Lennox
E205
LockoutGas valve control relay shorted
IFC thinks its valve relay contacts are shorted.
Walk E205 in Diagnose
2 plates — walk the one on the cabinet
First check
1 Coil ohms and 24 VAC during trial only
On Lennox EL195NE measure each solenoid. 24 VAC should appear only during trial / the commanded stage. Unplug the valve. If E205 stays, the IFC relay is the fault.
Expect: Coil ohms per the valve sticker. 24 VAC only when the IFC commands that stage.
The rest of the walkthrough is Diagnose.
On the plates
- Unplug the valve. If E205 stays, the IFC relay is the fault.
- If it clears, ohm the valve coil and harness for a short to chassis.