BOVA 2.0
Bosch IDS 2.0 · inverter ducted split · BOVA outdoor + BVA/BAA AHU
Bosch IDS 2.0 / BOVA 2.0 inverter outdoor paired with a BVA / BAA air handler. The indoor–outdoor pair is communicating. The wall thermostat on many jobs is conventional 24 V at the AHU. Charge is weigh-in / the Bosch chart — not piston superheat. Do not apply Daikin U4 or Carrier 31 to this system.
Not Daikin DZ20VC (U4/L5). Not Mitsubishi MXZ. Not a 24V piston 14-SEER with a contactor-only outdoor. Not Climate 5000 ductless (different code set).
Outdoor
BOVA20 / BOVB inverter HP · R-410A · 2–5 ton class
Indoor
BVA / BAA air handler · electric-heat kits with their own limits
Pair wiring
Communicating cable indoor–outdoor. 24V stat typically at the AHU (Y/B/G/W/C)
Charge
Weigh-in + Bosch IDS chart. Not a piston SH target
Example SKU
BVA-36N1 indoor · BOVA20 outdoor
This board
BOVA outdoor inverter PCB + BVA indoor board
- Faults show on the outdoor display (C3, E4, E5, E6, E7, E9, H0, H8, P0, P1, P2, P3, P4, ATL, and inverter L-family). Read the IDS sticker in THIS outdoor.
- Indoor–outdoor comm is the dedicated pair between BVA and BOVA. The wall stat is 24 V at the AHU on most residential jobs. Techs mix these two cables constantly.
- Do not translate these as Daikin U4 or Carrier 31. Bosch letters are Bosch.
- Electric-heat limits live on the AHU heat kit (mechanical limits / sequencers), not as a Daikin E3.
Outdoor display last-fault before you pull the disconnect. Indoor board LEDs if the AHU is the only thing alive.
Universal swap
Inverter ducted split. No WR/ICM furnace IFC.
White-Rodgers
—ICM
—Honeywell
—- Indoor furnace universals (50A55, 50M56U, ICM282B, ICM2811). This is not an IFC.
- Do not ‘adapt’ a furnace board to an outdoor inverter or defrost PCB.
After you pull the dead card
- 1OEM BOVA outdoor inverter control and BVA indoor board. They are a pair — do not mix generations.
Field wiring
Written landings for Bosch BOVA 2.0. Not a factory schematic.
BOVA 2.0 inverter HP. Communicating cable indoor–outdoor. Conventional 24V stat typically at the air handler (Y / B / G / W / C).
Written circuit description only — FieldBench does not redraw maker schematics. Example: R to W closes on a heat call; verify 24V at W1 before you change the IFC.
Open manufacturer PDFThis indoor
24V stat at the Bosch AHU. Comm cable to the BOVA outdoor.
BOVA + AHU
IDS / BOVA outdoor with the matching Bosch air handler.
24V stat at the AHU
Y cool, B heat (Bosch often uses B), G, W aux, C.
- R24V hot24V
- CCommon24V
- YCool24V
- BHeat — confirm on THIS AHU24V
- GFan24V
- WAux24V
BOVA outdoor
Communicating cable to the AHU. Photograph the silk. No furnace IFC universal.
- COMMIndoor–outdoor comm on the silkData
Landing
- 24VStat Y/B/G/W/CAHU 24V strip
~24 VAC at the air handler
- DataAHU commBOVA comm
Data cable. Not thermostat wire logic.
Prove it
- 24V at the AHU under Y or B.
- Read the outdoor silk for the comm cable.
Do not
- Do not apply Mitsubishi S1/S2/S3 or Daikin P1/P2.
- Do not throw a dual run cap.
24V lives at the AHU. The outdoor is a drive on a comm cable.
Sequence
- 1
Stat call
24 V at the AHU (Y cool, B/O reversing, G fan, W strips). The AHU then talks to the outdoor on the comm cable. No Y at the outdoor like a contactor unit.
- 2
Outdoor start
Inverter ramps after the comm handshake. H0 / E9 / blank display with a good 24 V stat is almost always the indoor–outdoor cable, not the stat.
- 3
Heat pump heat
B (or O, per Bosch diagram) must be correct or you get ATL / no HP heat and the strips take over.
- 4
Defrost
Outdoor coil sensors (T3/T4) and the IDS defrost routine. Failed sensors are E4 / C3, not a furnace rollout.
