Bryant codes

Bryant

2-flash

Protect

IGC 2-flash — example

Example on most Carrier/Bryant packaged CES IGC stickers: pressure switch / draft did not make. Confirm the sticker in THIS heat section — revisions differ.

Walk 2-flash in Diagnose

Sign in for the next measurement

First check

1 Prove inducer and the live code

Do not pull power — that clears the Bryant 581J active code. Write 2-flash. Is the inducer spinning on this call? Silent inducer is not a pressure switch. Type 2-flash / 2 flashes as the IGC shows it. Then walk inducer → hose → switch.

Expect: 120 VAC at the inducer on a heat call. Wheel turning.

If fail: 120 VAC missing → IFC / door switch / incoming power. Voltage + dead motor → inducer.

If pass: Inducer running + this code → trap, hose, switch, vent (step 2).

The rest of the walkthrough is Diagnose.

On the plates

  • Type 2-flash / 2 flashes as the IGC shows it. Then walk inducer → hose → switch.
  • Inducer spinning. Roof hoses fill with water.
  • Do not leave the switch jumped.

Plates that use 2-flash

Same number, other makers

2-flash on Bryant is not the same code on these plates.