Daikin
E8
LockoutHigh-stage PS stuck closed
High-fire switch is made with the inducer not on high. Furnace may stay on low.
Walk E8 in Diagnose
3 plates — walk the one on the cabinet
First check
1 Unplug the switch with the inducer off
On Daikin DM80VC this code is the switch made when the inducer is not running. Unplug that switch only. This is Category I metal vent. There is no 96% collector or PVC trap to prime.
Expect: Code changes when the harness is open.
If fail: Wrong switch, or the IFC input is shorted.
If pass: Switch/hose path. Go to step 2.
The rest of the walkthrough is Diagnose.
On the plates
- This is the second switch — not E1.
- Welded HPS or water in the high hose.
- W2 shorted so the IFC thinks it is already on high.
- This is Category I metal vent. There is no 96% collector or PVC trap to prime.
- Cap, liner, common-vent tables, inducer wheel, hose on the inducer housing.
Plates that use E8
Same number, other makers
E8 on Daikin is not the same code on these plates.