Goodman
EEH
LockoutGrounding error
IFC failed its ground check (sister to EA).
Walk EEH in Diagnose
4 plates — walk the one on the cabinet
First check
1 Hot and neutral at the IFC, not the disconnect
On Goodman GR9S80 polarity/ground is measured at the board. A correctly landed disconnect with a swapped whip at the IFC still throws this. Green ground to cabinet and IFC. Painted screw, missing star washer.
Expect: L1 hot, N neutral, ~120 VAC L1 to N, ~0 VAC N to ground.
The rest of the walkthrough is Diagnose.
On the plates
- Green ground to cabinet and IFC.
- Painted screw, missing star washer.
- If not twinned, nothing should be on the TWIN terminal.
- Green ground to cabinet and IFC. Painted screw, missing star washer.