Daikin
d0
LockoutData not yet on network
Communicating pair is wired and the IFC has no shared data (new board, missing memory card, learn not done).
Walk d0 in Diagnose
4 plates — walk the one on the cabinet
First check
1 Read the plug / card on THIS cabinet
On Daikin DM80VC the model plug or shared-data card must match this cabinet size. A 100 kBtu plug in an 80 cabinet overfires and limits. A leftover memory card after a control swap throws d0/d4-class codes. Memory card / ComfortBridge learn for this SKU.
Expect: Plug / card part matches the rating plate and the replacement control bulletin.
The rest of the walkthrough is Diagnose.
On the plates
- Memory card / ComfortBridge learn for this SKU.
- Outdoor and Daikin One actually on the bus? d0 on a standalone 24V job means someone enabled communicating when the network is empty.
- Do not confuse with E0 (ignition lockout).
- Memory card / learn. Empty network if someone landed data wires with no Daikin One / outdoor.
Plates that use d0
Same number, other makers
d0 on Daikin is not the same code on these plates.