Lennox
E115
LockoutLow 24V
Secondary below ~18–30 V class. Control restarts if voltage recovers.
Walk E115 in Diagnose
2 plates — walk the one on the cabinet
First check
1 Measure at the IFC under load
On Lennox EL195NE line-voltage codes are incoming power. Measure L1/L2 (or L1/N) at the board while it is trying to run, not just at the disconnect. 24 VAC at the IFC under load. Extra accessories robbing the transformer.
Expect: Voltage in the rating-plate window under load.
The rest of the walkthrough is Diagnose.
On the plates
- 24 VAC at the IFC under load. Extra accessories robbing the transformer.
- Door-switch / shorted valve / undersized VA. Fix the load before you upsize the transformer.