926S
Preferred 96 · single-stage · variable-speed · InteliSense
Bryant Preferred 96 single-stage. VS / 25-speed blower and InteliSense like 926T, but one gas solenoid and one pressure switch. Two-digit IFC. A 32 on this board is not ‘low fire’ — there is no high fire.
Not 926T (two-stage, dual PS, W2). Not 916S Legacy (fixed/18-speed Comfort, no InteliSense VS story). Not 987M / 986T Evolution ABCD.
AFUE
Up to 97% · single-stage condensing
Staging
Single-stage gas valve · one inducer speed · one pressure switch
Blower
Variable / 25-speed ECM · setup, not a 926T two-stage plug map
Control
Two-digit Preferred IFC · 24V · optional InteliSense
This board
Preferred two-digit IFC · single-stage
- Same 11–14, 21–24, 31, 33, 34, 41, 45 family as other Bryant/Carrier two-digit boards.
- One draft switch. 31 is that switch. Door-card 32, if printed, is still the only PS — not a 926T low-fire path.
- No W2 furnace terminal that means high fire. A leftover W2 is unused or an AC stage.
Write the two-digit code before a power cycle. 11 = empty history.
Universal swap
Single-stage but still a VS blower. 50A55 / 50M56U will not drive it.
White-Rodgers
—ICM
—Honeywell
—- 50A55-843 / 50M56U-843 / 50M56X-843 / S9200U1000.
- ICM282B unless the silk is an HK42FZ004–016 and the motor is not VS — it is VS on this plate.
- 926T two-stage IFC. Evolution boards.
After you pull the dead card
- 1OEM Preferred single-stage VS IFC. Do not ‘make’ a 50A55 work on a serial/VS plug.
Field wiring
Written landings for Bryant 926S. Not a factory schematic.
Conventional single-stage furnace IFC. One W. Cool Y passes through to the outdoor. No ComfortBridge, no ABCD, no W2.
Written circuit description only — FieldBench does not redraw maker schematics. Example: R to W closes on a heat call; verify 24V at W1 before you change the IFC.
Open manufacturer PDFHeat sequence
- 1Power. L1 / N → IFC → transformer → R120V in, 24V out
- 2Call. Stat W → IFC W~24 VAC
- 3Draft. IFC → inducer → PS close120V motor, 24V prove
- 4Ignite. IFC → HSI120 VAC
- 5Gas. IFC → valve~24 VAC
- 6Flame. Rod → IFCµA DC
- 7Blow. IFC → heat speedAfter flame prove
This indoor
Preferred single-stage. One W. Not 926T W2.
24V single-stage heat
Door card is one-stage. Twin terminal empty unless the job is actually twinned.
Wall thermostat
Single-stage heat/cool. W2 from a leftover two-stage stat does nothing useful.
- R24V hot from the IFC24V
- CCommon24V
- WHeat24V
- YCool — also starts the outdoor24V
- GFan24V
Furnace IFC
Transformer lives here. Y out to the outdoor contactor. TWIN empty on a standalone.
- RHot to the stat24V
- CCommon — must reach the outdoor24V
- WHeat call24V
- YCool in / cool out24V
- GBlower24V
- TWINEmpty unless twinned24V
Landing
- 24VIFC Rstat R
~24 VAC hot
- 24VIFC Cstat Coutdoor C
Common
- 24VStat WIFC W
Heat. Stays in this cabinet.
- 24VStat YIFC Youtdoor Y
Cool / contactor
- 24VStat GIFC G
Fan. Does not go outdoors.
IFC harness — single-stage heat
After W arrives. This is the gas train, not the thermostat strip.
Transformer + fuse
120V primary. 24V secondary. Dark stat = fuse / door / transformer first.
- L1 / N120V to the IFCLine
- XFMR24V to R24V
- FUSEOn the IFC24V
24V safety chain
Door, limit, rollout in series. Open anywhere kills heat.
- DOORInterlock24V
- LIMITMain limit — rise / no airflow24V
- ROLLOUTManual reset. Do not jumper and leave24V
Inducer + one pressure switch
W → inducer 120V → PS closes → IFC continues. One hose, one switch.
- IND120V from the IFC to the inducerLine
- PS24V prove back to the IFC24V
- HOSESingle hose. Do not add a second because two-stage boards have two.24V
HSI + single valve
Igniter is 120V from the IFC. Valve is 24V. Flame rod is µA DC back to the IFC.
- HSI120V hot-surface igniter — not 24VLine
- VALVE24V to the single solenoid24V
- FLAMEµA DC on the rod. Not a 24V circuit24V
PSC blower + run cap
Heat / cool / park taps on the motor. The cap is on this blower — not the outdoor dual can.
- HEATHeat speed tap24V
- COOLCool speed tap24V
- PARKUnused leads parked24V
- CAPRun capacitor on the blowerCap
Landing
- LineL1IFCinducer
120 VAC after W
- 24VIFCPSIFC
~24 VAC prove. Open PS = no ignition.
