Wiring

ComfortBridge two-stage outdoor

1/2 data — or 24V Y1/Y2

1/2 data — or 24V Y1/Y2

Goodman GSXC / Amana ASXC class. Talks ComfortBridge on 1 and 2 when the indoor is GMVC / AMVC / AVPTC. On a 9-speed 24V indoor it is just Y1/Y2.

Written circuit description only — FieldBench does not redraw maker schematics. Example: R to W closes on a heat call; verify 24V at W1 before you change the IFC.

Open manufacturer PDF

ComfortBridge indoor

GMVC96 / AMVC96 / AVPTC / ARVT96 on the data pair.

CoolCloud / communicating control

Menus live on the indoor. Do not land R/C on 1 and 2.

  • 1DataData
  • 2DataData

Communicating indoor

One master on the bus. 1/2 polarity matters.

  • 1DataData
  • 2DataData
  • R24V for accessories24V
  • CCommon24V

ComfortBridge pair

Indoor 1 and 2 to outdoor 1 and 2. Polarity matters. This is not 24V Y.

  • 1DataData
  • 2DataData

Outdoor line

208/230 through the disconnect to the contactor line side.

  • L1LineLine
  • L2LineLine
  • GNDEquipment groundLine

Landing

  • DataIndoor 1outdoor 1 · indoor 2outdoor 2

    Data. Not 24 VAC.

  • LineL1 / L2outdoor

    208/230

24V indoor (GR9 / AR9 / GMEC)

9-speed or CT indoor. No ComfortBridge menus.

Wall thermostat

Two-stage cool. A single-Y stat never pulls high.

  • R24V hot24V
  • C24V common24V
  • Y1Low-stage cool24V
  • Y2High-stage cool24V
  • GIndoor fan24V
  • WHeat. Stays at the indoor.24V

Indoor IFC / AHU

Y1 and Y2 both have to leave this cabinet on high.

  • RTransformer hot24V
  • CCommon — run it to the outdoor24V
  • Y1Low-stage in / out24V
  • Y2High-stage in / out24V
  • GBlower24V
  • W1Heat24V

Outdoor — Y1 / Y2

Low vs high is these two screws, not an inverter L-code.

  • Y1Low-stage request24V
  • Y2High-stage request24V
  • C24V common24V

Outdoor line

208/230 through the disconnect to the contactor line side.

  • L1LineLine
  • L2LineLine
  • GNDEquipment groundLine

Landing

  • 24VStat Y1/Y2/Cindooroutdoor Y1/Y2/C

    ~24 VAC. Data wire is a miswire.

Prove it

  • Identify the indoor first. Communicating indoor = 1/2. 24V indoor = Y1/Y2.
  • Comm faults are invalid on a 24V hookup.

Do not

  • Do not land data wire on a GR9T96 / AR9T96 / GR9S96.
  • Do not apply this to GSX16 / GLXS4B or GXV9S / AXV9S.

1 and 2 are the published ComfortBridge pair.