LockoutLow vs high pressure switch
Two-stage draft path. 31 is the active-stage / draft prove; 32 is low-fire PS. Unlike 59MN7, these are discrete switches.
Sign in for the next measurement
First check
1 Prove inducer and the live code
Do not pull power — that clears the Bryant 935CA active code. Write 31 / 32. Is the inducer spinning on this call? Silent inducer is not a pressure switch. Two hoses, two switches. Do not treat this as a modulating band.
Expect: 120 VAC at the inducer on a heat call. Wheel turning.
If fail: 120 VAC missing → IFC / door switch / incoming power. Voltage + dead motor → inducer.
If pass: Inducer running + this code → trap, hose, switch, vent (step 2).
The rest of the walkthrough is Diagnose.
On the plates
- Two hoses, two switches. Do not treat this as a modulating band.
- 32 = low-fire hose, low inducer, attic PVC/trap/wind.
- High-fire prove fail is the high PS, not a 59MN7 42 band story.
- Trap and collector first — 96% physics.