Lennox
E272
LockoutSoft lockout — last recycle PS opened
Ran, then draft dropped.
Walk E272 in Diagnose
4 plates — walk the one on the cabinet
First check
1 Prove inducer and the live code
Do not pull power — that clears the Lennox EL195NE active code. Write E272. Is the inducer spinning on this call? Silent inducer is not a pressure switch. It ran, then draft dropped. Wind, ice, trap siphon, inducer after light-off.
Expect: Inducer port: Open to the collector, not packed with oxide. Two hoses, never teed.
If fail: 120 VAC missing → IFC / door switch / incoming power. Voltage + dead motor → inducer.
If pass: Inducer running + this code → trap, hose, switch, vent (step 2).
The rest of the walkthrough is Diagnose.
On the plates
- It ran, then draft dropped. Wind, ice, trap siphon, inducer after light-off.
- Same two-hose / port-clean as the E223 cluster.
- Same two-hose / port-clean cluster.