise chase the new code.
E241
Flame out of sequence — flame still present
Flame with valve off. Hazard.
1 Shut the gas cock first
On Lennox EL196E the rod sees flame with the valve de-energized. Shut the cock. If flame stays, the valve is leaking — replace it. Do not jump or energize it as a test. Shut the cock. Leaking valve.
Expect: Flame dies when the cock is shut.
If fail: Leaking valve. Replace. Do not leave the unit.
2 Rod and IFC flame circuit
If flame dies with the cock shut, the rod is shorted to ground or the IFC flame circuit is lying. Unplug the rod, inspect ceramic, and check the harness for a rub-through on the collector.
Expect: Rod isolated from ground. IFC does not report flame with the rod unplugged.
3 Confirm valve solenoids are actually off
Measure 24 VAC at both solenoids after the call drops. A welded IFC relay or a shorted W will keep a solenoid wet and look like ‘unexpected flame.’ Replace the IFC only after the valve and rod are proven.
Expect: 0 VAC at both solenoids after the call. No flame.
E250
Limit switch circuit open
Limit / rollout string open. Open >3 min → E274.
1 Treat this as flame outside the exchanger
Do not reset the Lennox EL196E rollout and walk away. Write the code, kill the call, and look for flame at the burners, crossover, and vestibule before you do anything else.
Expect: No flame outside the exchanger. Burners seated. Crossover lit.
If pass: Still inspect secondary / flue / condensate before you reset.
2 Secondary, condensate, and flue
Blocked secondary, drowned collector, or a plugged flue pushes flame out the front. Pull the inducer/collector look, confirm the trap is flowing, and check PVC/vent. Heat tap vs rise — this is a CT motor, not VS CFM. Media cabinet, coil, filter. Rollout if E274 stores.
Expect: Dry collector, open flue, trap clear.
3 Reset only after the cause is fixed
Manual-reset rollout. Recurring rollout on Lennox EL196E is a CO / fire call — cracked primary, misaligned burners, or a failed secondary. Confirm CO in the space before you leave.
Expect: One clean cycle after the cause is fixed. No second reset as a repair.
E270
Soft lockout — max retries, no flame current
Never saw flame current.
1 Measure µA while it is running
Do not clean first and guess. Series-µA the rod on Lennox EL196E during a call. Falling µA is oxide, ground, or a dying flame. A hard drop is often the pressure switch or limit opening, not the rod. Watch a try. HSI, gas, rod. Not rollout.
Expect: Typically ≥ 1.0 µA DC on this family — confirm the door card. Rising while running.
2 Rod, ground, then gas
Clean the rod with a non-scratch pad — not sandpaper. Chassis ground to burner box and IFC (painted screw and missing star washer are classic). Then manifold on the stage that is dropping and confirm LP conversion leftovers.
Expect: Manifold on the rating plate. Solid burner-box ground.
3 Prove it is not a switch opening
Watch the live Lennox EL196E display when flame drops. A PS or limit code that appears at the drop means the rod was a victim. Inducer, hose, vent wind, or a limit on a wrong heat tap.
Expect: µA stable and the live code stays a flame code — then rod/valve/IFC. Otherwise chase the new code.
E271
Soft lockout — last retry PS opened
Last try died on a pressure switch.
1 Prove inducer and the live code
Do not pull power — that clears the Lennox EL196E active code. Write E271. Is the inducer spinning on this call? Silent inducer is not a pressure switch. Hardened E223 / E227. Port, trap, PVC.
Expect: 120 VAC at the inducer on a heat call. Wheel turning.
If fail: 120 VAC missing → IFC / door switch / incoming power. Voltage + dead motor → inducer.
If pass: Inducer running + this code → trap, hose, switch, vent (step 2).
2 Trap, collector, and the hose
A drowned 96% trap will not make collector pressure. Pull the trap, flush it, confirm the collector box and inducer outlet are not full. Hose cracked, off the port, or full of water fakes an open switch.
Expect: Trap flowing, hose dry and downhill, ports not swapped on a two-switch board.
3 Switch ohms, then vent load
Ohm the pressure switch: NO, must close when that inducer speed is making the collector setpoint. If the switch is good, walk the PVC — bird screen, ice, long 2" run, wind, shared chase.
Expect: LPS / HPS: Two NO switches, two hoses, never teed.
If fail: Replace the open switch only after the vent and trap are proven.
