GSZC18
Two-stage / communicating heat pump outdoor
Goodman/Amana two-stage or communicating heat pump outdoor (GSZC18 / GSZC16 / ASZC18). Reversing valve plus defrost control live on the outdoor board. Codes are outdoor, not furnace E-codes. GSZB16 is listed as a search alias only — many GSZB units are single-stage with a simpler defrost board.
Not GSXC18 (AC-only, no reversing valve, no defrost). Not GSX14 piston AC. GSZB14 / GSZB16 single-stage heat pumps use a simpler time/temp defrost board — do not apply this communicating / two-stage outdoor chart to those DST boards.
Stages
Two-stage (GSZC) · GSZB single-stage cousins use a different defrost board
Reversing valve
Present. Energize direction is board-specific — read the outdoor diagram
Defrost
Timed / demand on the outdoor control (not a furnace IFC function)
Pair
ComfortBridge indoor (GMVC / AVPTC) or 24V Y1/Y2 + O/B
Sister SKU
GSZC16 · Amana ASZC18 same family
This board
Outdoor heat-pump control · defrost + RV + pressure
- Codes live on the outdoor board. Indoor furnace E2/E9 is a different chart.
- HPS / LPS are pressure. Defrost-sensor and ‘stuck in defrost’ are this board, not the indoor IFC.
- Comm / U-style codes are valid only on a ComfortBridge pair. On 24V Y1/Y2 they mean a miswire.
- Write the outdoor LED/display before you pull the disconnect.
Outdoor LED / display before the disconnect — disconnect clears live. Defrost boards may not store a deep history.
Universal swap
Outdoor HP control (defrost + RV + pressures). No indoor IFC swap.
White-Rodgers
—ICM
—Honeywell
—- Indoor furnace universals (50A55, 50M56U, ICM282B, ICM2811). This is not an IFC.
- Do not ‘adapt’ a furnace board to an outdoor inverter or defrost PCB.
After you pull the dead card
- 1OEM outdoor board. Do not put a furnace universal on a heat-pump outdoor.
Field wiring
Written landings for Goodman GSZC18. Not a factory schematic.
Goodman GSXC / Amana ASXC class. Talks ComfortBridge on 1 and 2 when the indoor is GMVC / AMVC / AVPTC. On a 9-speed 24V indoor it is just Y1/Y2.
Written circuit description only — FieldBench does not redraw maker schematics. Example: R to W closes on a heat call; verify 24V at W1 before you change the IFC.
Open manufacturer PDFThis indoor
Same 1/2 vs Y1/Y2 fork as GSXC18, plus O/B / defrost on the outdoor.
ComfortBridge indoor
GMVC96 / AMVC96 / AVPTC / ARVT96 on the data pair.
CoolCloud / communicating control
Menus live on the indoor. Do not land R/C on 1 and 2.
- 1DataData
- 2DataData
Communicating indoor
One master on the bus. 1/2 polarity matters.
- 1DataData
- 2DataData
- R24V for accessories24V
- CCommon24V
ComfortBridge pair
Indoor 1 and 2 to outdoor 1 and 2. Polarity matters. This is not 24V Y.
- 1DataData
- 2DataData
Outdoor line
208/230 through the disconnect to the contactor line side.
- L1LineLine
- L2LineLine
- GNDEquipment groundLine
Landing
- DataIndoor 1outdoor 1 · indoor 2outdoor 2
Data. Not 24 VAC.
- LineL1 / L2outdoor
208/230
24V indoor (GR9 / AR9 / GMEC)
9-speed or CT indoor. No ComfortBridge menus.
Wall thermostat
Two-stage cool. A single-Y stat never pulls high.
- R24V hot24V
- C24V common24V
- Y1Low-stage cool24V
- Y2High-stage cool24V
- GIndoor fan24V
- WHeat. Stays at the indoor.24V
Indoor IFC / AHU
Y1 and Y2 both have to leave this cabinet on high.
- RTransformer hot24V
- CCommon — run it to the outdoor24V
- Y1Low-stage in / out24V
- Y2High-stage in / out24V
- GBlower24V
- W1Heat24V
Outdoor — Y1 / Y2
Low vs high is these two screws, not an inverter L-code.