Faults on this IFC
Step 1, then 2, then 3. Expected reading and the fail branch sit under each check.
ATL
Ambient temperature limited
Outdoor T4 outside the allowed window (cool: T4 ≥125°F or <15°F; heat: T4 ≥86°F or <−4°F on IDS 2.0), or the reversing-valve call is wrong so the outdoor thinks it is in the wrong mode.
1 Confirm O/B is energized the way THIS outdoor expects
Most US splits energize O in cool. Some Rheem/Ruud energize B in heat. Read the Bosch BOVA 2.0 diagram, not a generic heat-pump card. Idle ≥5 min, compare T4 on the board to real outdoor temp (10K sensor, ~10 kΩ at 77°F).
Expect: Correct 24 V at the solenoid for the mode that is failing.
2 Listen for the valve, then measure
A healthy valve slams. 24 V at the solenoid on the shift call? Voltage + no slam → valve mechanically stuck. No voltage → stat / defrost board / IFC. Heat call must energize B per the Bosch diagram. Y-only in heat, or B stuck on in cool, produces ATL.
Expect: Solenoid voltage present. Pressures swap after the slam.
3 Stuck valve vs a defrost board that never leaves cool
A defrost board stuck in defrost looks like ‘no heat’ with the OD fan off. If the valve is energized and pressures never swap, recover and replace the valve — do not beat on it as a repair. 18–28 VAC B–C at the outdoor during a heat call.
Expect: Mode change on the gauges. OD fan on in heat except during a real defrost.
C3 / C4
Condenser coil sensor seating
T3 reads implausible vs T4 (T3 < T4 − 3°F for 10 min).
1 Which sensor is this code?
On Bosch BOVA 2.0 C3 / C4 is a specific thermistor — indoor return/pipe, outdoor coil, discharge, or ambient. Unplug that sensor and ohm it vs the OEM temperature/resistance chart. T3 on the outdoor coil U-bend per the diagram, not hanging in air.
Expect: Ohms move with temperature. Not open, not shorted.
2 Seating and the harness
A sensor that ohms good on the bench and fails in the unit is seating or a rubbed harness. Reseat in the well / on the coil, check the plug at the board. T3/T4 10K ohms. 18 SEER has one T3; some 15/20 SEER have T3 and T3L.
Expect: Sensor fully in the well. Harness not pinched.
3 Board input last
Known-good sensor + known-good harness and the code stays = Bosch BOVA 2.0 control input. Do not replace every sensor on the unit.
Expect: Code clears with a known-good sensor at the board.
E4
Temperature sensor fault
T3, T3L, T4, T5, or TF out of range.
1 Which sensor is this code?
On Bosch BOVA 2.0 E4 is a specific thermistor — indoor return/pipe, outdoor coil, discharge, or ambient. Unplug that sensor and ohm it vs the OEM temperature/resistance chart. Identify which sensor the display names.
Expect: Ohms move with temperature. Not open, not shorted.
2 Seating and the harness
A sensor that ohms good on the bench and fails in the unit is seating or a rubbed harness. Reseat in the well / on the coil, check the plug at the board. T3/T4/T3L: 10K. T5/TF: 5K class — use the IDS ohm chart. Open/shorted harness vs failed bulb.
Expect: Sensor fully in the well. Harness not pinched.
3 Board input last
Known-good sensor + known-good harness and the code stays = Bosch BOVA 2.0 control input. Do not replace every sensor on the unit.
Expect: Code clears with a known-good sensor at the board.
E5
High / low voltage protection
Line voltage out of band (IDS: operate ~180–270 V; typical run ≥210 V).
1 Measure at the IFC under load
On Bosch BOVA 2.0 line-voltage codes are incoming power. Measure L1/L2 (or L1/N) at the board while it is trying to run, not just at the disconnect. L1–L2 at the outdoor. A just-pulled disconnect can E5 on the inrush — wait and recheck.
Expect: Voltage in the rating-plate window under load.
2 Drop, breaker, and the whip
Large drop from the disconnect to the IFC is a loose lug or damaged whip. Breaker that will not hold under inducer/blower start is the circuit, not the board. This is line voltage, not a 24 V stat brownout. Still verify 18–28 VAC Y–C at the AHU so you do not chase the drive for a dead transformer.