If pass: Switch closes on draft and the code stays → IFC input.
E272
Soft lockout — last recycle PS opened
Ran, then draft dropped.
1 Prove inducer and the live code
Do not pull power — that clears the Lennox EL196E active code. Write E272. Is the inducer spinning on this call? Silent inducer is not a pressure switch. Same two-hose / port-clean cluster.
Expect: 120 VAC at the inducer on a heat call. Wheel turning.
If fail: 120 VAC missing → IFC / door switch / incoming power. Voltage + dead motor → inducer.
If pass: Inducer running + this code → trap, hose, switch, vent (step 2).
2 Trap, collector, and the hose
A drowned 96% trap will not make collector pressure. Pull the trap, flush it, confirm the collector box and inducer outlet are not full. Hose cracked, off the port, or full of water fakes an open switch.
Expect: Trap flowing, hose dry and downhill, ports not swapped on a two-switch board.
3 Switch ohms, then vent load
Ohm the pressure switch: NO, must close when that inducer speed is making the collector setpoint. If the switch is good, walk the PVC — bird screen, ice, long 2" run, wind, shared chase.
Expect: LPS / HPS: Two NO switches, two hoses, never teed.
If fail: Replace the open switch only after the vent and trap are proven.
If pass: Switch closes on draft and the code stays → IFC input.
E273
Soft lockout — last recycle flame failure
Lost flame after it had proven.
1 Measure µA while it is running
Do not clean first and guess. Series-µA the rod on Lennox EL196E during a call. Falling µA is oxide, ground, or a dying flame. A hard drop is often the pressure switch or limit opening, not the rod. Rod µA, ground, manifold after blower-on.
Expect: Typically ≥ 1.0 µA DC on this family — confirm the door card. Rising while running.
2 Rod, ground, then gas
Clean the rod with a non-scratch pad — not sandpaper. Chassis ground to burner box and IFC (painted screw and missing star washer are classic). Then manifold on the stage that is dropping and confirm LP conversion leftovers.
Expect: Manifold on the rating plate. Solid burner-box ground.
3 Prove it is not a switch opening
Watch the live Lennox EL196E display when flame drops. A PS or limit code that appears at the drop means the rod was a victim. Inducer, hose, vent wind, or a limit on a wrong heat tap.
Expect: µA stable and the live code stays a flame code — then rod/valve/IFC. Otherwise chase the new code.
E274
Soft lockout — last recycle limit open or limit >3 min
Hardened E250.
1 Airflow before you touch the limit
On Lennox EL196E a limit is airflow or overfire until proven otherwise. Do not replace the limit first. Filter, blower wheel, A-coil, and the heat-speed setting for THIS motor (tap, model plug, or communicating CFM — not a sister SKU chart). Heat tap, static, rollout string.
Expect: Heat tap: Rise in the plate range. Wrong tap = E250.
2 Measure static and temperature rise
Total external static vs the Lennox EL196E blower chart for this cabinet size. Supply minus return rise after 8–10 minutes. A new 5" media cabinet or closed supplies will trip this all winter.
Expect: Rise typically 35–65 °F — rating plate wins.
If fail: Fix the restriction or the heat-speed setting. The limit is doing its job.
If pass: Airflow in range → step 3 (overfire / limit itself).
3 Overfire, then the limit circuit
Clock the meter / manifold on the stage that is tripping vs the rating plate. Then ohm the limit after it cools — a limit that never recloses is failed. Rollout in the same circuit is a different call (see rollout on this door card).
Expect: Manifold on plate. Limit closed when cool.
E290
Ignitor circuit fault
Failed ignitor or trigger circuit.
1 Ohms at the igniter, then at the IFC
On Lennox EL196E measure cold ohms at the igniter plug, then at the IFC connector. An open at the plug is the element or local harness. Open only at the IFC is the harness rub-through on the collector. HSI ohms and 120 VAC during trial.
Expect: Nitride cold ohms per THIS door sticker — do not use an 80% Norton chart.
2 120 VAC during warm-up
Call for heat and measure 120 VAC at the igniter during the warm-up window. 0 V + good ohms = IFC igniter relay. Voltage + no glow = cracked nitride.
Expect: 120 VAC only during warm-up. Visible glow before the valve opens.
3 Do not keep cycling a cracked element
A cracked nitride can ohm ‘good’ cold and open hot. If ohms and voltage are good and there is no glow, replace the igniter. Confirm polarity/ground (this plate’s polarity code) before you condemn a new igniter.
