Daikin
E4
HazardFlame when no flame should be present
Rod sees flame with the valve de-energized.
Walk E4 in Diagnose
4 plates — walk the one on the cabinet
First check
1 Shut the gas cock first
On Daikin DM80VC the rod sees flame with the valve de-energized. Shut the cock. If flame stays, the valve is leaking — replace it. Do not jump or energize it as a test. Shut the gas cock. Leaking valve — replace, do not jump.
Expect: Flame dies when the cock is shut.
If fail: Leaking valve. Replace. Do not leave the unit.
The rest of the walkthrough is Diagnose.
On the plates
- Shut the gas cock. Leaking valve — replace, do not jump.
- Flame-sense short or IFC input.
- Shut the cock. Leaking or slow-close valve.
Plates that use E4
Same number, other makers
E4 on Daikin is not the same code on these plates.