Goodman
HPS
LockoutHigh pressure
Outdoor airflow, overcharge, or restriction opened the high-pressure switch.
Walk HPS in Diagnose
6 plates — walk the one on the cabinet
First check
1 Heat rejection first
On Goodman GLXS4B high pressure is outdoor airflow until proven otherwise. Fan running the right direction, coil clean, fins not folded, no recirc over a fence or through a garage. Fan running? Coil dirty? SC vs nameplate on a TXV coil.
Expect: OD fan on, coil clean, discharge air leaving the top/side freely.
The rest of the walkthrough is Diagnose.
On the plates
- Outdoor fan running? Coil dirty, recirc, bent fins.
- Subcooling vs indoor TXV sheet. Liquid-line drier / restriction.
- Do not keep resetting HPS into a locked fan.
- Mode first. Heat-mode HPS = indoor coil, filter, blower, TXV. Cool-mode HPS = outdoor fan/coil.
- SC / SH in the running mode. Restriction vs overcharge.
- Fan running in that mode? A unit stuck in defrost will look like a cool-mode HPS if you are not watching the RV.
- Fan running? Coil dirty? SC vs nameplate on a TXV coil.
- OD coil packed. Fan running and correct rotation on 3-phase.
Plates that use HPS
Same number, other makers
HPS on Goodman is not the same code on these plates.