Daikin codes

Daikin

E2

Lockout

Low-stage PS open

Inducer on low, low-fire switch never closes. Classic 96% trap / PVC.

Walk E2 in Diagnose

3 plates — walk the one on the cabinet

First check

1 Prove inducer and the live code

Do not pull power — that clears the Daikin DM80VC active code. Write E2. Is the inducer spinning on this call? Silent inducer is not a pressure switch. This is Category I metal vent. There is no 96% collector or PVC trap to prime.

Expect: 120 VAC at the inducer on a heat call. Wheel turning.

If fail: 120 VAC missing → IFC / door switch / incoming power. Voltage + dead motor → inducer.

If pass: Inducer running + this code → trap, hose, switch, vent (step 2).

The rest of the walkthrough is Diagnose.

On the plates

  • Inducer 120 VAC and spinning.
  • Collector, trap, PVC intake/exhaust, wind.
  • LPS hose on the low tap, not teed to high.
  • Open > ~5 min can 1-hour lockout then retry.
  • This is Category I metal vent. There is no 96% collector or PVC trap to prime.
  • Cap, liner, common-vent tables, inducer wheel, hose on the inducer housing.

Plates that use E2

Same number, other makers

E2 on Daikin is not the same code on these plates.