Expect: Minimal drop. Tight lugs. Correct breaker size.
3 Transformer 24 V last
If line is good and 24 V is low, load the transformer (stat + valve + accessories). A collapsing 24 V looks like a comm or fuse call.
Expect: 24 V holds under load. Line stays in window.
E6
Outdoor DC fan motor
Outdoor fan failed or the board is not driving it.
1 Let it cool, then read the drive LED
On Bosch BOVA 2.0 overcurrent / overheat is often a dirty coil, a failed OD fan, or a locked compressor — not a dead inverter. Clear airflow, confirm the OD fan, and read the drive LED before you order a control. Blade free? Ice/wind lock?
Expect: OD fan running. Coil clean. Drive LED decoded from THIS outdoor’s card.
2 Voltage and compressor windings
Incoming voltage in range (this plate’s line-voltage code). Compressor windings even, no ground. A shorted compressor will kill a new drive. Motor vs board: resistance and drive voltage per the 5-wire or 3-wire diagram on THIS BOVA.
Expect: Balanced windings. No winding to ground. Line voltage stable under load.
3 Charge and the drive last
A starved or flooded compressor will overcurrent. Confirm SH/SC and charge weight. Only then condemn the inverter. A dead outdoor fan becomes P1/P0 next.
Expect: Charge on the nameplate. Drive code gone after a cool-down and a clean coil.
E7
Discharge sensor seating
T5 not tracking (T5 < T3 − 5°F in cool, or similar band in heat, for 10 min) — plug not on the discharge or a real high-discharge event.
1 Which sensor is this code?
On Bosch BOVA 2.0 E7 is a specific thermistor — indoor return/pipe, outdoor coil, discharge, or ambient. Unplug that sensor and ohm it vs the OEM temperature/resistance chart. T5 fully on the discharge tube. 5K sensor.
Expect: Ohms move with temperature. Not open, not shorted.
2 Seating and the harness
A sensor that ohms good on the bench and fails in the unit is seating or a rubbed harness. Reseat in the well / on the coil, check the plug at the board. If T5 is seated and hot, that is charge / restriction / P4 territory — do not just reseat forever.
Expect: Sensor fully in the well. Harness not pinched.
3 Board input last
Known-good sensor + known-good harness and the code stays = Bosch BOVA 2.0 control input. Do not replace every sensor on the unit.
Expect: Code clears with a known-good sensor at the board.
E9
EEPROM fault
Outdoor control EEPROM / memory chip.
1 Write the live code and watch one cycle
On Bosch BOVA 2.0 read BOVA outdoor inverter PCB + BVA indoor board before you pull power. Write E9 exactly. Watch one full sequence and note which step dies. L1–L2 in range. If E9 remains, the outdoor board — not a Daikin indoor IFC.
Expect: Stat call: 24 V at the AHU (Y cool, B/O reversing, G fan, W strips). The AHU then talks to the outdoor on the comm cable. No Y at the outdoor like a contactor unit.
2 Prove the circuit this code names
Do not ‘reprogram’ this like ComfortBridge shared data.
Expect: A measured open, short, or out-of-range reading — not a guess.
3 Confirm with a number, then the next part
If the named part measures good, the IFC input/output or a related code on this same plate is next. Do not apply a sister-SKU chart.
Expect: Stat vs comm: 24 V at the AHU. Communicating pair indoor–outdoor only. Never 24 VAC on the comm pins.
H0
Comm / main control chip
Communication fault in the main control / EEPROM seating. Field: indoor–outdoor handshake and the outdoor board itself.
1 Data pair, not 24 V
On Bosch BOVA 2.0 indoor/outdoor comm is a data pair (AB, S1/S2, U, ComfortBridge, ComfortLink — whatever THIS plate uses). It is not a 24 V Y. Check polarity, continuity, and that nobody landed it on R/C. Dedicated comm cable BVA↔BOVA landed on the comm terminals — not the 24 V stat cable.
Expect: Pair continuous, not shorted to chassis, polarity per the diagram.
2 Power both ends, then the outdoor status
Indoor transformer and outdoor control both alive. Read the outdoor LED / 7-seg. Water in the outdoor control is the usual dead-end after a storm. EEPROM chip fully seated / not backwards on boards that have a plug-in chip.
Expect: Both controls powered. Outdoor showing a comm or address state, not a blank board.
