Bryant codes

Bryant

13 / 33

Protect

Limit

Airflow. 80% coil on top is still a dirty A-coil.

Walk 13 / 33 in Diagnose

4 plates — walk the one on the cabinet

First check

1 Airflow before you touch the limit

On Bryant 800S a limit is airflow or overfire until proven otherwise. Do not replace the limit first. Filter, blower wheel, A-coil, and the heat-speed setting for THIS motor (tap, model plug, or communicating CFM — not a sister SKU chart). Filter, heat speed / VS setup, coil.

Expect: Rise in the rating-plate window. Static vs this cabinet’s blower chart.

The rest of the walkthrough is Diagnose.

On the plates

  • VS heat CFM / setup — not a 9-speed tap.
  • Filter, coil, return. Rollout is manual reset.
  • Heat-speed tap / 18-speed setup, filter, coil.
  • 915SB 33 is the same winter call as Carrier 59SC5.
  • Filter, heat speed / VS setup, coil.

Plates that use 13 / 33

Same number, other makers

13 / 33 on Bryant is not the same code on these plates.