Daikin
idle / Ht1 / Ht2 / CF
StatusStatus, not a fault
Ready, low heat, high heat, or continuous-fan CFM on the triple display.
Walk idle / Ht1 / Ht2 / CF in Diagnose
3 plates — walk the one on the cabinet
First check
1 Confirm this is not a fault
On the Daikin DM80VC this readout (idle / Ht1 / Ht2 / CF) is run status, not a lockout. Write what the display actually shows and whether W/Y/G is present at the IFC.
Expect: Idle / Ht / CF / stage+CFM words change when you apply and remove the call.
If fail: If the word never changes on a real call, the call is not reaching this IFC.
If pass: The board is alive. Diagnose the comfort complaint, not this code.
The rest of the walkthrough is Diagnose.
On the plates
- Do not change the board because it says Ht1 or CF.
- CF is continuous fan, not a capacitor.
- Ht1 forever with a high-stage request → E9 / staging, not a bad status word.