3 Address / bias, then the control
Communicating plates need a matching indoor address and sometimes a terminating bias. Swap is last: known-good pair + power both ends + correct address. L1–L2 in range. H0 that survives a good comm cable and good power is the outdoor board.
Expect: Indoor sees the outdoor. No comm code after a power cycle.
H8
Pressure transducer
Suction PT failed or disagrees with gauges.
1 Heat rejection first
On Bosch BOVA 2.0 high pressure is outdoor airflow until proven otherwise. Fan running the right direction, coil clean, fins not folded, no recirc over a fence or through a garage. PT wiring. Idle PT vs manifold (±50 psi class on IDS).
Expect: OD fan on, coil clean, discharge air leaving the top/side freely.
2 Head, subcooling, and liquid line
Liquid pressure and liquid-line temperature → SC. High head + high SC = overcharge or non-condensables. High head + low SC = restriction or a dying compressor. Do not add gas because suction is low. Supply ~5 VDC on the transducer reference. Bad PT vs bad board.
Expect: SC vs the metering device on this plate (TXV ≠ piston).
3 Restriction vs the switch
Drier, liquid-line kink, TXV inlet screen, or a non-feed indoor coil will stack head. Ohm / jumper-test the HPS only as a momentary prove, then restore it. A switch that opens on a known-good charge and clean coil is the switch.
Expect: HPS closed at a normal liquid pressure for this refrigerant and OD ambient.
P0
High outdoor coil temp
T3 outdoor-coil overtemp.
1 Let it cool, then read the drive LED
On Bosch BOVA 2.0 overcurrent / overheat is often a dirty coil, a failed OD fan, or a locked compressor — not a dead inverter. Clear airflow, confirm the OD fan, and read the drive LED before you order a control. Outdoor coil and inverter heat sink clean. Fan running (see E6).
Expect: OD fan running. Coil clean. Drive LED decoded from THIS outdoor’s card.
2 Voltage and compressor windings
Incoming voltage in range (this plate’s line-voltage code). Compressor windings even, no ground. A shorted compressor will kill a new drive. T3/TF readings in the parameter list.
Expect: Balanced windings. No winding to ground. Line voltage stable under load.
3 Charge and the drive last
A starved or flooded compressor will overcurrent. Confirm SH/SC and charge weight. Only then condemn the inverter.
Expect: Charge on the nameplate. Drive code gone after a cool-down and a clean coil.
P1
High pressure switch
HPS opened (airflow, overcharge, restriction, or failed switch).
1 Heat rejection first
On Bosch BOVA 2.0 high pressure is outdoor airflow until proven otherwise. Fan running the right direction, coil clean, fins not folded, no recirc over a fence or through a garage. Outdoor fan and coil. Indoor filter/coil.
Expect: OD fan on, coil clean, discharge air leaving the top/side freely.
2 Head, subcooling, and liquid line
Liquid pressure and liquid-line temperature → SC. High head + high SC = overcharge or non-condensables. High head + low SC = restriction or a dying compressor. Do not add gas because suction is low. HPS (2 yellow leads on IDS) ohms closed when idle and cool.
Expect: SC vs the metering device on this plate (TXV ≠ piston).
3 Restriction vs the switch
Drier, liquid-line kink, TXV inlet screen, or a non-feed indoor coil will stack head. Ohm / jumper-test the HPS only as a momentary prove, then restore it. A switch that opens on a known-good charge and clean coil is the switch. Charge is weigh-in / Bosch subcooling chart — not piston SH.
Expect: HPS closed at a normal liquid pressure for this refrigerant and OD ambient.
P2
Low pressure / heating discharge SH
Low-pressure protection in cool, or high discharge superheat protection in heat (IDS: <44 psi for 5 min cool; high discharge SH band in heat).
1 Confirm this is not a fault
On the Bosch BOVA 2.0 this readout (P2) is run status, not a lockout. Write what the display actually shows and whether W/Y/G is present at the IFC.
Expect: Idle / Ht / CF / stage+CFM words change when you apply and remove the call.
If fail: If the word never changes on a real call, the call is not reaching this IFC.
If pass: The board is alive. Diagnose the comfort complaint, not this code.
2 Prove the call at the board
Measure R to W / Y / G at the Bosch BOVA 2.0 IFC, not at the thermostat. Communicating plates need the data pair and a live indoor address — 24 V on W is not the test.
