Daikin
LPS
LockoutLow pressure
Low-pressure / freeze protection. Charge, indoor airflow, metering.
Walk LPS in Diagnose
2 plates — walk the one on the cabinet
First check
1 Airflow and freeze before you add gas
On Daikin DX16TC low pressure / freeze is indoor airflow or a starved coil until proven otherwise. Filter, blower, dirty A-coil, closed supplies. In heat mode, a iced outdoor coil is the same family. Indoor filter, blower, coil freeze. Do not add gas on a frozen coil.
Expect: Indoor air moving. Coil not iced. OD coil clear in heat.
The rest of the walkthrough is Diagnose.
On the plates
- Do not add gas on a frozen indoor coil.
- Indoor blower running the commanded CFM? Filter, coil.
- Weigh-in on inverter. TXV health check only after the SKU is known.
- Indoor filter, blower, coil freeze. Do not add gas on a frozen coil.
- TXV / restriction. Weigh-out if the history is a leak.
- Low ambient and wind can nuisance-trip LPS on a light load — still prove charge.
Plates that use LPS
Same number, other makers
LPS on Daikin is not the same code on these plates.