- Y1Low-stage request24V
- Y2High-stage request24V
- C24V common24V
Outdoor line
208/230 through the disconnect to the contactor line side.
- L1LineLine
- L2LineLine
- GNDEquipment groundLine
Landing
- 24VStat Y1/Y2/Cindooroutdoor Y1/Y2/C
~24 VAC. Data wire is a miswire.
Prove it
- Identify the indoor first. Communicating indoor = 1/2. 24V indoor = Y1/Y2.
- Comm faults are invalid on a 24V hookup.
Do not
- Do not land data wire on a GR9T96 / AR9T96 / GR9S96.
- Do not apply this to GSX16 / GLXS4B or GXV9S / AXV9S.
1 and 2 are the published ComfortBridge pair.
Sequence
- 1
Y1 cool
Outdoor runs cool capacity. Indoor blower on cool. Reversing valve in the cool position per THIS outdoor diagram.
- 2
O/B reversing valve
Read the outdoor diagram. Do not assume Carrier O-on-cool. Goodman boards have shipped O energized in cool on some and B energized in heat on others. Confirm B vs O on the board silkscreen / IO before you swap a stat or an air handler.
- 3
Heat (HP)
Y (and O/B as required) at the outdoor. Compressor and outdoor fan in heat. Indoor is the condenser. If the outdoor is running in cool while the house wants heat, the RV did not shift or O/B is wrong.
- 4
Defrost timed / demand
Outdoor board terminates defrost on coil sensor and/or time. Sensor open/short or a failed board leaves the unit iced or stuck in defrost (outdoor fan off, RV in cool, steam / water under the unit for too long).
Faults on this IFC
Step 1, then 2, then 3. Expected reading and the fail branch sit under each check.
HPS
High pressure
Discharge / liquid pressure opened the high-pressure switch. In heat this is often indoor airflow; in cool this is outdoor airflow or overcharge.
1 Heat rejection first
On Goodman GSZC18 high pressure is outdoor airflow until proven otherwise. Fan running the right direction, coil clean, fins not folded, no recirc over a fence or through a garage. Mode first. Heat-mode HPS = indoor coil, filter, blower, TXV. Cool-mode HPS = outdoor fan/coil.
Expect: OD fan on, coil clean, discharge air leaving the top/side freely.
2 Head, subcooling, and liquid line
Liquid pressure and liquid-line temperature → SC. High head + high SC = overcharge or non-condensables. High head + low SC = restriction or a dying compressor. Do not add gas because suction is low. SC / SH in the running mode. Restriction vs overcharge.
Expect: SC vs the metering device on this plate (TXV ≠ piston).
3 Restriction vs the switch
Drier, liquid-line kink, TXV inlet screen, or a non-feed indoor coil will stack head. Ohm / jumper-test the HPS only as a momentary prove, then restore it. A switch that opens on a known-good charge and clean coil is the switch. Fan running in that mode? A unit stuck in defrost will look like a cool-mode HPS if you are not watching the RV.
Expect: HPS closed at a normal liquid pressure for this refrigerant and OD ambient.
LPS
Low pressure
Suction dropped out — charge, airflow in the evaporating coil, or a coil iced over in heat.
1 Airflow and freeze before you add gas
On Goodman GSZC18 low pressure / freeze is indoor airflow or a starved coil until proven otherwise. Filter, blower, dirty A-coil, closed supplies. In heat mode, a iced outdoor coil is the same family. Heat mode: outdoor coil iced, outdoor fan, defrost not running. Do not add gas on an iced outdoor.
Expect: Indoor air moving. Coil not iced. OD coil clear in heat.
2 SH / SC after a thaw
Thaw fully. Then SH and SC vs the metering device. Low charge ices a piston. A TXV stuck closed ices with high SH. A restriction downstream of the ports fakes a low-charge chart. Cool mode: indoor airflow, freeze, TXV.
Expect: SH/SC in range for this refrigerant and device after a stable 10-minute run.
3 Leak, TXV, then the LPS
Weigh-in if the chart says undercharge. Soap / electronic leak on joints and the coil. LPS that opens on a known-good charge and a clear coil is the switch — momentary test only, then restore. Weigh-out if the history is a leak. LPS on a heat pump is not automatically ‘low on 410A.’
