Outdoor fan

Lockout

Failed outdoor fan

Fan not running in cool, or not restarting after defrost in heat. Ices the outdoor in heat; high-heads in cool.

Walk Outdoor fan in Diagnose

Sign in for the next measurement

First check

1 Is it actually in defrost?

On Goodman GSZC18 confirm the board thinks it is in defrost: OD fan off, RV shifted, indoor calling heat/aux. A failed OD fan in heat ices the coil and looks like a defrost board. Voltage at the fan motor / ECM plug when the board is commanding fan.

Expect: Defrost only with a cold outdoor coil, not on every call.

The rest of the walkthrough is Diagnose.

On the plates

  • Voltage at the fan motor / ECM plug when the board is commanding fan.
  • Capacitor only on PSC fans — many of these outdoors are ECM. Confirm the motor family.
  • Blade ice, seized bearing, control output. A fan that dies mid-defrost leaves a block of ice and an LPS/HPS sandwich.

Plates that use Outdoor fan

Same number, other makers

Outdoor fan on Goodman is not the same code on these plates.