Rheem
46
LockoutLow PS open at LOW inducer speed
LPS did not close on low inducer. This is the VA low-fire / low-inducer half of the split TA never printed.
Walk 46 in Diagnose
3 plates — walk the one on the cabinet
First check
1 Prove inducer and the live code
Do not pull power — that clears the Rheem R951V active code. Write 46. Is the inducer spinning on this call? Silent inducer is not a pressure switch. Low-inducer LPS path, intake, trap, inducer low speed.
Expect: 120 VAC at the inducer on a heat call. Wheel turning.
If fail: 120 VAC missing → IFC / door switch / incoming power. Voltage + dead motor → inducer.
If pass: Inducer running + this code → trap, hose, switch, vent (step 2).
The rest of the walkthrough is Diagnose.
On the plates
- Low-inducer LPS path, intake, trap, inducer low speed.
- Do not swap the 45 switch first because a TA chart said ‘45 is low.’