- LineIFCHSI
120 VAC during trial
- 24VIFCgas valve
~24 VAC after flame prove starts
- 24VFlame rodIFC
µA DC. Not 24V.
- LineIFCblower
120V tap + cap
Prove it
- 24 VAC from R to C at the IFC. Fuse / transformer first if the stat is dark.
- W at the IFC under a heat call. Then inducer / igniter / valve per THIS door card.
Do not
- Do not land a ComfortBridge 1/2 or Infinity ABCD pair on this IFC.
- Do not hunt W2 / E8 / high-fire on a one-stage door.
- TWIN must be empty on a standalone.
9-speed tap, PSC, and CT motors share this thermostat landing. The motor is on the IFC harness diagram.
Sequence
- 1
W
Inducer → single PS must close (31 if not) → HSI → valve → flame (34) → VS blower.
- 2
No W2 path
There is no high-fire prove and no second solenoid.
Faults on this IFC
Step 1, then 2, then 3. Expected reading and the fail branch sit under each check.
13 / 33
Limit / lockout
Airflow or rollout. 13 is the hardened 33.
1 Treat this as flame outside the exchanger
Do not reset the Bryant 926S rollout and walk away. Write the code, kill the call, and look for flame at the burners, crossover, and vestibule before you do anything else.
Expect: No flame outside the exchanger. Burners seated. Crossover lit.
If pass: Still inspect secondary / flue / condensate before you reset.
2 Secondary, condensate, and flue
Blocked secondary, drowned collector, or a plugged flue pushes flame out the front. Pull the inducer/collector look, confirm the trap is flowing, and check PVC/vent. VS heat CFM / setup — not a 9-speed tap. Filter, coil, return. Rollout is manual reset.
Expect: Dry collector, open flue, trap clear.
3 Reset only after the cause is fixed
Manual-reset rollout. Recurring rollout on Bryant 926S is a CO / fire call — cracked primary, misaligned burners, or a failed secondary. Confirm CO in the space before you leave.
Expect: One clean cycle after the cause is fixed. No second reset as a repair.
14 / 34
Ignition
No flame prove. 14 is the hardened 34.
1 Watch one full try — do not reset
Write the Bryant 926S code. Watch inducer, HSI glow, valve click, flame, µA. The step that dies is the repair. Resetting only burns another try into a harder lockout. HSI, gas, rod, ground.
Expect: W → No W2 path
2 Gas and the valve
Cock open, inlet pressure, then manifold on the stage that is failing vs the rating plate. 24 VAC at the valve during trial? Coil ohms? A valve that never opens looks like a ‘bad igniter’ if you did not watch the sequence.
Expect: Manifold: Single-stage plate value — no low/high pair.
3 Flame prove, then the lockout timer
Glow + valve + no prove → rod, ground, or IFC sense. Prove then drop → µA / PS / limit. Soft lockouts on this family often auto-reset on a long clock — do not sit on resets.
Expect: Stable µA after light-off. No new PS/limit code.
24
Fuse
24 V fuse open.
1 Find the 24 V short before you replace the fuse
On Bryant 926S an open IFC fuse is a short on W, Y, G, HUM, EAC, or a data pair landed on 24 V. Unplug the thermostat / data harness first. Tstat short, HUM/EAC, valve harness.
Expect: Fuse out. 24 V transformer still good. Harness isolated.
2 Replace the fuse with the harness off
New fuse, harness still off. If it holds, the short is in the field wiring or accessory. Plug one circuit back at a time (W, then Y, then HUM/EAC).
Expect: Fuse holds with harness off. Dies when the shorted lead lands.
3 If it blows with the harness off
Short is on the Bryant 926S IFC or the gas-valve harness. Unplug the valve and try once more. Repeat blow with valve unplugged = IFC.
Expect: Do not keep feeding fuses into a welded valve coil or a burned IFC trace.
31
PS / draft
The only pressure switch did not close.
1 Prove inducer and the live code
Do not pull power — that clears the Bryant 926S active code. Write 31. Is the inducer spinning on this call? Silent inducer is not a pressure switch. Trap, collector, PVC, wind, inducer. One hose, one switch.
Expect: 120 VAC at the inducer on a heat call. Wheel turning.
If fail: 120 VAC missing → IFC / door switch / incoming power. Voltage + dead motor → inducer.
If pass: Inducer running + this code → trap, hose, switch, vent (step 2).
2 Trap, collector, and the hose
A drowned 96% trap will not make collector pressure. Pull the trap, flush it, confirm the collector box and inducer outlet are not full. Hose cracked, off the port, or full of water fakes an open switch. Do not hunt a high-fire hose.
Expect: Trap flowing, hose dry and downhill, ports not swapped on a two-switch board.
3 Switch ohms, then vent load
Ohm the pressure switch: NO, must close when that inducer speed is making the collector setpoint. If the switch is good, walk the PVC — bird screen, ice, long 2" run, wind, shared chase.
