Lennox
E225
LockoutHigh PS failed OPEN
High-fire prove failed.
Walk E225 in Diagnose
5 plates — walk the one on the cabinet
First check
1 Prove the high-fire call
Write the live Lennox EL195NE code before you pull power. Confirm this IFC is actually commanded to high — W2 at the board, or the staging timer has expired. Does the inducer actually go high?
Expect: R to W2 ~24 VAC (conventional) or a high-stage request on a communicating stat.
If fail: No high request → thermostat / staging / menu. Not a high-fire pressure switch.
If pass: Go to step 2. Do not jump the high-fire switch to ‘see if it runs.’
The rest of the walkthrough is Diagnose.
On the plates
- Does the inducer actually go high?
- High-fire hose not teed to the low switch. Vent capacity on 110/135 kBtu cabinets.
- Inducer actually high? High hose on the high tap only.
- Inducer actually high? Common vent / wind / liner. High hose not teed to the low switch.