Expect: Charge on the nameplate. LPS closed at a normal suction for this OD ambient.
Defrost sensor / stuck in defrost
Defrost path
Outdoor coil sensor open/short/out of range, or the board will not leave defrost (fan off, RV shifted to cool, long steam).
1 Is it actually in defrost?
On Goodman GSZC18 confirm the board thinks it is in defrost: OD fan off, RV shifted, indoor calling heat/aux. A failed OD fan in heat ices the coil and looks like a defrost board. Ohms the outdoor coil / defrost sensor vs the board chart. Unplugged sensor is a stuck-defrost classic.
Expect: Defrost only with a cold outdoor coil, not on every call.
2 Coil sensor and termination
Defrost sensor / coil thermistor ohms vs the chart. A sensor hanging off the coil never terminates. Time/temp terminate should end with the fan back on. Board initiating defrost on time with a warm coil? Bad sensor or bad board — prove the sensor first.
Expect: Sensor seated and in range. Defrost ends. Fan restarts.
3 Board vs the valve
If the board never initiates on a frozen coil, force a defrost and watch outputs. If it initiates and never ends, sensor or board. Do not leave it in a forced defrost. Outdoor fan must restart when defrost terminates. A dead fan motor ices the coil again on the next heat call.
Expect: One forced defrost that terminates. Then a normal heat cycle.
RV / no shift
Reversing valve / no shift
Unit runs the opposite mode, or pressures never swap when O/B is commanded.
1 Confirm O/B is energized the way THIS outdoor expects
Most US splits energize O in cool. Some Rheem/Ruud energize B in heat. Read the Goodman GSZC18 diagram, not a generic heat-pump card. Voltage at the RV solenoid during the call that should energize it. Confirm O vs B on THIS outdoor diagram — do not assume Carrier O-on-cool.
Expect: Correct 24 V at the solenoid for the mode that is failing.
2 Listen for the valve, then measure
A healthy valve slams. 24 V at the solenoid on the shift call? Voltage + no slam → valve mechanically stuck. No voltage → stat / defrost board / IFC. Solenoid ohms / mechanical valve stuck. Tap test is not a repair.
Expect: Solenoid voltage present. Pressures swap after the slam.
3 Stuck valve vs a defrost board that never leaves cool
A defrost board stuck in defrost looks like ‘no heat’ with the OD fan off. If the valve is energized and pressures never swap, recover and replace the valve — do not beat on it as a repair. Suction line temp and gauge swap are the prove. Indoor blowing cool on a heat call with the outdoor running is RV or O/B until proven otherwise.
Expect: Mode change on the gauges. OD fan on in heat except during a real defrost.
U / Comm
ComfortBridge / U-style comm
Indoor-outdoor data pair. Valid only on a communicating pair (GMVC / AVPTC / AMVC). On a 24V furnace indoor this is a miswire, not a failed outdoor board.
1 Data pair, not 24 V
On Goodman GSZC18 indoor/outdoor comm is a data pair (AB, S1/S2, U, ComfortBridge, ComfortLink — whatever THIS plate uses). It is not a 24 V Y. Check polarity, continuity, and that nobody landed it on R/C. Data pair polarity, splices, outdoor board power.
Expect: Pair continuous, not shorted to chassis, polarity per the diagram.
2 Power both ends, then the outdoor status
Indoor transformer and outdoor control both alive. Read the outdoor LED / 7-seg. Water in the outdoor control is the usual dead-end after a storm. Indoor must be a communicating IFC. GR9T96 / GMEC96 / GMSS96 cannot clear a U / comm fault on data wire.
Expect: Both controls powered. Outdoor showing a comm or address state, not a blank board.
3 Address / bias, then the control
Communicating plates need a matching indoor address and sometimes a terminating bias. Swap is last: known-good pair + power both ends + correct address. U4-class comm with a 24V furnace: land Y1/Y2/O/B/C or change the indoor. The outdoor will not learn 24V through the data pins.
Expect: Indoor sees the outdoor. No comm code after a power cycle.
