Suction dropped out the low-pressure switch.
Walk LPS in Diagnose
Sign in for the next measurement
First check
1 Prove inducer and the live code
Do not pull power — that clears the ICP PGC active code. Write LPS. Is the inducer spinning on this call? Silent inducer is not a pressure switch. Charge / leak. Filters and indoor coil first — a dirty rooftop ices like a starved piston.
Expect: 120 VAC at the inducer on a heat call. Wheel turning.
If fail: 120 VAC missing → IFC / door switch / incoming power. Voltage + dead motor → inducer.
If pass: Inducer running + this code → trap, hose, switch, vent (step 2).
The rest of the walkthrough is Diagnose.
On the plates
- Charge / leak. Filters and indoor coil first — a dirty rooftop ices like a starved piston.
- TXV / orifice. Economizer dumping 40 °F OA on the coil can look like a freeze-stat trip.
- Do not add gas because suction is low.
Plates that use LPS
Same number, other makers
LPS on ICP is not the same code on these plates.