Bryant
32
Lockout32 on Comfort 96 — the only PS
If this door card lists 32, it is the same single draft switch as 31 — not 59TP6 low-fire and not a missing high-fire hose. One switch, one hose.
7 plates — walk the one on the cabinet
First check
1 Prove the high-fire call
Write the live Bryant 912S code before you pull power. Confirm this IFC is actually commanded to high — W2 at the board, or the staging timer has expired. Count hoses. One = this chart. Two = you are on a TP6/TN6, not SC5.
Expect: R to W2 ~24 VAC (conventional) or a high-stage request on a communicating stat.
If fail: No high request → thermostat / staging / menu. Not a high-fire pressure switch.
If pass: Go to step 2. Do not jump the high-fire switch to ‘see if it runs.’
The rest of the walkthrough is Diagnose.
On the plates
- Low-fire hose only. Intake termination. Attic PVC slope back to the collector.
- Do not confuse a live 3 1.6 CFM readout with 32.
- Count transducers/hoses.
- Band miss: trap/PVC, then inducer RPM (42).
- Do not order a low-fire switch for this cabinet.
- Trap, collector, low hose, attic PVC.
- Fix 32 before you chase 34.
- Count hoses. One = this chart. Two = you are on a TP6/TN6, not SC5.
Plates that use 32
Same number, other makers
32 on Bryant is not the same code on these plates.