ICP
FREEZE
ProtectFREEZING (JADE LCD example)
JADE LCD: FREEZING. Mixed air below the low-limit. Damper drives shut; mechanical cool may lock.
Walk FREEZE in Diagnose
Sign in for the next measurement
First check
1 Damper position vs command
On ICP PGC look at the economizer before the compressor. Commanded open? Blade actually open? Linkage off the shaft is a rooftop weekly. MAT vs a real probe. A failed MAT lying low is this, not a frozen DX coil.
Expect: Blade matches the module command. Stuck open = overventilation. Stuck closed = no free cooling.
The rest of the walkthrough is Diagnose.
On the plates
- MAT vs a real probe. A failed MAT lying low is this, not a frozen DX coil.
- Damper stuck open dumping 30 °F OA on the mixed-air sensor — walk ACT ERROR first.
- True freeze: indoor airflow and charge after the damper is explained.
Plates that use FREEZE
Same number, other makers
FREEZE on ICP is not the same code on these plates.