Bryant
33
ProtectLimit or rollout open
Airflow or flame-containment. Single-stage heat speed, not TP6 model-plug CFM.
Walk 33 in Diagnose
4 plates — walk the one on the cabinet
First check
1 Treat this as flame outside the exchanger
Do not reset the Bryant 912S rollout and walk away. Write the code, kill the call, and look for flame at the burners, crossover, and vestibule before you do anything else.
Expect: No flame outside the exchanger. Burners seated. Crossover lit.
If pass: Still inspect secondary / flue / condensate before you reset.
The rest of the walkthrough is Diagnose.
On the plates
- Filter, VS heat CFM (setup switches / model plug), coil, return.
- Rollout is manual reset — inspect exchanger before you reset.
- Three minutes → 13.
- Filter, coil, return, heat tap (59SC5) or 18-speed heat selection (59SC6).
- Do not pull a 59TP6 model-plug CFM table onto this motor.
- Held open → 13.
Plates that use 33
Same number, other makers
33 on Bryant is not the same code on these plates.