Lennox
9 flash
LockoutPolarity
L1/N reversed or ground missing.
Walk 9 flash in Diagnose
3 plates — walk the one on the cabinet
First check
1 Hot and neutral at the IFC, not the disconnect
On Lennox ML180 polarity/ground is measured at the board. A correctly landed disconnect with a swapped whip at the IFC still throws this. Hot/neutral at the IFC. Chassis ground.
Expect: L1 hot, N neutral, ~120 VAC L1 to N, ~0 VAC N to ground.
The rest of the walkthrough is Diagnose.
On the plates
- Hot and neutral at the IFC. Chassis ground. Flame sense will not work reversed.
- Hot/neutral at the IFC. Chassis ground.
Plates that use 9 flash
Same number, other makers
9 flash on Lennox is not the same code on these plates.