Goodman
E2
LockoutLow-fire PS open
Inducer is on low and the low-fire switch will not close.
9 plates — walk the one on the cabinet
First check
1 Prove inducer and the live code
Do not pull power — that clears the Goodman GMEC96 active code. Write E2. Is the inducer spinning on this call? Silent inducer is not a pressure switch. Inducer 120 VAC and spinning.
Expect: 120 VAC at the inducer on a heat call. Wheel turning.
If fail: 120 VAC missing → IFC / door switch / incoming power. Voltage + dead motor → inducer.
If pass: Inducer running + this code → trap, hose, switch, vent (step 2).
The rest of the walkthrough is Diagnose.
On the plates
- Inducer spinning? 120 VAC at inducer on a W1 call.
- Collector box, inducer outlet, and condensate trap — this 96% unit will not make pressure with a full trap.
- PVC intake/exhaust (bird screen, ice, long run, wind).
- LPS hose cracked or on the wrong port (low vs high tap).
- Inducer 120 VAC and spinning on the heat call.
- Trap, collector, PVC intake/exhaust, LPS hose on the low tap.
- Shared-data / CFM settings do not create draft. Fix the vent path.
- Inducer 120 VAC and spinning.
Plates that use E2
GRVM97
ComfortBridge · modulating · serial VS · 97%
Pressure-band open / inducer will not prove
Variable inducer is running and the pressure switch / band for that rate never made. Same 96% trap/hose/vent physics as other Amana condensing furnaces — not ‘unplug the low-fire tee.’