Expect: One clean light after a known-good igniter and a proven ground.
E201
Indoor blower communication (wrong motor)
Serial-blower comm. Stock EL296E does not use this as the motor story.
1 Reseat the serial plug
On Lennox EL196E this is a communicating / serial ECM, not a tap motor. Kill power, reseat the 14-pin (or OEM serial plug) at the motor and at the IFC. Pins straight, no corrosion. If someone put an EL296V VS motor in this cabinet, E201 / E202 / E310 show up. Put the CT motor back.
Expect: Plug fully seated both ends. Correct motor for this cabinet.
2 Power and the data pair at the motor
Line voltage at the motor, then the serial/data pair continuity. A half-seated plug or a pinched harness throws comm on a good motor. A stock tap motor that will not run is a tap/profile / harness / module problem — not E201.
Expect: Line voltage present. Data pair not shorted to chassis.
3 Motor vs IFC serial driver
Known-good motor still throws this code = Lennox EL196E IFC serial driver. Known-good IFC still throws it = motor module. Do not put a PSC or 9-speed tap motor on a serial IFC.
Expect: One clean CFM request after a known-good pair.
Workflows
EL196E vs EL296E
Elite 96%, count the solenoids.
1 Prove the call and the live code
One solenoid = EL196E. Two = EL296E / EL296V.
Expect: Write whatever SureLight 7-seg IFC (E2xx, CT motor) is showing. Same E-menu as EL296V: last 10, c twice to clear.
If fail: No call at the IFC → stat / harness. Do not change gas parts.
2 Isolate the first failed step in the sequence
E223 on this plate is still trap / PVC — single-stage, one hose.
Expect: Blower: Heat/cool taps or profiles, not a serial CFM request. Wrong heat tap is the E250 generator.
3 Confirm with a number, then the next part
ML196 is Merit flash. If you are counting 1–9 you are not on Elite 7-seg.
Expect: Motor: Tap / common — not an EL296V serial plug. · LPS / HPS: Two NO switches, two hoses, never teed.
If fail: Stay on this plate. The out-of-range reading is the part.
If pass: Reading in range → the next step in this workflow is the repair.
Test points
Motor
Tap / common — not an EL296V serial plug.
LPS / HPS
Two NO switches, two hoses, never teed.
Heat tap
Rise in the plate range. Wrong tap = E250.
Gotchas
- EL296E is the two-stage CT Elite already in the bench.
Related plates
Install this plate
Install Lennox EL196E as Elite · single-stage · 96% · CT.
Elite · single-stage · 96% · CT
This plate — not the sister SKU
- Not EL296E / EL296V two-stage. Not ML196 Merit flash. Not EL195NE ULN.
- EL296E is the two-stage CT Elite already in the bench.
IFC on this door
- Same E-prefix as EL296V for gas, PS, HSI, flame, and limits.
- Idle decimal blink, E recall, F flame µA still apply. P-menu unit size is a VS story — this cabinet uses taps.
- E201 serial-blower comm is not the primary motor fault on a stock EL296E. If you see it, someone put a VS motor in this cabinet.
- Confirm any odd extra code on THAT door card.
Hardware
- AFUE: Up to 96% single-stage condensing
- Staging: One fire rate · one PS
First fire
- 1One solenoid = EL196E. Two = EL296E / EL296V.
- 2E223 on this plate is still trap / PVC — single-stage, one hose.
- 3ML196 is Merit flash. If you are counting 1–9 you are not on Elite 7-seg.
Do not on Lennox EL196E
- Not EL296E / EL296V two-stage. Not ML196 Merit flash. Not EL195NE ULN.
- EL296E is the two-stage CT Elite already in the bench.
Maker literature
FieldBench does not host manufacturer files. Each link opens the maker’s own literature page in a new tab.
- Lennox residential furnacesLiterature searchEL296V / ML196E / SLP99V / SL280V listing. Wiring and I/O: LennoxPros.Open manufacturer PDF
Warranty and bulletins
Affected models, serial range, symptom, remedy, date. Maker files open on the manufacturer site.
Residential limited warranty
warranty sheetLennox furnace warranty
Registered EL / ML / SL / SLP furnace warranty · Dealer claims portal
Dealer portals
dealerWhere remaining service letters live
Current-year service letters not on a public literature page · Maker dealer portal