Lennox
E117
ProtectPoor ground
Ground is present but dirty. Warning only — clears ~30 s after it recovers.
Walk E117 in Diagnose
2 plates — walk the one on the cabinet
First check
1 Hot and neutral at the IFC, not the disconnect
On Lennox EL195NE polarity/ground is measured at the board. A correctly landed disconnect with a swapped whip at the IFC still throws this. Same ground path as E112, just not open. Flame µA and HSI both suffer.
Expect: L1 hot, N neutral, ~120 VAC L1 to N, ~0 VAC N to ground.
The rest of the walkthrough is Diagnose.
On the plates
- Same ground path as E112, just not open. Flame µA and HSI both suffer.
- Do not ignore a repeating E117 on an E240 / E270 call.