Lennox
F
StatusFlame signal
Menu: live flame current in µA on the 7-seg.
Walk F in Diagnose
2 plates — walk the one on the cabinet
First check
1 Measure µA while it is running
Do not clean first and guess. Series-µA the rod on Lennox EL195NE during a call. Falling µA is oxide, ground, or a dying flame. A hard drop is often the pressure switch or limit opening, not the rod. Use this on an E240 / E270 call instead of guessing the rod.
Expect: Flame (F menu): µA per EL296 card. Rising while running.
The rest of the walkthrough is Diagnose.
On the plates
- Use this on an E240 / E270 call instead of guessing the rod.
- Exits on power reset, hold-to-bars, or 10 minutes.