FREEZE

Protect

FREEZING (JADE LCD example)

JADE LCD: FREEZING. Mixed air below the low-limit. Damper drives shut; mechanical cool may lock.

Walk FREEZE in Diagnose

Sign in for the next measurement

First check

1 Damper position vs command

On York ZF look at the economizer before the compressor. Commanded open? Blade actually open? Linkage off the shaft is a rooftop weekly. MAT vs a real probe. A failed MAT lying low is this, not a frozen DX coil.

Expect: Blade matches the module command. Stuck open = overventilation. Stuck closed = no free cooling.

The rest of the walkthrough is Diagnose.

On the plates

  • MAT vs a real probe. A failed MAT lying low is this, not a frozen DX coil.
  • Damper stuck open dumping 30 °F OA on the mixed-air sensor — walk ACT ERROR first.
  • True freeze: indoor airflow and charge after the damper is explained.

Plates that use FREEZE

Same number, other makers

FREEZE on York is not the same code on these plates.