Daikin
E2
LockoutLow-stage PS open
Inducer on low, low-fire switch never closes. Classic 96% trap / PVC.
Walk E2 in Diagnose
3 plates — walk the one on the cabinet
First check
1 Prove inducer and the live code
Do not pull power — that clears the Daikin DM80VC active code. Write E2. Is the inducer spinning on this call? Silent inducer is not a pressure switch. This is Category I metal vent. There is no 96% collector or PVC trap to prime.
Expect: 120 VAC at the inducer on a heat call. Wheel turning.
If fail: 120 VAC missing → IFC / door switch / incoming power. Voltage + dead motor → inducer.
If pass: Inducer running + this code → trap, hose, switch, vent (step 2).
The rest of the walkthrough is Diagnose.
On the plates
- Inducer 120 VAC and spinning.
- Collector, trap, PVC intake/exhaust, wind.
- LPS hose on the low tap, not teed to high.
- Open > ~5 min can 1-hour lockout then retry.
- This is Category I metal vent. There is no 96% collector or PVC trap to prime.
- Cap, liner, common-vent tables, inducer wheel, hose on the inducer housing.
Plates that use E2
Same number, other makers
E2 on Daikin is not the same code on these plates.