Outdoor fan
Failed outdoor fan
Fan not running in cool, or not restarting after defrost in heat. Ices the outdoor in heat; high-heads in cool.
1 Is it actually in defrost?
On Goodman GSZC18 confirm the board thinks it is in defrost: OD fan off, RV shifted, indoor calling heat/aux. A failed OD fan in heat ices the coil and looks like a defrost board. Voltage at the fan motor / ECM plug when the board is commanding fan.
Expect: Defrost only with a cold outdoor coil, not on every call.
2 Coil sensor and termination
Defrost sensor / coil thermistor ohms vs the chart. A sensor hanging off the coil never terminates. Time/temp terminate should end with the fan back on. Capacitor only on PSC fans — many of these outdoors are ECM. Confirm the motor family.
Expect: Sensor seated and in range. Defrost ends. Fan restarts.
3 Board vs the valve
If the board never initiates on a frozen coil, force a defrost and watch outputs. If it initiates and never ends, sensor or board. Do not leave it in a forced defrost. Blade ice, seized bearing, control output. A fan that dies mid-defrost leaves a block of ice and an LPS/HPS sandwich.
Expect: One forced defrost that terminates. Then a normal heat cycle.
Workflows
No heat pump heat
Indoor calling heat, outdoor running in cool or not shifting, house cold.
1 Prove the call and the live code
Confirm the indoor is actually asking the outdoor for HP heat — not W-only furnace heat with Y open.
Expect: Write whatever Outdoor heat-pump control · defrost + RV + pressure is showing. Outdoor LED / display before the disconnect — disconnect clears live. Defrost boards may not store a deep history.
If fail: No call at the IFC → stat / harness. Do not change gas parts.
2 Isolate the first failed step in the sequence
Read O vs B on the outdoor diagram. A Carrier-wired O-on-cool stat on a B-on-heat Goodman board runs the RV backwards.
Expect: O/B reversing valve: Read the outdoor diagram. Do not assume Carrier O-on-cool. Goodman boards have shipped O energized in cool on some and B energized in heat on others. Confirm B vs O on the board silkscreen / IO before you swap a stat or an air handler.
3 Confirm with a number, then the next part
Voltage at the RV solenoid on the call that should energize it. No voltage → board / O-B landing. Voltage, no shift → valve. Outdoor running, indoor blowing cool: RV or O/B. Outdoor silent: power, HPS/LPS, comm. Defrost board stuck in defrost looks like ‘always cool at the outdoor.’ Sensor and terminate before you condemn the RV.
Expect: O vs B: Per the outdoor diagram on THIS unit. Do not assume Carrier O-on-cool. · Defrost sensor: Ohms vs outdoor-board chart. Mounted on the coil circuit.
If fail: Stay on this plate. The out-of-range reading is the part.
If pass: Reading in range → the next step in this workflow is the repair.
Iced outdoor
Outdoor coil is a block of ice in heat. LPS / no heat / water under the unit.
1 Prove the call and the live code
Do not add charge on an iced coil. Recover the picture: fan, sensor, board, time in defrost.
Expect: Write whatever Outdoor heat-pump control · defrost + RV + pressure is showing. Outdoor LED / display before the disconnect — disconnect clears live. Defrost boards may not store a deep history.
If fail: No call at the IFC → stat / harness. Do not change gas parts.
2 Isolate the first failed step in the sequence
Defrost sensor ohms and placement on the coil circuit, not hanging in air.
Expect: O/B reversing valve: Read the outdoor diagram. Do not assume Carrier O-on-cool. Goodman boards have shipped O energized in cool on some and B energized in heat on others. Confirm B vs O on the board silkscreen / IO before you swap a stat or an air handler.
3 Confirm with a number, then the next part
Does the board enter defrost (RV shift, outdoor fan stop, steam)? No → sensor/board. Yes, but fan never returns → fan motor / output. Airflow across the outdoor (snow, leaves, fence recirc) will re-ice a healthy defrost. Low charge ices a heat pump outdoor too — weigh after it is defrosted, not while it is a block.
Expect: O vs B: Per the outdoor diagram on THIS unit. Do not assume Carrier O-on-cool. · Defrost sensor: Ohms vs outdoor-board chart. Mounted on the coil circuit.
