Lennox
E112
LockoutGround not detected
IFC does not see earth ground. Unit shuts down.
Walk E112 in Diagnose
2 plates — walk the one on the cabinet
First check
1 Hot and neutral at the IFC, not the disconnect
On Lennox EL195NE polarity/ground is measured at the board. A correctly landed disconnect with a swapped whip at the IFC still throws this. Green to cabinet and IFC. Painted screw / missing star washer.
Expect: L1 hot, N neutral, ~120 VAC L1 to N, ~0 VAC N to ground.
The rest of the walkthrough is Diagnose.
On the plates
- Green to cabinet and IFC. Painted screw / missing star washer.
- Resumes ~5 s after a real ground is provided.