LockoutPressure transducer
Suction PT failed or disagrees with gauges.
Walk H8 in Diagnose
Sign in for the next measurement
First check
1 Heat rejection first
On Bosch BOVA 2.0 high pressure is outdoor airflow until proven otherwise. Fan running the right direction, coil clean, fins not folded, no recirc over a fence or through a garage. PT wiring. Idle PT vs manifold (±50 psi class on IDS).
Expect: OD fan on, coil clean, discharge air leaving the top/side freely.
The rest of the walkthrough is Diagnose.
On the plates
- PT wiring. Idle PT vs manifold (±50 psi class on IDS).
- Supply ~5 VDC on the transducer reference. Bad PT vs bad board.