If fail: Stay on this plate. The out-of-range reading is the part.
If pass: Reading in range → the next step in this workflow is the repair.
U4 / comm with a 24V furnace indoor
GSZC on data wire into a GR9T96 / GMEC96 / GMSS96.
1 Prove the call and the live code
Those indoor IFCs are not ComfortBridge. U / comm will never clear on data wire into a 9-speed or CT 24V board.
Expect: Write whatever Outdoor heat-pump control · defrost + RV + pressure is showing. Outdoor LED / display before the disconnect — disconnect clears live. Defrost boards may not store a deep history.
If fail: No call at the IFC → stat / harness. Do not change gas parts.
2 Isolate the first failed step in the sequence
Land Y1/Y2, O or B per the outdoor diagram, C, and common. Or change the indoor to GMVC96 / AVPTC.
Expect: O/B reversing valve: Read the outdoor diagram. Do not assume Carrier O-on-cool. Goodman boards have shipped O energized in cool on some and B energized in heat on others. Confirm B vs O on the board silkscreen / IO before you swap a stat or an air handler.
3 Confirm with a number, then the next part
Do not replace the outdoor board to ‘fix U4’ on this mix. The indoor cannot speak the bus. After you convert to 24V, confirm O vs B again. The communicating indoor used to own that decision.
Expect: O vs B: Per the outdoor diagram on THIS unit. Do not assume Carrier O-on-cool. · Defrost sensor: Ohms vs outdoor-board chart. Mounted on the coil circuit.
If fail: Stay on this plate. The out-of-range reading is the part.
If pass: Reading in range → the next step in this workflow is the repair.
Test points
O vs B
Per the outdoor diagram on THIS unit. Do not assume Carrier O-on-cool.
Defrost sensor
Ohms vs outdoor-board chart. Mounted on the coil circuit.
Charge
Nameplate + line-set. SC in cool on a TXV indoor. Weigh-in after a defrost, not into ice.
Data pair
Only on ComfortBridge indoors. Never 24 VAC on the data pins.
Gotchas
- GSZB14/16 single-stage often uses a small pin-style defrost board. Same yard, different chart.
- ASZC18 is the Amana badge twin of GSZC18.
- Amana AVPTC is the communicating air handler that actually belongs on the ComfortBridge pair with this outdoor.
- Furnace W heat with the HP also calling is a dual-fuel / control issue — not an iced outdoor by itself.
Related plates
Install this plate
Install GSZC18 as a two-stage / communicating heat pump. Defrost and O/B live here, not on the furnace IFC.
Two-stage HP · reversing valve · outdoor defrost control · ComfortBridge or 24V Y1/Y2 + O/B
Refrigerant & RV
- TXV indoor required for rating. Weigh-in plus line-set adder.
- O/B direction is board- and stat-specific. Confirm energize-on-cool vs heat on THIS outdoor diagram — do not assume Carrier O-on-cool.
Pairing
- ComfortBridge indoor (GMVC / AVPTC) on the data pair, or 24V Y1/Y2 + O/B from a conventional furnace.
- GSZB / GSZ14 single-stage cousins use a simpler time/temp defrost board — different outdoor control.
First fire
- 1Cooling call first (easier to prove charge), then a heat call and a forced defrost.
- 2Watch RV shift and outdoor fan. Furnace E2 on the indoor is not this board.
Do not on Goodman GSZC18
- Do not treat this as GSXC18 (no RV, no defrost).
- Do not apply inverter L5 / U4 language from DZ20VC unless this plate is actually the inverter SKU.
Maker literature
FieldBench does not host manufacturer files. Each link opens the maker’s own literature page in a new tab.
- GSZC18 product pageProduct pageOpen manufacturer PDF
- GSZC18 specification sheetSpec sheetSearch this plate in the Goodman literature library.Open manufacturer PDF
- Goodman literature libraryLiterature searchSearch Goodman GSZC18 on the maker’s literature page.Open manufacturer PDF
Warranty and bulletins
Affected models, serial range, symptom, remedy, date. Maker files open on the manufacturer site.
Dealer portals
dealerWhere remaining service letters live
Current-year service letters not on a public literature page · Maker dealer portal