Expect: Pressure switch: One NO switch. Closed only after inducer is up.
If fail: Replace the open switch only after the vent and trap are proven.
If pass: Switch closes on draft and the code stays → IFC input.
41 / 44
Blower RPM / calibration
VS motor vs setup.
1 Is the wheel free?
Spin the Bryant 926S blower by hand. Ice, debris, or a seized bearing is not a control problem. Confirm the motor type on this plate — serial ECM, 9-speed tap, or X-13 — before you grab a capacitor. Static, filter, correct setup for the coil tons.
Expect: Wheel free. Correct motor family for this IFC.
2 Command vs rotation
Call for G or heat and confirm the IFC is actually requesting CFM (taps, serial, or communicating). Amp the motor. Locked rotor + a good command = motor. No command = IFC / harness / shared data.
Expect: Command present. Motor amps in range, not locked.
3 Static and the wrong motor
High static will trip current/limit codes and look like a dead motor. Measure TES vs this cabinet. Wrong horsepower or a leftover memory card after a control swap is the other half of this call.
Expect: Static on the blower chart. Matching motor / shared-data card.
45
Control lockout
IFC parked. Not Rheem 45.
1 Write the live code and watch one cycle
On Bryant 926S read Preferred two-digit IFC · single-stage before you pull power. Write 45 exactly. Watch one full sequence and note which step dies. Find the root two-digit first.
Expect: W: Inducer → single PS must close (31 if not) → HSI → valve → flame (34) → VS blower.
2 Prove the circuit this code names
Use the Bryant 926S door card and the test points on this plate. Isolate the named switch, sensor, or output with a meter — do not swap the IFC first.
Expect: Pressure switch: One NO switch. Closed only after inducer is up.
3 Confirm with a number, then the next part
If the named part measures good, the IFC input/output or a related code on this same plate is next. Do not apply a sister-SKU chart.
Expect: Pressure switch: One NO switch. Closed only after inducer is up.
Workflows
31 on a 926S
Inducer runs, no ignition.
1 Prove the call and the live code
This is single-stage. One PS. Do not pull a 926T dual-hose card.
Expect: Write whatever Preferred two-digit IFC · single-stage is showing. Write the two-digit code before a power cycle. 11 = empty history.
If fail: No call at the IFC → stat / harness. Do not change gas parts.
2 Isolate the first failed step in the sequence
Trap and PVC first — 96% Preferred still drowns a collector.
Expect: No W2 path: There is no high-fire prove and no second solenoid.
3 Confirm with a number, then the next part
Then inducer 120 VAC and the only hose. If someone landed W2 from an old 926T job, ignore it for furnace staging.
Expect: Pressure switch: One NO switch. Closed only after inducer is up. · Manifold: Single-stage plate value — no low/high pair.
If fail: Stay on this plate. The out-of-range reading is the part.
If pass: Reading in range → the next step in this workflow is the repair.
Test points
Pressure switch
One NO switch. Closed only after inducer is up.
Manifold
Single-stage plate value — no low/high pair.
Gotchas
- Techs treat 926S like 926T and start looking for high-fire. There is none.
- 916S is the Legacy Comfort cousin — similar 31, different blower setup.
Related plates
Install this plate
Install 926S as Preferred 96 single-stage VS. One pressure switch — no W2 furnace path.
Cat IV PVC · single-stage · one PS · VS ECM + model plug · 24V W
Prove & plug
- One PS. 31 is the only draft prove. Do not look for 32-as-low-fire.
- Model plug still required for the VS motor. Wrong plug = 21 / 41.
- 916S / 915S is the Legacy Comfort 96 cousin — similar one-PS idea, different blower and IFC generation.
First fire
- 1W: inducer → 31-path close → HSI → valve → VS heat CFM.
- 2Cap unused W2. Jumping W2 will not create a second stage.
Do not on Bryant 926S
- Do not apply the 926T dual-PS / W2 commissioning.
- Do not pair an Evolution stat and expect ABCD.
Maker literature
FieldBench does not host manufacturer files. Each link opens the maker’s own literature page in a new tab.
- 926S product pageProduct pageOpen manufacturer PDF
- Bryant document searchLiterature searchEnter the full Bryant plate (926TB60100V21, 987MA…). Owner PDFs are public; many I/Os are dealer-gated.Open manufacturer PDF
- Bryant document searchLiterature searchSearch Bryant 926S on the maker’s literature page.Open manufacturer PDF
Warranty and bulletins
Affected models, serial range, symptom, remedy, date. Maker files open on the manufacturer site.
Residential limited warranty
warranty sheetCarrier / Bryant registered heat-exchanger terms
Current 59-series / Evolution / Preferred registered warranty · Limited warranty certificate
Dealer portals
dealerWhere remaining service letters live
Current-year service letters not on a public literature page · Maker dealer portal