Expect: Service valves open. Indoor blower on a cool call; outdoor fan on a heat call.
If fail: Fix the stat, harness, or data pair before you change parts.
3 Watch one full sequence
Leave power on. Watch BOVA outdoor inverter PCB + BVA indoor board through one cycle and write the first real fault that replaces this status word.
Expect: Stat call: 24 V at the AHU (Y cool, B/O reversing, G fan, W strips). The AHU then talks to the outdoor on the comm cable. No Y at the outdoor like a contactor unit.
P3
Compressor overcurrent
Inverter current out of band (tonnage-specific trip on the IDS card).
1 Let it cool, then read the drive LED
On Bosch BOVA 2.0 overcurrent / overheat is often a dirty coil, a failed OD fan, or a locked compressor — not a dead inverter. Clear airflow, confirm the OD fan, and read the drive LED before you order a control. Valves open, coils clean, outdoor fan running, outdoor <125°F.
Expect: OD fan running. Coil clean. Drive LED decoded from THIS outdoor’s card.
2 Voltage and compressor windings
Incoming voltage in range (this plate’s line-voltage code). Compressor windings even, no ground. A shorted compressor will kill a new drive. Overcharge and a locked compressor both P3 — weigh-in and windings before you order a drive.
Expect: Balanced windings. No winding to ground. Line voltage stable under load.
3 Charge and the drive last
A starved or flooded compressor will overcurrent. Confirm SH/SC and charge weight. Only then condemn the inverter.
Expect: Charge on the nameplate. Drive code gone after a cool-down and a clean coil.
P4
High compressor discharge temp
T5 overtemp (IDS trips in steps up to a 230°F-class shutdown).
1 Let it cool, then read the drive LED
On Bosch BOVA 2.0 overcurrent / overheat is often a dirty coil, a failed OD fan, or a locked compressor — not a dead inverter. Clear airflow, confirm the OD fan, and read the drive LED before you order a control. Weigh-in / Bosch chart (undercharge is the usual P4).
Expect: OD fan running. Coil clean. Drive LED decoded from THIS outdoor’s card.
2 Voltage and compressor windings
Incoming voltage in range (this plate’s line-voltage code). Compressor windings even, no ground. A shorted compressor will kill a new drive. Valves open, indoor blower, outdoor coil, T5 seated.
Expect: Balanced windings. No winding to ground. Line voltage stable under load.
3 Charge and the drive last
A starved or flooded compressor will overcurrent. Confirm SH/SC and charge weight. Only then condemn the inverter.
Expect: Charge on the nameplate. Drive code gone after a cool-down and a clean coil.
AHU heat limit
Electric heat limits on the BVA
Strip kit opened a limit / sequencer. This is AHU airflow or a bad element, not a BOVA P-code.
1 Is aux actually being requested?
On Bosch BOVA 2.0 confirm W / E / aux at the indoor control. A heat-pump call with a communicating board that thinks it needs strips is a config / outdoor issue first. Filter, blower, heat-kit size vs the BVA nameplate.
Expect: Aux request present only when it should be.
2 Sequencer and each element
24 VAC at each sequencer coil, then line through each element. Open element vs a dead sequencer are different parts. Limit on a strip is airflow or a failed limit. W at the AHU calling strips because HP failed (RV, sensors, ATL) — fix the HP before you upsize strips.
Expect: Each element comes on in sequence. Limits closed.
3 Airflow across the strips
Strips without enough CFM open limits immediately. Confirm blower heat/aux tap or communicating electric-heat CFM before you change sequencers. No Carrier 33 and no Daikin E3 on this limit string.
Expect: Blower on before or with the first element. Limits stay closed.
Workflows
Outdoor not starting
AHU alive, outdoor silent. Techs mixed the comm cable with the 24V stat.
1 Prove the call and the live code
24 V stat lives at the AHU. Y/B/G/W/C there should look like a conventional heat pump.
Expect: Write whatever BOVA outdoor inverter PCB + BVA indoor board is showing. Outdoor display last-fault before you pull the disconnect. Indoor board LEDs if the AHU is the only thing alive.
If fail: No call at the IFC → stat / harness. Do not change gas parts.
2 Isolate the first failed step in the sequence
Indoor–outdoor is the dedicated comm cable on the Bosch comm terminals. It is not R/Y to the outdoor contactor — there is no contactor.
