Goodman
U / Comm
LockoutComfortBridge / U-style comm
Indoor-outdoor data pair. Valid only on a communicating pair (GMVC / AVPTC / AMVC). On a 24V furnace indoor this is a miswire, not a failed outdoor board.
Walk U / Comm in Diagnose
Sign in for the next measurement
First check
1 Data pair, not 24 V
On Goodman GSZC18 indoor/outdoor comm is a data pair (AB, S1/S2, U, ComfortBridge, ComfortLink — whatever THIS plate uses). It is not a 24 V Y. Check polarity, continuity, and that nobody landed it on R/C. Data pair polarity, splices, outdoor board power.
Expect: Pair continuous, not shorted to chassis, polarity per the diagram.
The rest of the walkthrough is Diagnose.
On the plates
- Data pair polarity, splices, outdoor board power.
- Indoor must be a communicating IFC. GR9T96 / GMEC96 / GMSS96 cannot clear a U / comm fault on data wire.
- U4-class comm with a 24V furnace: land Y1/Y2/O/B/C or change the indoor. The outdoor will not learn 24V through the data pins.