LockoutSoft lockout — last retry failed because PS opened
Last try died on a pressure switch.
Walk E271 in Diagnose
4 plates — walk the one on the cabinet
First check
1 Prove inducer and the live code
Do not pull power — that clears the Lennox EL195NE active code. Write E271. Is the inducer spinning on this call? Silent inducer is not a pressure switch. Treat as a hardened E223 / E227. Port, trap, PVC, inducer.
Expect: Inducer port: Open to the collector, not packed with oxide. Two hoses, never teed.
If fail: 120 VAC missing → IFC / door switch / incoming power. Voltage + dead motor → inducer.
If pass: Inducer running + this code → trap, hose, switch, vent (step 2).
The rest of the walkthrough is Diagnose.
On the plates
- Treat as a hardened E223 / E227. Port, trap, PVC, inducer.
- Do not replace the ignitor because the stack says 270-family.
- Hardened E223 / E227. Port, trap, PVC.