Bosch
P0
LockoutHigh outdoor coil temp
T3 outdoor-coil overtemp.
Walk P0 in Diagnose
Sign in for the next measurement
First check
1 Let it cool, then read the drive LED
On Bosch BOVA 2.0 overcurrent / overheat is often a dirty coil, a failed OD fan, or a locked compressor — not a dead inverter. Clear airflow, confirm the OD fan, and read the drive LED before you order a control. Outdoor coil and inverter heat sink clean. Fan running (see E6).
Expect: OD fan running. Coil clean. Drive LED decoded from THIS outdoor’s card.
The rest of the walkthrough is Diagnose.
On the plates
- Outdoor coil and inverter heat sink clean. Fan running (see E6).
- T3/TF readings in the parameter list.