E226
LockoutHigh PS failed CLOSED
High switch made when it should be open.
Walk E226 in Diagnose
4 plates — walk the one on the cabinet
First check
1 Prove the switch is made with inducer not on high
On Lennox EL195NE this code means the high-fire switch is closed when it should be open. Do not treat it as the low-fire stuck-closed code. Write the live display, then unplug the high-fire switch only.
Expect: Code should change when the high-fire harness is open.
If fail: IFC input shorted or you unplugged the wrong switch.
The rest of the walkthrough is Diagnose.
On the plates
- Unplug the high switch only. Water or a welded disc.
- W2 shorted so the IFC thinks it should already be in high.
- Unplug the high switch. Residual draft or welded disc.