2 flash
LockoutIGC 2-flash — example
Example on most Carrier/Bryant packaged CES IGC stickers: pressure switch / draft did not make. Confirm the sticker in THIS heat section — revisions differ.
2 plates — walk the one on the cabinet
First check
1 Prove inducer and the live code
Do not pull power — that clears the Goodman GMSS96 active code. Write 2 flash. Is the inducer spinning on this call? Silent inducer is not a pressure switch. Unplug the PS. Hose water holding residual draft.
Expect: 120 VAC at the inducer on a heat call. Wheel turning.
If fail: 120 VAC missing → IFC / door switch / incoming power. Voltage + dead motor → inducer.
If pass: Inducer running + this code → trap, hose, switch, vent (step 2).
The rest of the walkthrough is Diagnose.
On the plates
- Unplug the PS. Hose water holding residual draft.
- Welded switch or IFC input shorted.
- Type 2-flash / 2 flashes as the IGC shows it. Then walk inducer → hose → switch.
- Inducer spinning. Roof hoses fill with water.
- Do not leave the switch jumped.
Plates that use 2 flash
Same number, other makers
2 flash on Goodman is not the same code on these plates.