Expect: Outdoor start: Inverter ramps after the comm handshake. H0 / E9 / blank display with a good 24 V stat is almost always the indoor–outdoor cable, not the stat.
3 Confirm with a number, then the next part
If someone landed the stat on the outdoor and the comm pair on the stat, H0/E9/blank outdoor is the result. Fix the landings before you order a board. Then E5 line voltage and E6 fan. Then inverter codes on the door card.
Expect: Stat vs comm: 24 V at the AHU. Communicating pair indoor–outdoor only. Never 24 VAC on the comm pins. · Charge: Recover and weigh. Bosch IDS chart / nameplate + line-set. Not piston SH.
If fail: Stay on this plate. The out-of-range reading is the part.
If pass: Reading in range → the next step in this workflow is the repair.
No heat in HP mode
Strips run or the house is cold; outdoor idle or ATL/EA-class.
1 Prove the call and the live code
Is B (reversing) actually energized on a heat call at the AHU and present where Bosch wants it? Wrong O/B is ATL or cool-mode outdoor in January.
Expect: Write whatever BOVA outdoor inverter PCB + BVA indoor board is showing. Outdoor display last-fault before you pull the disconnect. Indoor board LEDs if the AHU is the only thing alive.
If fail: No call at the IFC → stat / harness. Do not change gas parts.
2 Isolate the first failed step in the sequence
Outdoor sensors T3/T4/T5 (E4/C3/E7) and PT (H8) before you condemn the 4-way.
Expect: Outdoor start: Inverter ramps after the comm handshake. H0 / E9 / blank display with a good 24 V stat is almost always the indoor–outdoor cable, not the stat.
3 Confirm with a number, then the next part
If the AHU is on W strips, find out why the HP gave up — do not leave it as an electric furnace. Charge is weigh-in / Bosch chart. A ‘2 °F SH piston’ top-off is how these P4/P2.
Expect: Stat vs comm: 24 V at the AHU. Communicating pair indoor–outdoor only. Never 24 VAC on the comm pins. · Charge: Recover and weigh. Bosch IDS chart / nameplate + line-set. Not piston SH.
If fail: Stay on this plate. The out-of-range reading is the part.
If pass: Reading in range → the next step in this workflow is the repair.
Test points
Stat vs comm
24 V at the AHU. Communicating pair indoor–outdoor only. Never 24 VAC on the comm pins.
Charge
Recover and weigh. Bosch IDS chart / nameplate + line-set. Not piston SH.
Sensors
T3/T4 10K, T5 5K class, PT ~5 V reference. Use the IDS parameter list.
Gotchas
- Do not invent Daikin U4 or Carrier 31 on a BOVA display.
- BOVB / BAA / BVA-36N1 are this IDS 2.0 pair, not a different code family.
- Inverter L-family codes (LO–L9 on some boards) are on the outdoor drive — read the IDS card; they are not Daikin L5.
Related plates
Install this plate
Install BOVA 2.0 + BVA/BAA as Bosch IDS. Communicating outdoor–indoor cable. 24V stat typically at the AHU.
Inverter ducted HP · R-410A 2–5 ton · BOVA20 outdoor · BVA-36N1 typical indoor · weigh-in + Bosch IDS chart
Pair & charge
- Communicating cable indoor–outdoor (not a Mitsubishi S-wire, not ComfortBridge). 24V Y/B/G/W/C at the air handler.
- Weigh-in + Bosch IDS charge chart. Not a piston 14-SEER SH target.
- Electric-heat kits on BVA/BAA have their own limits and breakers — use the indoor I/O.
First fire
- 1Confirm comms between BOVA and BVA before a long charge debate.
- 2Cool, heat, then a heat-kit call if strips are installed.
Do not on Bosch BOVA 2.0
- Do not apply Daikin U4/L5 or Mitsubishi P-codes.
- Do not use Climate 5000 ductless literature on this ducted IDS.
Maker literature
FieldBench does not host manufacturer files. Each link opens the maker’s own literature page in a new tab.
- Bosch Inverter Ducted Split familyProduct pageIDS / BOVA outdoor + BVA/BAA air handler.Open manufacturer PDF
- Bosch heat-pump manualsLiterature searchIDS / BOVA / BVA install and service PDFs. Pick BOVA 2.0, not Climate 5000 ductless.Open manufacturer PDF